Plan Review Details - Permit 18051461
Plan Review Stops For Permit 18051461 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-08-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-12 |
Time |
12:38 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-12 |
Time |
12:38 |
Sent To |
|
|
Notes |
2018-08-12 12:39:00 | ****CORRECTIONS**** | | REVISED 8/13 | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. A002, FBC B 1004, 100 SF PER OCCUPANT IS SHOWN FOR | | ONE OF THE PRE-FUNCTION AREAS, AND 15 SF PER PERSON FOR | | THE PREFUNCTION LOUNGE. ALTHOUGH LABELED WITH DIFFERENT | | ROOM DESIGNATIONS ("PRE-FUNCTION" VS "PREFUNCTION | | LOUNGE") THEY APPEARS TO BE THE SAME. EITHER REVISE | | PRE-FUNCTION TO HAVE OCCUPANT LOAD OF 1/15 SF OR SEND | | AN EMAIL WITH RATIONALE TO GET THIS RESOLVED PRIOR TO | | RESUBMITTAL. IT IS ACKNOWLEDGED THAT THE DIFFERENCE IN | | OCCUPANT LOAD WILL NOT AFFECT EGRESS, BUT DISCREPANCY | | SHOULD BE CORRECTED OR EXPLAINED. | | | | 2. A002, DOOR 1, SEE FBC A 404.2.6, DOORS IN A SERIES, | | AND REVISE PLAN TO SHOW COMPLIANCE. | | | | 3. NA | | | | 4. FBC B 1010.1.10, THE DOUBLE DOORS 151A AND 151B | | INDICATES HARDWARE SET 4, NO PANIC BARS PROPOSED. I WAS | | UNABLE TO LOCATE HARDWARE SET 4; COMPLIANCE NOT CLEAR; | | REVISE PLAN ACCORDINGLY. | | | | 5. FBC CHAPTER 10, DOOR 150A IS SHOWN ON THE DEMO PLAN | | AS SWINGING FROM THE MAIN LOBBY/ATRIUM TOWARDS THE | | ASSEMBLY AREA. IT NOW SWINGS THE OTHER DIRECTION, AND | | IS SHOWN AS HAVING AN EGRESS CAPACITY OF 360, OCCUPANT | | LOAD OF 40. | | | | PLEASE REVISE PLAN TO CONFIRM THAT THIS DOOR WAS NOT | | USED FOR EXITING FROM THE LOBBY AND ATRIUM, AS CHANGING | | DOOR SWING NOW MAKES THIS SWING AGAINST EGRESS TRAVEL. | | | | REVISE THE PLAN TO CONTINUE MEANS OF EGRESS SHOWN WHICH | | NOW DIRECTS SOME OCCUPANTS THROUGH THE MAIN LOBBY. IT | | IS NOT CLEAR IF THAT AREA CAN ACCOMMODATE EXITING FOR | | ADDITIONAL OCCUPANTS. TRAVEL DISTANCE FOR THOSE | | OCCUPANTS IS NOT CLEAR AS THE EXIT IS NOT SHOWN ON THE | | LIFE SAFETY PLAN. | | | | 6. FBC EB 701.3, THIS STRUCTURE IS LOCATED IN A SPECIAL | | FLOOD HAZARD AREA. PROVIDE CUMULATIVE FIVE YEAR VALUE | | OF IMPROVEMENTS AND VALUE OF STRUCTURE. IT APPEARS THAT | | THE BUILDINGS ARE CONNECTED BY AN ATRIUM, SO IS | | CONSIDERED ONE BUILDING. PLEASE CONTACT ME FOR | | ASSISTANCE. | | | | A COMPLETE REVIEW CANNOT BE DONE UNTIL IT IS DETERMINED | | WHETHER OR NOT THIS IS CONSIDERED A "SUBSTANTIAL | | IMPROVEMENT". OUR ORDINANCE REQUIRES THAT FIVE YEARS OF | | IMPROVEMENTS ARE CONSIDERED. | | | | IF AN ELEVATION CERTIFICATE IS AVAILABLE FOR THIS | | STRUCTURE, PLEASE SEND TO ME VIA EMAIL. | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-08-06 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-08-06 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-08-06 |
Time |
16:14 |
Sent To |
|
|
Notes |
2018-08-06 16:14:54 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. SHEET E001, APPLICABLE CODES, NOTE 1 (N), SHOWS THE | | 2014 FBC AS BASIS FOR DESIGN. THIS IS NOT THE CURRENT | | CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CODES | | ABOVE.) | | 2. SHEET E001, NOTE 54, SHOWS THE 2014 FBC ENERGY | | CONSERVATION AS BASIS FOR DESIGN. THIS IS NOT THE | | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE | | CODES ABOVE.) | | 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 | | 4. PROVIDE LOAD CALCULATION FOR PANEL HB, PANEL DPB, | | AND PANEL BB, INCLUDE EXISTING AND NEW LOADS TO CONFIRM | | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | SHEETS?. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-06-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-06-28 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-06-25 |
Time |
11:28 |
Sent To |
|
|
Notes |
