Plan Review Details - Permit 18051486
Plan Review Stops For Permit 18051486
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-25 Cont ID  
Sent By rmcdouga Date 2018-06-25 Time 18:54 Rev Time 0.00
Received By rmcdouga Date 2018-06-25 Time 18:54 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2018-07-14 Time 09:20 Rev Time 0.00
Received By fgiaquin Date 2018-07-14 Time 08:52 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-26 Cont ID  
Sent By rmcdouga Date 2018-06-26 Time 06:08 Rev Time 0.00
Received By fgiaquin Date 2018-06-26 Time 05:41 Sent To I
Notes
2018-06-26 05:58:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEED TO PRINT AND SIGN PLAN AND PUT ADDRESS OF
 PROJECT ON PLAN. ELECTRICAL PLAN IS REQUIRED TO BE
 DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL OR
 THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. VALUE WILL BE ADJUSTED TO 16500$
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 09:49 Rev Time 0.00
Received By tklarge Date 2018-07-25 Time 06:08 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-21 Cont ID  
Sent By tklarge Date 2018-06-21 Time 06:43 Rev Time 0.00
Received By tklarge Date 2018-06-21 Time 05:33 Sent To  
Notes
2018-06-21 06:43:261) THE EXISTING GAS PLANS ON FILE IN THE CITY HAVE THE
 FOLLOWING INFORMATION FOR THE EXISTING BTU LOAD:
 A) WATER HEATER - 55,000 BTU'S
 B) GAS DRYER - 35,000 BTU'S
 C) BBQ - 40,000 BTU'S
 D) POOL HEATER - 400,000 BTU'S
 THESE VALUES SHALL BE USED FOR THE EXISTING BTU LOAD ON
 YOUR PLANS.
 2) THE TOTAL BTU LOAD WILL BE 850,000 BTU'S. THE GAS
 METER SHALL BE CHECKED TO ENSURE THAT IT WILL HANDLE
 THE TOTAL BTU LOAD OF THE SYSTEM. CONTACT THE GAS
 PURVEYOR FOR FURTHER DIRECTION. THIS WILL BE CHECKED BY
 THE FIELD INSPECTOR AT FINAL INSPECTION.
 3) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 FOR THE REGULATOR.WPB AMEND. TO FBC SEC. 107.2.1.
 4) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER 2017
 FBC-GAS SEC.410.1. THE REGULATOR SPECS DO NOT SHOW
 THIS.
 5) INDICATE ON THE REGULATOR SPECS THE MODEL BEING
 INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
 7) THE EXISTING GAS PLANS ON FILE IN THE CITY SSHOW AN
 1 1/2 INCH GALVANIZED LINE FROM THE METER OUTLET AND A
 1 INCH GALVANIZED LINE TO THE INTERIOR AND YOUR PLAN
 SHOWS A 3/4 INCH LINE AT BOTH POINTS. CLARIFY.
 8) INDICATE ON THE PLANS THE SIZING TABLE FOR THE LOW
 PRESSURE SIDE FOR THE GENERATOR.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 09:50 Rev Time 0.00
Received By tklarge Date 2018-07-12 Time 13:39 Sent To  
Notes
2018-07-13 13:39:25RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-26 Cont ID  
Sent By cpuell Date 2018-06-26 Time 10:35 Rev Time 0.00
Received By cpuell Date 2018-05-31 Time 11:20 Sent To  
Notes
2018-06-01 11:20:24ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-06 Cont ID  
Sent By mcruz Date 2018-06-06 Time 17:00 Rev Time 0.00
Received By mcruz Date 2018-06-06 Time 16:56 Sent To B
Notes
2018-06-06 17:00:00NOTE - SHALL BE AT LEAST 4' FROM SIDE PROPERTY LINE.