Plan Review Details - Permit 18051461
Plan Review Stops For Permit 18051461
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 12:38 Rev Time 0.00
Received By shill Date 2018-08-12 Time 12:38 Sent To  
Notes
2018-08-12 12:39:00****CORRECTIONS****
 REVISED 8/13
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A002, FBC B 1004, 100 SF PER OCCUPANT IS SHOWN FOR
 ONE OF THE PRE-FUNCTION AREAS, AND 15 SF PER PERSON FOR
 THE PREFUNCTION LOUNGE. ALTHOUGH LABELED WITH DIFFERENT
 ROOM DESIGNATIONS ("PRE-FUNCTION" VS "PREFUNCTION
 LOUNGE") THEY APPEARS TO BE THE SAME. EITHER REVISE
 PRE-FUNCTION TO HAVE OCCUPANT LOAD OF 1/15 SF OR SEND
 AN EMAIL WITH RATIONALE TO GET THIS RESOLVED PRIOR TO
 RESUBMITTAL. IT IS ACKNOWLEDGED THAT THE DIFFERENCE IN
 OCCUPANT LOAD WILL NOT AFFECT EGRESS, BUT DISCREPANCY
 SHOULD BE CORRECTED OR EXPLAINED.
  
 2. A002, DOOR 1, SEE FBC A 404.2.6, DOORS IN A SERIES,
 AND REVISE PLAN TO SHOW COMPLIANCE.
  
 3. NA
  
 4. FBC B 1010.1.10, THE DOUBLE DOORS 151A AND 151B
 INDICATES HARDWARE SET 4, NO PANIC BARS PROPOSED. I WAS
 UNABLE TO LOCATE HARDWARE SET 4; COMPLIANCE NOT CLEAR;
 REVISE PLAN ACCORDINGLY.
  
 5. FBC CHAPTER 10, DOOR 150A IS SHOWN ON THE DEMO PLAN
 AS SWINGING FROM THE MAIN LOBBY/ATRIUM TOWARDS THE
 ASSEMBLY AREA. IT NOW SWINGS THE OTHER DIRECTION, AND
 IS SHOWN AS HAVING AN EGRESS CAPACITY OF 360, OCCUPANT
 LOAD OF 40.
  
 PLEASE REVISE PLAN TO CONFIRM THAT THIS DOOR WAS NOT
 USED FOR EXITING FROM THE LOBBY AND ATRIUM, AS CHANGING
 DOOR SWING NOW MAKES THIS SWING AGAINST EGRESS TRAVEL.
  
 REVISE THE PLAN TO CONTINUE MEANS OF EGRESS SHOWN WHICH
 NOW DIRECTS SOME OCCUPANTS THROUGH THE MAIN LOBBY. IT
 IS NOT CLEAR IF THAT AREA CAN ACCOMMODATE EXITING FOR
 ADDITIONAL OCCUPANTS. TRAVEL DISTANCE FOR THOSE
 OCCUPANTS IS NOT CLEAR AS THE EXIT IS NOT SHOWN ON THE
 LIFE SAFETY PLAN.
  
 6. FBC EB 701.3, THIS STRUCTURE IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA. PROVIDE CUMULATIVE FIVE YEAR VALUE
 OF IMPROVEMENTS AND VALUE OF STRUCTURE. IT APPEARS THAT
 THE BUILDINGS ARE CONNECTED BY AN ATRIUM, SO IS
 CONSIDERED ONE BUILDING. PLEASE CONTACT ME FOR
 ASSISTANCE.
  
 A COMPLETE REVIEW CANNOT BE DONE UNTIL IT IS DETERMINED
 WHETHER OR NOT THIS IS CONSIDERED A "SUBSTANTIAL
 IMPROVEMENT". OUR ORDINANCE REQUIRES THAT FIVE YEARS OF
 IMPROVEMENTS ARE CONSIDERED.
  
 IF AN ELEVATION CERTIFICATE IS AVAILABLE FOR THIS
 STRUCTURE, PLEASE SEND TO ME VIA EMAIL.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-06 Cont ID  
Sent By jpearson Date 2018-08-06 Time 16:14 Rev Time 0.00
Received By jpearson Date 2018-08-06 Time 16:14 Sent To  
Notes
2018-08-06 16:14:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E001, APPLICABLE CODES, NOTE 1 (N), SHOWS THE
 2014 FBC AS BASIS FOR DESIGN. THIS IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CODES
 ABOVE.)
 2. SHEET E001, NOTE 54, SHOWS THE 2014 FBC ENERGY
 CONSERVATION AS BASIS FOR DESIGN. THIS IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CODES ABOVE.)
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PROVIDE LOAD CALCULATION FOR PANEL HB, PANEL DPB,
 AND PANEL BB, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-06-28 Cont ID  
Sent By pleduc Date 2018-06-28 Time   Rev Time 0.00
Received By pleduc Date 2018-06-25 Time 11:28 Sent To  
Notes
2018-06-28 13:28:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A020 - THERE ARE A PAIR OF DOUBLE DOORS
 LEADING OUT OF THE BALL ROOM, 151A & 151B. THIS IS A
 MIXED NON-SEPARATED OCCUPANY. THE BALL ROOM IS AN
 ASSEMBLY SPACE.
  
