Plan Review Stops For Permit 18051320 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-07-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-30 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-30 |
Time |
10:31 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-06-20 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-06-20 |
Time |
08:11 |
Sent To |
I |
|
Notes |
2018-06-20 08:28:29 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR | | G007043-0 AND G007042-0 THAT'S SPECIFICATIONS WERE | | SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE | | AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT | | BE USED WITH THIS GENERATOR. FBC-R 301.1 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-07-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-31 |
Time |
06:09 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-07-31 |
Time |
06:04 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-06-07 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-06-07 |
Time |
06:14 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-06-07 |
Time |
06:04 |
Sent To |
|
|
Notes |
2018-06-07 06:14:48 | ROUTED TO GENERATOR/POOLS INBOX | | | | VALUE ADJUSTED TO 16500$ | | | | | | | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2018-08-20 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-08-20 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-08-20 |
Time |
16:50 |
Sent To |
|
|
Notes |
2018-08-20 16:51:51 | 08/20/18 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-07-30 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-30 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-30 |
Time |
06:33 |
Sent To |
|
|
Notes |
2018-07-30 07:26:08 | 1) EXISTING GAS PLANS IN CITY RECORDS SHOW THE LONGEST | | DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET AS | | 104 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF | | THIS SYSTEM. 2017 FBCR- SEC. G2413.4.1. | | 2) EXISTING GAS PLAN ON FILE WITH THE CITY SHOWS A 1 | | INCH LINE TO THE INTERIOR EXISTING GAS FIXTURES BUT THE | | SUBMITTED GAS DRAWING SHOWS A 3/4 INCH LINE. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-06-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-03 |
Time |
06:54 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-03 |
Time |
06:07 |
Sent To |
|
|
Notes |
2018-06-03 06:54:39 | 1) EXISTING GAS PLPANS IN CITY RECORDS SHOW THE LONGEST | | DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET AS | | 104 FEET. THIS DISTANCE SHALL BE USED IN THE SIZING OF | | THIS SYSTEM. 2017 FBCR- SEC. G2413.4.1. | | 2) THE PIPE SIZE OF THE SCH. 40 METALLIC PIPE AT THE | | OUTLET OF THE GAS METER SHALL BE 1 1/2 INCHES PER TABLE | | 402.4 (2) OF 2017 FBC-FUEL GAS, 2017 FBCR TABLE G2413.4 | | (2). | | 3) THE GAS PLAN SHOWS A 3/4 INCH GALVANIZED LINE AT THE | | OUTLET OF THE GAS METER., PLEASE EXPLAIN HOW YOU WILL | | SUPPLY AN 1 1/4 INCH PE LINE WITH A 3/4 INCH GALVANIZED | | LINE.THE EXISTING PLAN ON RECORD SHOWS AN 1 1/2 INCH | | LINE. | | 4) INDICATE ON THE PLAN HOW THE GALVANIZED PIPE WILL BE | | INSTALLED. WILL IT BE ATTACHED TO THE WALL OF THE | | STRUCTURE? SUBMIT ADDITIONAL INFO/DETAILS. WPB AMEND. | | TO FBC SEC. 107.2.1. | | 5) SHOW THE DISTANCE FROM THE METER TO FURTHEST OUTLET | | TO THE APPLIANCES IN THE STRUCTURE.WPB AMEND. TO FBC | | SEC. 107.2.1. | | 6) SHOW THE DISTANCE FROM THE EXISTING GAS METER TO THE | | POOL HEATER.WPB AMEND. TO FBC SEC. 107.2.1. | | 7) SHOW THE POOL HEATER AS EXISTING O NTHE GAS PLAN. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-08-20 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-08-20 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-08-16 |
Time |
13:33 |
Sent To |
|
|
Notes |
2018-08-17 13:33:25 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-07-31 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-07-31 |
Time |
06:09 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-07-16 |
Time |
14:41 |
Sent To |
|
|
Notes |
2018-07-17 14:41:29 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-20 |
Time |
08:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-29 |
Time |
13:51 |
Sent To |
|
|
Notes |
2018-05-30 13:51:49 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-07-23 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-07-23 |
Time |
13:44 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-06-20 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-05-31 |
Time |
16:29 |
Sent To |
B |
|
Notes |
2018-05-31 16:30:42 | NOTE - SHALL BE AT LEAST 3.5' FROM SIDE PROPERTY LINE. | | | | MAGGIE CRUZ | | ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1442 | | E-MAIL: [email protected] |
|
|