Plan Review Details - Permit 18051438
Plan Review Stops For Permit 18051438
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-10 Cont ID  
Sent By rmcdouga Date 2018-10-10 Time 06:46 Rev Time 0.00
Received By rmcdouga Date 2018-10-10 Time 06:46 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-11 Cont ID  
Sent By rmcdouga Date 2018-09-11 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2018-09-11 Time 08:28 Sent To I
Notes
2018-09-11 08:38:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING DOCUMENTS DO NOT HAVE
 THE ORIGINAL HANDWRITTEN SIGNATURE OF THE ENGINEER ON
 THE SEAL. FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY
 SIGNING AND SEALING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS. ENGINEERING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED
 AND SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MAY BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) THE WIDTH DIMENSION FOR THE 20KW GENERATOR LISTED IN
 THE MANUFACTURER'S SPECIFICATIONS EXCEEDS THE MAXIMUM
 UNIT DIMENSION THAT IS ALLOWED BY THE PAD ENGINEERING.
 FBC 107.2.1
  
 3) THE MINIMUM WEIGHT FOR THE UNIT THAT IS REQUIRED BY
 THE PAD ENGINEERING IS 535 LBS. AND THE WEIGHT FOR THIS
 UNIT IS 500 LBS. PER THE MANUFACTURER'S SPECIFICATIONS.
 FBC 107.2.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-21 Cont ID  
Sent By rmcdouga Date 2018-06-21 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2018-06-21 Time 09:00 Sent To I
Notes
2018-06-21 09:47:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING DOCUMENTS DO NOT HAVE
 THE ORIGINAL HANDWRITTEN SIGNATURE OF THE ENGINEER ON
 THE SEAL. FAC 61G15-23.003 PROCEDURES FOR PHYSICALLY
 SIGNING AND SEALING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) THE PAD DOCUMENTS REFERENCE THE 2010 FLORIDA
 BUILDING CODE AND THE CODE THAT APPLIES TO THIS PROJECT
 IS THE 2017 FBC. FBC 102.2
  
 3) THE LENGTH DIMENSION FOR THE 20KW GENERATOR LISTED
 IN THE MANUFACTURER'S SPECIFICATIONS EXCEEDS THE
 MAXIMUM UNIT DIMENSION THAT IS ALLOWED BY THE PAD
 ENGINEERING. FBC 107.2.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By fgiaquin Date 2018-08-29 Time 06:50 Rev Time 0.00
Received By fgiaquin Date 2018-08-29 Time 06:50 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-06 Cont ID  
Sent By fgiaquin Date 2018-06-06 Time 07:25 Rev Time 0.00
Received By fgiaquin Date 2018-06-06 Time 07:12 Sent To  
Notes
2018-06-06 07:25:39ROUTED BACK TO GENERATORS/POOLS INBOX
  
  
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By lcrespo Date 2018-08-29 Time 16:38 Rev Time 0.00
Received By lcrespo Date 2018-08-29 Time 16:38 Sent To  
Notes
2018-08-29 17:00:4308/29/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-21 Cont ID  
Sent By tklarge Date 2018-06-21 Time 05:29 Rev Time 0.00
Received By tklarge Date 2018-06-20 Time 14:00 Sent To  
Notes
2018-06-20 15:18:341) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2017 FBC-FUEL GAS
 SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1,
 G2413.4.2.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. IDENTIFY ON THE SPECIFICATION SHEETS
 WHICH MODEL REGULATOR IS BEING INSTALLED AND THE
 ORIFICE SIZE TO ENSURE THE REGULATOR CAN ACCOMMODATE
 THE BTU LOAD THROUGH THE REGULATOR.2017 FGC SEC.410.1,
 2017 FBC-RES. SEC. G2421.1.
 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
 6) THE PLANS REFER TO AN EXISTING GAS METER. THERE ARE
 NO RECORDS ON FILE WITH THE CITY FOR A GAS PERMIT FOR
 THIS ADDRESS. ANY PREVIOUS GAS INSTALLATION SHALL BE
 PERMITTED. WPB AMEND. TO FBC SEC. 105.1.
 7) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
 10) ) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET
 OF THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 11) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBCR SEC. G2420.4.
 12) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
 13) THE GAS PERMIT APPLICATION HAS THE ELECTRICAL
 CONTRACTOR'S LICENSE NUMBER ON IT. AN ELECTRICAL
 CONTRACTOR CANNOT INSTALL GAS UNLESS HE IS LICENSED IN
 THAT CATEGORY. AN ELECTRICAL CONTRACTOR'S LICENSE DOES
 NOT ALLOW YOU TO INSTALL GAS PIPING. FL. STATUTE
 489.505
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-10 Cont ID  
Sent By rmcdouga Date 2018-10-10 Time 06:46 Rev Time 0.00
Received By rmcdouga Date 2018-10-03 Time 09:37 Sent To  
Notes
2018-10-05 09:37:18RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-11 Cont ID  
Sent By rmcdouga Date 2018-09-11 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2018-08-23 Time 14:03 Sent To  
Notes
2018-08-24 14:04:02RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-21 Cont ID  
Sent By rmcdouga Date 2018-06-21 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2018-05-30 Time 14:59 Sent To  
Notes
2018-05-31 14:59:32ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-05 Cont ID  
Sent By mcruz Date 2018-06-05 Time 16:08 Rev Time 0.00
Received By mcruz Date 2018-06-05 Time 11:15 Sent To B
Notes
2018-06-05 11:19:52NOTE - GENERATOR SHALL BE SETBACK AT LEAST 8 FEET FROM
 REAR PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]