 PER NFPA 101, CHAPTER 12, NEW ASSEMBLY,
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
  
 THERE IS NO INDICATION OF PANIC HARDWARE FOR THESE
 DOOR.
  
 THERE IS AN INDICATION OF HARDWARE SET 4, PUT THE
 HARDWARE DETAILS COULD NOT BE READILY INDETIFIED IN THE
 PLAN SHEETS.
  
 PLEASE PROVIDE DETAILS FOR THESE DOORS THAT MEET THE
 REQUIRMENTS OF THE CODE.
  
  
  
 2) ELECTRICAL SHHETS - THERE ARE INDICATIONS OF FIRE
 ALARM EQUIPMENT; HOWEVER, NO INDICATIONS OF FIRE ALARM
 WORK OR SHOP DRAWINGS.
  
 ALL WORK ON ANY FIRE ALARM EQUIPMENT OF SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 PLEASE PROVIE AN APPLICABLE NOTE.
  
  
  
 3) SHEET A002 - THERE ARE CHAIRS INDICATED IN THE BALL
 ROOM. ARE THESE CHAIRS PERMANENT. TEMPORARY, LOOSE OR
 INTERLOCKING?
  
 PLEASE PROVIDE CHAIR DETAILS.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-14 Cont ID  
Sent By gjohnson Date 2018-08-14 Time 11:46 Rev Time 0.00
Received By gjohnson Date 2018-06-22 Time 09:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-26 Cont ID  
Sent By ccole Date 2018-07-26 Time 17:13 Rev Time 0.00
Received By ccole Date 2018-07-26 Time 16:07 Sent To  
Notes
2018-07-26 17:48:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051461
 7/26/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE HEAT LOAD SUMMARY SHEET INDICATES A TOTAL
 SENSIBLE MBH OF 408, HOWEVER THAT VALUE APPEARS TO BE
 THE TOTAL MBH OF THE SYSTEM- PLEASE CORRECT.
  
 2) THE ENERGY COMPLIANCE REPORT INDICATES A HEATING
 SYSTEM AT 11608 BTUH CAPACITY FOR RTU-1, HOWEVER THE
 SCHEDULE ON SHEET M-001 DOES NOT SHOW ANY DATA FOR
 HEAT.
  
 3) SHEET M001: THE VENTILATION CALCULATION FOR THE
 PREFUNCTION CORRIDOR SHALL BE BASED ON AN OCCUPANT LOAD
 OF 30 PERSONS PER 1000 SQ. FT. PER TABLE 403.1.1 FBC M.
 PLEASE CORRECT THE CALCULATION.
  
 4) IN ACCORDANCE WITH SECTION C403.2.6.1 FBC EC DEMAND
 CONTROLLED VENTILATION IS REQUIRED IN THE BALLROOM,
 BOARDROOM AND PREFUNCTION AREA.
  
 5) IN ACCORDANCE WITH SECTION C403.2.7 FBC EC, AN ERV
 IS REQUIRED FOR THE NEW AC SYSTEM.
  
 6) SHEET M200: PROVIDE COMPLETE STRUCTURAL ENGINEERING
 FOR INSTALLATION OF THE RTU USING THE CORRECT WINDSPEED
 OF 170 MPH AND DESIGN CRITERIA BASED ON THAT SPEED.
 PLEASE CORRECT THE NOTES INDICATING 140 MPH- SECTION
 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 13:07 Rev Time 0.00
Received By shill Date 2018-08-12 Time 13:07 Sent To  
Notes
2018-08-12 13:08:06SEE BUILDING REVIEW
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-14 Cont ID  
Sent By gjohnson Date 2018-08-14 Time 11:44 Rev Time 0.00
Received By gjohnson Date 2018-08-13 Time 16:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 13:09 Rev Time 0.00
Received By shill Date 2018-08-12 Time 13:09 Sent To  
Notes
2018-08-14 11:46:518/14/18 PLUMB DIG SIG OK/GPJ
2018-08-12 13:09:59ALL SIGNATURES, ALL TRADES SPOT CHECKED AND ARE OK
 NEW PAGES SUBMITTED 2ND REVIEW CYCLE NEED VERIFICATION
  
2018-07-26 16:07:30MECH SIGS GOOD
 CCOLE- 7/26/18

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-27 Cont ID  
Sent By hmtribou Date 2018-06-27 Time 08:38 Rev Time 0.00
Received By hmtribou Date 2018-06-27 Time 08:38 Sent To  
Notes
2018-06-27 08:45:31PROVIDE LANDSCPAE PLANS TO REMOVE AND OR REPLACE
 REQUIRED MISSING OR DEAD TREES AND PLANTS IN FRONT OF
 ENTRY OF NEW MEETING SPACE INCLUDING IN THE PARKING
 AREA WHICH SHALL INCLUDE THE ENTRY ON BELVEDERE TO THE
 FIRST ENTRY ON BRISTOL.
 PROVIDE REQUIRED BIKE PARKING 1 PER 10 REQUIRED PARKING
 SPACES.
 PARKING REQUIREMETNS FOR MEETING SPACE AND LOUNGE SPACE
 ARE EQUAL AT 1 SPACE PER 100 SQ. FT.- NO ACTION
 REQUIRED.