Plan Review Details - Permit 18060073
Plan Review Stops For Permit 18060073
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By rmcdouga Date 2018-07-25 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2018-07-25 Time 07:06 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By rmcdouga Date 2018-06-26 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2018-06-26 Time 16:14 Sent To E
Notes
2018-06-26 16:20:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE NOT ANY 16KW GENERAC MODELS LISTED IN THE
 GENERATOR TABLE ON THE AMERICAST GENERATOR PAD
 ENGINEERING THAT WAS SUBMITTED. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-28 Cont ID  
Sent By fgiaquin Date 2018-06-28 Time 07:17 Rev Time 0.00
Received By fgiaquin Date 2018-06-27 Time 06:08 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-07-27 Cont ID  
Sent By tklarge Date 2018-07-25 Time 05:26 Rev Time 0.00
Received By jleahy Date 2018-07-25 Time 05:02 Sent To  
Notes
2018-07-25 05:26:071) LIST THE BTU LOAD OF THE EXISTING POOL HEATER AND
 THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). 2ND
 REQUEST.
 2) SHOW THE GAS METER ON THE GAS DRAWING AND THE
 DISTANCE FROM THE GAS METER TO THE FARTHEST MP
 REGULATOR.2ND REQUEST.
 3) SHOW THE TYPE & SIZE OF PIPE FROM THE EXISTING GAS
 METER TO THE POOL HEATER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-07-27 Cont ID  
Sent By tklarge Date 2018-06-22 Time 14:43 Rev Time 0.00
Received By jleahy Date 2018-06-22 Time 14:05 Sent To  
Notes
2018-06-22 14:16:311) LIST THE BTU LOAD OF THE GENERATOR AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE GAS
 SYSTEM ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1,
 402.4.3 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2,
 G2413.4.3.
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.
 4) THE SUBMITTED SURVEY SHOWS AN EXISTING GAS POOL
 HEATER. CITY RECORDS DO NOT SHOW A HISTORY OF ANY GAS
 PERMITS ISSUED FOR THIS PROPERTY. THE POOL HEATER AND
 ANY OTHER GAS APPLIANCES WILL NEED TO BE PERMITTED.
 5) THE PLANS INDICATE AN EXISTING GAS POOL HEATER. THE
 BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO
 THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 6) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-25 Cont ID  
Sent By rmcdouga Date 2018-07-25 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 10:40 Sent To  
Notes
2018-07-12 10:40:16RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-28 Cont ID  
Sent By fgiaquin Date 2018-06-28 Time 07:20 Rev Time 0.00
Received By fgiaquin Date 2018-06-04 Time 13:55 Sent To  
Notes
2018-06-04 13:55:59ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By mcruz Date 2018-06-07 Time 11:40 Rev Time 0.00
Received By mcruz Date 2018-06-07 Time 11:38 Sent To B
Notes
***NONE***