Plan Review Details - Permit 18051456
Plan Review Stops For Permit 18051456
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2018-06-26 Cont ID  
Sent By shill Date 2018-06-26 Time 13:18 Rev Time 0.00
Received By shill Date 2018-06-26 Time 13:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-09 Cont ID  
Sent By shill Date 2018-06-09 Time 08:21 Rev Time 0.00
Received By shill Date 2018-06-09 Time 08:21 Sent To  
Notes
2018-06-09 08:24:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE TEMPORARY CONSTRUCTION FENCE (18031003)
 ASSOCIATED WITH THE PROPOSED SIGNAGE IS NOT YET ISSUED,
 FBC 105.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-06 Cont ID  
Sent By cpuell Date 2019-01-06 Time 06:55 Rev Time 0.00
Received By cpuell Date 2018-12-17 Time 12:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-23 Cont ID  
Sent By lmarchan Date 2018-10-23 Time 09:08 Rev Time 0.00
Received By lmarchan Date 2018-09-20 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-11 Cont ID  
Sent By cpuell Date 2018-06-29 Time 17:44 Rev Time 0.00
Received By cpuell Date 2018-06-07 Time 16:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2018-06-09 Cont ID  
Sent By shill Date 2018-06-09 Time 08:24 Rev Time 0.00
Received By shill Date 2018-06-09 Time 08:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2019-01-04 Cont ID  
Sent By eschneid Date 2019-01-04 Time 16:58 Rev Time 0.25
Received By eschneid Date 2019-01-04 Time 16:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-10-22 Cont ID  
Sent By eschneid Date 2018-10-22 Time 17:47 Rev Time 0.25
Received By eschneid Date 2018-10-22 Time 17:47 Sent To  
Notes
2018-10-23 15:03:34FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) PROVIDE VERIFICATION THAT THE WINDSCREEN COMPLIES
 WITH CITY REQUIREMENTS. ----- THE MESH SPECIFICATION
 PAGE IS ILLEGIBLE. PLEASE PROVIDE A BETTER COPY.
  
 2) PLEASE VERIFY THAT THERE WILL ONLY BE TEXT ON THE
 ARKONA COURT SIDE OF THE FENCE AND NOT ON THE FLAGLER
 DRIVE SIDE. THIS IS WHAT IS SHOWN ON THE CURRENT PERMIT
 DRAWINGS. IF TEXT IS PROPOSED FOR THE FLAGLER DRIVE
 SIDE, THEN THIS NEEDS TO BE SHOWN ON THE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-29 Cont ID  
Sent By eschneid Date 2018-06-29 Time 13:48 Rev Time 0.25
Received By eschneid Date 2018-06-29 Time 13:48 Sent To  
Notes
2018-06-29 13:50:36FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE PERMIT DRAWINGS NEED TO INCLUDE THE DIMENSIONS
 FOR THE TEXT ON EACH PANEL. PLEASE NOTE THAT THE YOU
 NEED TO PROVIDE A BOX AROUND THE ENTIRE TEXT/LOGO ON
 EACH PANEL. THIS MEANS THAT THE SPACE BETWEEN EACH LINE
 OF TEXT IS COUNTED, NOT JUST THE LINE OF TEXT
 INDIVIDUALLY.
  
 2) THE DIMENSIONS ALSO NEED TO BE PROVIDED ON THE PANEL
 FOR THE BOX AROUND THE BUILDING.
  
 3) PROVIDE VERIFICATION THAT THE WINDSCREEN COMPLIES
 WITH CITY REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]