Plan Review Details - Permit 18051520
Plan Review Stops For Permit 18051520
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By jpearson Date 2018-06-06 Time 10:38 Rev Time 0.00
Received By jpearson Date 2018-06-05 Time 10:38 Sent To I
Notes
2018-06-05 10:38:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 2. NO LIGHTING CONTROL IS SHOWN FOR THE NEW LIGHTING
 LAYOUT. A NOTE STATES TO SEE THE TENANT LIGHTING
 CONTROL DIAGRAM, BUT THIS IS NOT PROVIDED. PROVIDE THE
 ADDITIONAL AUTOMATIC LIGHTING CONTROLS STIPULATED IN
 THE FBC ENERGY CODE. FBC EC 405.2.2, 405.2.2.2
 3. PROVIDE PANEL SCHEDULE FOR PANEL P3, INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 215.2, 215.5, 408.4
 4. VALUE FOR REVISION WORK STATED ON PERMIT APPLICATION
 APPEARS LOW AS THERE IS SUBSTANTIAL ELECTRICAL BEING
 ADDED. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By jpearson Date 2018-06-07 Time 07:20 Rev Time 0.00
Received By lmarchan Date 2018-05-31 Time 14:38 Sent To  
Notes
2018-06-04 14:38:37REVISION ROUTED TO JPEARSON


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved