Plan Review Details - Permit 18051333
Plan Review Stops For Permit 18051333
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2018-06-14 Cont ID  
Sent By jleahy Date 2018-06-14 Time 15:50 Rev Time 0.00
Received By jleahy Date 2018-06-14 Time 15:49 Sent To  
Notes
2018-06-14 15:50:41DID SLAB REVIEW UNDER THE ELECTRIC PLAN REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-14 Cont ID  
Sent By jleahy Date 2018-06-14 Time 15:41 Rev Time 0.00
Received By jleahy Date 2018-06-14 Time 15:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-06-26 Cont ID  
Sent By lcrespo Date 2018-06-26 Time 15:39 Rev Time 0.00
Received By lcrespo Date 2018-06-26 Time 15:39 Sent To  
Notes
2018-06-26 15:41:0606/26/18 APPROVED BY PLUMBING FOR GAS AND SENT TO
 PROCESSING, LAC

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 05:10 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 04:25 Sent To  
Notes
2018-06-03 05:10:181) CITY RECORDS SHOW THE TOTAL BTU GAS LOAD TO THE
 EXISTING GAS APPLIANCES AS 153, 000 NOT 117,000 AS
 SHOWN ON THE SUBMITTED GAS DRAWING. REVISE THE
 SUBMITTED GAS PLAN TO COMPLY WITH THE EXISTING RECORD
 ON FILE.2017 FBC-FUEL GAS SEC.401.4.
 2) CITY RECORDS SHOW THE MOST REMOTE OUTLET TO THE
 EXISTING APPLIANCES AS 140 FEET FROM THE POINT OF
 DELIVERY. THIS DISTANCE SHALL BE USED IN SIZING THE GAS
 SYSTEM. 2017 FBC-FUEL GAS SEC.402.4.1.
 3) THE EXISTING LOAD TABLE NOTES THE EXISTING LOAD AS
 117,000 BTU'S BUT THE GAS DRAWING SHOWS THE EXISTING
 LOAD AS 88,000 BTU'S. ????? REVISE THE DRAWING TO
 COMPLY WITH COMMENTS # 1 & 2 ABOVE.
 4) THE GAS DRAWING REFERENCES TABLE 402.4 (22) WHICH IS
 FOR A 2 PSI PRESSURE BUT YOU HAVE SUBMITTED THE TABLE
 FOR A PE LESS THAN 2 PSI SYSTEM 402.4 (21). WHICH IS
 IT, 2 PSI OR LESS THAN 2 PSI?
 5) YOU HAVE SUBMITTED SPECIFICATIONS FOR REGULAORS. IF
 THIS IS LESS THAN A 2 PSI SYSTEM, WHY THE REGULATORS?
 CLARIFY.
 6) IF THIS IS GOING TO BE A 2 PSI SYSTEM, INDICATE ON
 THE REGULATOR SPECS THE MODEL BEING INSTALLED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 7) THE MINIMUM SIZE LINE TO THE EXISTING APPLIANCES
 SHALL BE 1 INCH IF THIS IS TO REMAIN A LESS THAN 2 PSI
 SYSTEM. CLARIFY.
 8) THE MINIMU SIZE SCH. 40 METALLIC PIPE AT THE OUTLET
 OF THE GAS METER SHALL BE 2 INCHES PER TABLE 402.4 (2)
 AAT 140 FEET.
 9) THE NEW TOTAL BTU LOAD OF THE SYSTEM IS 434,000
 BTU'S NOT 398,000 AS SHOWN ON THE PLANS.
 10) THE MINIMUM SIZE METALLIC PIPE TO THE GENERATOR
 SHALL BE 1 1/4 INCHES PER TABLE 402.4(2) AT 140 FEET
 DISTANCE TO THE MOST REMOTE OUTLET ON THE SYSTEM PER
 THE EXISTING GAS PLAN.
 11) SUBMIT MANUF. SPECS FOR THE FLEX CONNECTOR FOR THE
 GENERATOR. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEX CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
 12) THE GENERATOR EXHAUST SHALL BE A MINIMUM OF 10 FEET
 FROM ANYBUILDING OPENING INCLUDING SOFFIT SCREENS/ATTIC
 VENTS.
  
 NOTE: I HAVE PLACED TWO COPIES OF THE EXISTING GAS PLAN
 FROM CITY RECORDS TO BE USED AS A REFERENCE ONLY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-26 Cont ID  
Sent By lcrespo Date 2018-06-26 Time 15:39 Rev Time 0.00
Received By lcrespo Date 2018-06-15 Time 13:41 Sent To  
Notes
2018-06-18 13:42:06RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-14 Cont ID  
Sent By jleahy Date 2018-06-14 Time 15:50 Rev Time 0.00
Received By jleahy Date 2018-05-29 Time 13:46 Sent To I
Notes
2018-05-30 13:46:19ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 16:19 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 16:17 Sent To B
Notes
***NONE***