Plan Review Details - Permit 18051467
Plan Review Stops For Permit 18051467
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-02 Cont ID  
Sent By rmcdouga Date 2018-08-02 Time 07:08 Rev Time 0.00
Received By rmcdouga Date 2018-08-02 Time 06:45 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-16 Cont ID  
Sent By rmcdouga Date 2018-07-16 Time 10:30 Rev Time 0.00
Received By rmcdouga Date 2018-07-16 Time 10:30 Sent To I
Notes
2018-07-16 10:32:102ND REVIEW: FBC FIFTH EDITION (2014) REFERENCE PRIMARY
 PERMIT 16040430
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING (COMMENTS FROM 1ST REVIEW WERE NOT
 ADDRESSED)
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF GENERATOR PAD PLANS. PROVIDE PAD
 DIMENSIONS AND LOCATION. SPECIFY THE SIZE, TYPE AND
 QUANITY OF ANCHORS FOR THE GENERATOR TO SLAB
 CONNECTIONS. FBC 107.2.1
  
 2) THE PROJECT IS LOCATED IN AN A5 SPECIAL FLOOD HAZARD
 ZONE AN ELEVATION CERTIFICATE WILL BE REQUIRED TO BE
 SUBMITTED AND APPROVED BEFORE FINAL INSPECTION. THE
 MINIMUM ELEVATION FOR THIS PROJECT IS 7.5' NGVD BASED
 ON THE FIRMS IN EFFECT AT THE TIME THE SINGLE FAMILY
 HOME THIS GENERATOR WILL SERVICE WAS PERMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-22 Cont ID  
Sent By rmcdouga Date 2018-06-22 Time 19:06 Rev Time 0.00
Received By rmcdouga Date 2018-06-22 Time 19:06 Sent To E
Notes
2018-06-22 19:06:061ST REVIEW: FBC FIFTH EDITION (2014) REFERENCE PRIMARY
 PERMIT 16040430
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF GENERATOR PAD PLANS. PROVIDE PAD
 DIMENSIONS AND LOCATION. SPECIFY THE SIZE, TYPE AND
 QUANITY OF ANCHORS FOR THE GENERATOR TO SLAB
 CONNECTIONS. FBC 107.2.1
  
 2) THE PROJECT IS LOCATED IN AN A5 SPECIAL FLOOD HAZARD
 ZONE AN ELEVATION CERTIFICATE WILL BE REQUIRED TO BE
 SUBMITTED AND APPROVED BEFORE FINAL INSPECTION. THE
 MINIMUM ELEVATION FOR THIS PROJECT IS 7.5' NGVD BASED
 ON THE FIRMS IN EFFECT AT THE TIME THE SINGLE FAMILY
 HOME THIS GENERATOR WILL SERVICE WAS PERMITTED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-14 Cont ID  
Sent By fgiaquin Date 2018-07-14 Time 08:45 Rev Time 0.00
Received By fgiaquin Date 2018-07-14 Time 08:23 Sent To B
Notes
2018-07-14 08:45:24VALUE ADJUSTED TO 15000$
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY:
 LOAD CALCULATION REQUIRED FOR EM PANEL AT TIME OF OR
 BEFORE FINAL INSPECTION.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-27 Cont ID  
Sent By fgiaquin Date 2018-06-27 Time 05:22 Rev Time 0.00
Received By fgiaquin Date 2018-06-27 Time 05:14 Sent To I
Notes
2018-06-27 05:21:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL PLAN SUBMITTED FOR REVIEW. PROVIDE
 ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED BY A
 LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; WPB
 FBC 107.2.1, 107.3.5
  
 CONDUIT SIZE? WIRE SIZE? LOCATION OF EM PANEL? PANEL
 SIZE/TYPE? ETC...
  
 INFORMATIONAL NOTE: MAKE SURE ALL SUBMITTED PLANS
 INCLUDE THE ADDRESS OF THE PROJECT, PRINTED NAME AND
 SIGNATURE OF QUALIFIER, AND LICENSE #.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-22 Cont ID  
Sent By tklarge Date 2018-06-22 Time 06:36 Rev Time 0.00
Received By tklarge Date 2018-06-22 Time 06:28 Sent To  
Notes
2018-06-22 06:37:32A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-02 Cont ID  
Sent By rmcdouga Date 2018-08-02 Time 07:26 Rev Time 0.00
Received By rmcdouga Date 2018-07-31 Time 14:10 Sent To  
Notes
2018-08-01 14:10:54RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-16 Cont ID  
Sent By rmcdouga Date 2018-07-16 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2018-07-06 Time 13:28 Sent To  
Notes
2018-07-09 13:28:16RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-27 Cont ID  
Sent By fgiaquin Date 2018-06-27 Time 05:22 Rev Time 0.00
Received By fgiaquin Date 2018-05-31 Time 11:23 Sent To  
Notes
2018-06-01 11:23:22ROUTED TO ZONING INBOX

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-12 Cont ID  
Sent By mcruz Date 2018-07-12 Time 14:07 Rev Time 0.00
Received By mcruz Date 2018-07-12 Time 14:07 Sent To E
Notes
2018-07-12 14:08:05ZONING PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST
 6' FROM NORTH PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-06 Cont ID  
Sent By mcruz Date 2018-06-06 Time 17:11 Rev Time 0.00
Received By mcruz Date 2018-06-06 Time 17:00 Sent To B
Notes
2018-06-06 17:10:43ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO 94-305(B)(4) - MECHANICAL EQUIMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A SETBACK. THEREFORE,
 THE GENERATOR SHOULD BE AT LEAST 6 FEET FROM THE
 PROPERTY LINE.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]