2018-06-28 13:28:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET A020 - THERE ARE A PAIR OF DOUBLE DOORS | | LEADING OUT OF THE BALL ROOM, 151A & 151B. THIS IS A | | MIXED NON-SEPARATED OCCUPANY. THE BALL ROOM IS AN | | ASSEMBLY SPACE. | | | | PER NFPA 101, CHAPTER 12, NEW ASSEMBLY, | | | | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM | | AN AREA HAVING | | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE | | PERMITTED TO BE | | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK | | IS PANIC | | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, | | UNLESS | | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: | | | | THERE IS NO INDICATION OF PANIC HARDWARE FOR THESE | | DOOR. | | | | THERE IS AN INDICATION OF HARDWARE SET 4, PUT THE | | HARDWARE DETAILS COULD NOT BE READILY INDETIFIED IN THE | | PLAN SHEETS. | | | | PLEASE PROVIDE DETAILS FOR THESE DOORS THAT MEET THE | | REQUIRMENTS OF THE CODE. | | | | | | | | 2) ELECTRICAL SHHETS - THERE ARE INDICATIONS OF FIRE | | ALARM EQUIPMENT; HOWEVER, NO INDICATIONS OF FIRE ALARM | | WORK OR SHOP DRAWINGS. | | | | ALL WORK ON ANY FIRE ALARM EQUIPMENT OF SYSTEM SHALL BE | | DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE | | SAFETY CONTRACTORS. | | | | PLEASE PROVIE AN APPLICABLE NOTE. | | | | | | | | 3) SHEET A002 - THERE ARE CHAIRS INDICATED IN THE BALL | | ROOM. ARE THESE CHAIRS PERMANENT. TEMPORARY, LOOSE OR | | INTERLOCKING? | | | | PLEASE PROVIDE CHAIR DETAILS. | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-08-14 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-14 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-22 |
Time |
09:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-07-26 |
Time |
17:13 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-07-26 |
Time |
16:07 |
Sent To |
|
|
Notes |
2018-07-26 17:48:21 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18051461 | | 7/26/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE HEAT LOAD SUMMARY SHEET INDICATES A TOTAL | | SENSIBLE MBH OF 408, HOWEVER THAT VALUE APPEARS TO BE | | THE TOTAL MBH OF THE SYSTEM- PLEASE CORRECT. | | | | 2) THE ENERGY COMPLIANCE REPORT INDICATES A HEATING | | SYSTEM AT 11608 BTUH CAPACITY FOR RTU-1, HOWEVER THE | | SCHEDULE ON SHEET M-001 DOES NOT SHOW ANY DATA FOR | | HEAT. | | | | 3) SHEET M001: THE VENTILATION CALCULATION FOR THE | | PREFUNCTION CORRIDOR SHALL BE BASED ON AN OCCUPANT LOAD | | OF 30 PERSONS PER 1000 SQ. FT. PER TABLE 403.1.1 FBC M. | | PLEASE CORRECT THE CALCULATION. | | | | 4) IN ACCORDANCE WITH SECTION C403.2.6.1 FBC EC DEMAND | | CONTROLLED VENTILATION IS REQUIRED IN THE BALLROOM, | | BOARDROOM AND PREFUNCTION AREA. | | | | 5) IN ACCORDANCE WITH SECTION C403.2.7 FBC EC, AN ERV | | IS REQUIRED FOR THE NEW AC SYSTEM. | | | | 6) SHEET M200: PROVIDE COMPLETE STRUCTURAL ENGINEERING | | FOR INSTALLATION OF THE RTU USING THE CORRECT WINDSPEED | | OF 170 MPH AND DESIGN CRITERIA BASED ON THAT SPEED. | | PLEASE CORRECT THE NOTES INDICATING 140 MPH- SECTION | | 301.15 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
F |
Date |
2018-08-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-12 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-12 |
Time |
13:07 |
Sent To |
|
|
Notes |
2018-08-12 13:08:06 | SEE BUILDING REVIEW | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2018-08-14 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-14 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-08-13 |
Time |
16:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2018-08-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-08-12 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-12 |
Time |
13:09 |
Sent To |
|
|
Notes |
2018-08-14 11:46:51 | 8/14/18 PLUMB DIG SIG OK/GPJ | 2018-08-12 13:09:59 | ALL SIGNATURES, ALL TRADES SPOT CHECKED AND ARE OK | | NEW PAGES SUBMITTED 2ND REVIEW CYCLE NEED VERIFICATION | | | 2018-07-26 16:07:30 | MECH SIGS GOOD | | CCOLE- 7/26/18 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-06-27 |
|
|
Cont ID |
|
Sent By |
hmtribou |
Date |
2018-06-27 |
Time |
08:38 |
Rev Time |
0.00 |
Received By |
hmtribou |
Date |
2018-06-27 |
Time |
08:38 |
Sent To |
|
|
Notes |
2018-06-27 08:45:31 | PROVIDE LANDSCPAE PLANS TO REMOVE AND OR REPLACE | | REQUIRED MISSING OR DEAD TREES AND PLANTS IN FRONT OF | | ENTRY OF NEW MEETING SPACE INCLUDING IN THE PARKING | | AREA WHICH SHALL INCLUDE THE ENTRY ON BELVEDERE TO THE | | FIRST ENTRY ON BRISTOL. | | PROVIDE REQUIRED BIKE PARKING 1 PER 10 REQUIRED PARKING | | SPACES. | | PARKING REQUIREMETNS FOR MEETING SPACE AND LOUNGE SPACE | | ARE EQUAL AT 1 SPACE PER 100 SQ. FT.- NO ACTION | | REQUIRED. |
|
|
|