Plan Review Details - Permit 18060124
Plan Review Stops For Permit 18060124
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-26 Cont ID  
Sent By shill Date 2019-03-26 Time 18:04 Rev Time 0.00
Received By shill Date 2019-03-26 Time 17:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 19:15 Rev Time 0.00
Received By shill Date 2018-06-16 Time 19:14 Sent To  
Notes
2018-06-16 19:15:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. IT APPEARS THAT THE PROPOSED TANK IS OUTDOORS. FBC B
 1609, PROVIDE A DETAIL FOR HOW THE TANK WILL BE
 ANCHORED TO RESIST OVERTURNING AND SLIDING.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By scaldero Date 2019-03-11 Time 10:23 Rev Time 0.00
Received By scaldero Date 2019-03-11 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-11 Cont ID  
Sent By scaldero Date 2018-06-11 Time 10:47 Rev Time 0.00
Received By scaldero Date 2018-06-11 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-26 Cont ID  
Sent By shill Date 2019-03-26 Time 18:05 Rev Time 0.00
Received By shill Date 2019-03-08 Time 14:05 Sent To  
Notes
2019-03-08 14:05:50B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-13 Cont ID  
Sent By mcruz Date 2018-07-13 Time 12:01 Rev Time 0.00
Received By mcruz Date 2018-07-13 Time 12:01 Sent To PC
Notes
2018-06-07 09:25:04B08

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-26 Cont ID  
Sent By jesmith Date 2019-03-26 Time 11:46 Rev Time 0.00
Received By jesmith Date 2019-03-26 Time 10:38 Sent To  
Notes
2019-03-26 11:46:46APPROVED
 PLUMBING PROVISO
 RE: PERMIT 18060124 1009 BANYAN AVENUE
 SCOPE IS LIMITED TO REPLACEMENT OF TWO (2) EXISTING
 PROCESS TANKS. CONNECT BY MEANS OF A COUPLING TO
 EXISTING PIPING.
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL
 THE FOLLOWING SHEETS HAVE BEEN REVIEWED FOR COMPLIANCE
 WITH LOCAL AND NATIONAL PLUMBING CODES
 1. ATTACHMENT 1; TANK LOAD & ANCHOR BOLT DETAIL. (1
 PAGE)
 2. ATTACHMENT 2; SITE PLAN (1 PAGE)
 3. ATTACHMENT 3; RECORD DRAWINGS (11 PAGES)
 4. ATTACHMENT 4; TANK MANUFACTURER QUOTE (2 PAGES)
 5. ATTACHMENT 5; TANK MANUFACTURER DESIGN
 SPECIFICATIONS (4 PAGES)
 6. ATTACHMENT 6; CLARIFOC A-210P SAFETY DATA SHEET (13
 PAGES)

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-27 Cont ID  
Sent By gjohnson Date 2018-06-27 Time 07:46 Rev Time 0.00
Received By gjohnson Date 2018-06-27 Time 06:10 Sent To  
Notes
2018-06-27 08:01:371ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE A PIPING DIAGRAM THATS IS A MIN 1/8IN
 SCALE AND LEGIBLE THE ONE THAT WAS PROVIDED IS NOT. PER
 WPB AMEND TO FBC 107.2.1.3
 2. PROVIDE SIT PLAN THE SAT PHOTOGRAPH IS NOT CLEAR.
 PER WPB AMEND TO FBC 107.2.1.3, 107.2.5
 3. PLEASE INDICATE ON THE MANUFACTURE SPEC THE MODEL OF
 THE TANK AND TIE DOWN THAT YOU ARE USING THE PROPOSAL
 AND SPEC DON'T MATCH UP. PER PER WPB AMEND TO
 FBC107.2.1
 4. PROVIDE MSDS SHEETS FOR CHEMICAL STORED IN TANKS.
 PER WPB AMEND TO FBC107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2018-07-13 Cont ID  
Sent By AA Date 2018-07-13 Time 12:00 Rev Time 0.00
Received By mcruz Date 2018-07-13 Time 11:59 Sent To PC
Notes
2018-07-13 12:00:41ZONING REVIEW IS N/A. TANKS BEING REPLACED ARE SAME
 SIZE/CAPACITY AT SAME LOCATION.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  