Plan Review Details - Permit 18051320
Plan Review Stops For Permit 18051320
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By rmcdouga Date 2018-07-30 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2018-07-30 Time 10:31 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By mcruz Date 2018-06-20 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2018-06-20 Time 08:11 Sent To I
Notes
2018-06-20 08:28:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR
 G007043-0 AND G007042-0 THAT'S SPECIFICATIONS WERE
 SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE
 AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT
 BE USED WITH THIS GENERATOR. FBC-R 301.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By rmcdouga Date 2018-07-31 Time 06:09 Rev Time 0.00
Received By fgiaquin Date 2018-07-31 Time 06:04 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-07 Cont ID  
Sent By fgiaquin Date 2018-06-07 Time 06:14 Rev Time 0.00
Received By fgiaquin Date 2018-06-07 Time 06:04 Sent To  
Notes
2018-06-07 06:14:48ROUTED TO GENERATOR/POOLS INBOX
  
 VALUE ADJUSTED TO 16500$
  
  
  
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 16:51 Rev Time 0.00
Received By lcrespo Date 2018-08-20 Time 16:50 Sent To  
Notes
2018-08-20 16:51:5108/20/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-07-30 Cont ID  
Sent By tklarge Date 2018-07-30 Time 08:15 Rev Time 0.00
Received By tklarge Date 2018-07-30 Time 06:33 Sent To  
Notes
2018-07-30 07:26:081) EXISTING GAS PLANS IN CITY RECORDS SHOW THE LONGEST
 DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET AS
 104 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF
 THIS SYSTEM. 2017 FBCR- SEC. G2413.4.1.
 2) EXISTING GAS PLAN ON FILE WITH THE CITY SHOWS A 1
 INCH LINE TO THE INTERIOR EXISTING GAS FIXTURES BUT THE
 SUBMITTED GAS DRAWING SHOWS A 3/4 INCH LINE. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 06:54 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 06:07 Sent To  
Notes
2018-06-03 06:54:391) EXISTING GAS PLPANS IN CITY RECORDS SHOW THE LONGEST
 DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET AS
 104 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF
 THIS SYSTEM. 2017 FBCR- SEC. G2413.4.1.
 2) THE PIPE SIZE OF THE SCH. 40 METALLIC PIPE AT THE
 OUTLET OF THE GAS METER SHALL BE 1 1/2 INCHES PER TABLE
 402.4 (2) OF 2017 FBC-FUEL GAS, 2017 FBCR TABLE G2413.4
 (2).
 3) THE GAS PLAN SHOWS A 3/4 INCH GALVANIZED LINE AT THE
 OUTLET OF THE GAS METER., PLEASE EXPLAIN HOW YOU WILL
 SUPPLY AN 1 1/4 INCH PE LINE WITH A 3/4 INCH GALVANIZED
 LINE.THE EXISTING PLAN ON RECORD SHOWS AN 1 1/2 INCH
 LINE.
 4) INDICATE ON THE PLAN HOW THE GALVANIZED PIPE WILL BE
 INSTALLED. WILL IT BE ATTACHED TO THE WALL OF THE
 STRUCTURE? SUBMIT ADDITIONAL INFO/DETAILS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 5) SHOW THE DISTANCE FROM THE METER TO FURTHEST OUTLET
 TO THE APPLIANCES IN THE STRUCTURE.WPB AMEND. TO FBC
 SEC. 107.2.1.
 6) SHOW THE DISTANCE FROM THE EXISTING GAS METER TO THE
 POOL HEATER.WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHOW THE POOL HEATER AS EXISTING O NTHE GAS PLAN.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 16:51 Rev Time 0.00
Received By lcrespo Date 2018-08-16 Time 13:33 Sent To  
Notes
2018-08-17 13:33:25RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-31 Cont ID  
Sent By fgiaquin Date 2018-07-31 Time 06:09 Rev Time 0.00
Received By fgiaquin Date 2018-07-16 Time 14:41 Sent To  
Notes
2018-07-17 14:41:29RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 08:11 Rev Time 0.00
Received By rmcdouga Date 2018-05-29 Time 13:51 Sent To  
Notes
2018-05-30 13:51:49RESUB ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-07-23 Time 13:46 Rev Time 0.00
Received By mcruz Date 2018-07-23 Time 13:44 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-20 Cont ID  
Sent By mcruz Date 2018-06-20 Time 10:01 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 16:29 Sent To B
Notes
2018-05-31 16:30:42NOTE - SHALL BE AT LEAST 3.5' FROM SIDE PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]