|
 |
 |
 |
 |
 |
Plan Review Details - Permit 18051323
Plan Review Stops For Permit 18051323 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-26 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-26 |
Time |
12:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-06-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-03 |
Time |
06:01 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-03 |
Time |
06:01 |
Sent To |
|
|
Notes |
2018-06-03 06:01:49 | 1) SHOW THE BTU LOAD OF THE EXISTING POOL HEATER ON THE | | PLANS. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SHOW THE BTU LOAD OF THE EXISTING 3/4 INCH | | GALVANIZED LINE TO THE INTERIOR OF THE STRUCTURE.WPB | | AMEND. TO FBC SEC. 107.2.1. | | 3) EXISTING GAS PLANS ON FILE IN CITY RECORDS SHOW THE | | FURTHEST GAS OUTLET AT 82 FEET. THIS DISTANCE SHALL BE | | USED FOR SIZING THIS GAS SYSTEM. 2017 FBC-RES. SEC. G | | 2413.4.1, G2413.4.2. | | 4) SUBMIT 2 COPIES OF THE APPLICABLE SIZING TABLE BEING | | USED TO SIZE THE LOW PRESSURE SIDE OF THE GAS SYSTEM. | | 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE PRESSURE REGULATORS. THE | | REGULATORS SHALL BE IN COMPLIANCE WITH 2017 FBCR-SEC. | | G2421.1, G2421.2 (1-7).IDENTIFY WHICH MODEL REGULATOR | | IS BEING INSTALLED. | | 6) SHOW THE DISTANCE FROM THE MP REGULATOR TO THE MOST | | REMOTE OUTLET ON THE SYSTEM FOR THE EXISTING PIPING | | INTO THE STRUCTURE.WPB AMEND. TO FBC SEC. 107.2.1, 2017 | | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. | | SEC. G 2413.4.1, G2413.4.2. | | 7) THE SHUTOFF VALVE FOR THE EXISTING PIPING INTO THE | | STRUCTURE SHALL BE LOCATED UPSTREAM (AHEAD) OF THE MP | | REGULATOR PER 2017 FBC-FUEL GAS SEC. 409.4, 2017 | | FBC-RES. SEC. G2420.4. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-26 |
Time |
12:02 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-26 |
Time |
12:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-06-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-03 |
Time |
06:02 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-03 |
Time |
06:01 |
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |