Plan Review Details - Permit 18051322
Plan Review Stops For Permit 18051322
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By rmcdouga Date 2018-07-30 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2018-07-30 Time 08:50 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2018-06-20 Time 08:47 Sent To I
Notes
2018-06-20 08:50:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR
 G007043-0 AND G007042-0 THAT'S SPECIFICATIONS WERE
 SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE
 AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT
 BE USED WITH THIS GENERATOR. FBC-R 301.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By fgiaquin Date 2018-07-23 Time 06:59 Rev Time 0.00
Received By fgiaquin Date 2018-07-23 Time 06:54 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By fgiaquin Date 2018-06-07 Time 06:35 Rev Time 0.00
Received By fgiaquin Date 2018-06-07 Time 06:26 Sent To  
Notes
2018-06-07 06:34:52ROUTED TO GENERATOR/POOLS INBOX.
  
 VALUE ADJUSTED TO 16500$
  
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 12:02 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 11:37 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 06:00 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 05:40 Sent To  
Notes
2018-06-03 06:00:371) ) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. THE
 REGULATORS SHALL BE IN COMPLIANCE WITH 2017 FBCR-SEC.
 G2421.1, G2421.2 (1-7). IDENTIFY WHICH MODEL REGULATOR
 IS BEING INSTALLED.
 2) THE SHUTOFF VALVE FOR THE EXISTING PIPING INTO THE
 STRUCTURE SHALL BE LOCATED UPSTREAM (AHEAD) OF THE MP
 REGULATOR PER 2017 FBC-FUEL GAS SEC. 409.4, 2017
 FBC-RES. SEC. G2420.4.
 3) A REGULATOR IS REQUIRED AT THE EXISTING POOL HEATER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-30 Cont ID  
Sent By rmcdouga Date 2018-07-30 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2018-07-16 Time 14:03 Sent To  
Notes
2018-07-17 14:03:52RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2018-05-29 Time 13:44 Sent To  
Notes
2018-05-30 13:44:34ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-19 Cont ID  
Sent By mcruz Date 2018-07-19 Time 13:08 Rev Time 0.00
Received By mcruz Date 2018-07-19 Time 13:04 Sent To E
Notes
2018-07-19 13:08:31NOTE - GENRATOR SHALL BE AT LEAST 3.5 ' FROM SIDE
 PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 16:13 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 16:01 Sent To B
Notes
2018-05-31 16:13:17NOTE - SHALL BE AT LEAST 3.5 ' FROM SIDE PROPERTY
 LINES.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]