Plan Review Details - Permit 18051366
Plan Review Stops For Permit 18051366
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-22 Cont ID  
Sent By rmcdouga Date 2018-06-22 Time 13:41 Rev Time 0.00
Received By rmcdouga Date 2018-06-22 Time 13:39 Sent To I
Notes
2018-06-22 13:41:20FBC-R4501.19 FINAL INSPECTION. FINAL ELECTRICAL AND
 BARRIER CODE INSPECTION SHALL BE COMPLETED PRIOR TO
 FILLING THE POOL WITH WATER.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-08 Cont ID  
Sent By jleahy Date 2018-06-08 Time 10:09 Rev Time 0.00
Received By jleahy Date 2018-06-08 Time 10:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 07:22 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 06:57 Sent To  
Notes
2018-06-03 07:22:53THERE IS NO GAS ON THIS POOL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-24 Cont ID  
Sent By lcrespo Date 2018-07-24 Time 18:24 Rev Time 0.00
Received By lcrespo Date 2018-07-11 Time 14:53 Sent To  
Notes
2018-07-12 14:53:38RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-22 Cont ID  
Sent By rmcdouga Date 2018-06-22 Time 13:41 Rev Time 0.00
Received By rmcdouga Date 2018-05-29 Time 13:26 Sent To  
Notes
2018-05-30 13:27:02ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-24 Cont ID  
Sent By lcrespo Date 2018-07-24 Time 18:25 Rev Time 0.00
Received By lcrespo Date 2018-07-24 Time 18:24 Sent To  
Notes
2018-07-24 18:25:5807/24/18 APPROVED BY PLUMBING AND SENT TO PROCESSING,
 LAC

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 07:22 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 06:57 Sent To  
Notes
2018-06-03 07:22:111) THE SUCTION OUTLET SAGETY CCOMPLIANCE DATA SHEET
 SHOWS THAT THE SYSTEM FLOW RATE HAS BEEN DETERMINED BY
 THE MAXIMUM FLOW FROM THE PUMP CURVE. THIS METHOD IS NO
 LONGER PERMITTED BY APSP/ANSI-7 2013 EDITION SEC.
 4.4.9. TOTAL DYNAMIC HEAD CALCULATIONS ARE REQUIRED.
 2) IDENTIFY ON THE PUMP CURVE GRAPH THE PUMP BEING
 INSTALLED. SUBMIT A CURVE SHOWING THE GRADIENT LINES SO
 THE MAXIMUM FLOW CAN BE DETERMINED FROM THE TDH
 CALCULATIONS.
 3) SHT. 2 OF 3 REFERS TO SEC. 424 OF THE FLORIDA
 BULDING CODE. THIS CODE SECTION IS FOR CHILDREN'S PLAY
 STRUCTURES, NOT SWIMMING POOLS. PLEASE REVISE THE NOTE
 TO THE CORRECT CODE SECTION(S).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 15:59 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 15:59 Sent To B
Notes
***NONE***