Plan Review Details - Permit 18051249
Plan Review Stops For Permit 18051249
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 12:11 Rev Time 0.00
Received By shill Date 2018-06-16 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-11 Cont ID  
Sent By skennedy Date 2018-07-11 Time 11:21 Rev Time 0.00
Received By skennedy Date 2018-07-11 Time 11:21 Sent To  
Notes
2018-07-11 11:25:44SEE 17120465 LICENSE EC13005450

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-08 Cont ID  
Sent By fgiaquin Date 2018-07-08 Time 07:34 Rev Time 0.00
Received By fgiaquin Date 2018-07-08 Time 07:25 Sent To I
Notes
2018-07-08 07:34:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. (ELECTRICAL NOTES M-10, M-11) ON SUBMITTED PLAN ARE
 BEYOND THE SCOPE OF WORK FOR AN ES LICENSE HOLDER.
 ELECTRICAL SUB-PERMIT (18051250) CANNOT BE ISSUED. AN
 ER OR EC LICENSE HOLDER (LICENSED ELECTRICIAN) MUST
 PERFORM WORK NEEDED TO MEET DISCONNECT REQUIREMENTS OF
 NEC 600.6A(1)
  
 PLEASE SEE SCOPE OF WORK FOR ES LICENSE:
  
 F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SIGN
 CONTRACTORS SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR) THE SCOPE OF CERTIFICATION
 INCLUDES THE STRUCTURAL FABRICATION INCLUDING CONCRETE
 FOUNDATION, ERECTION, INSTALLATION, ALTERATION, REPAIR,
 SERVICE AND WIRING OF ELECTRICAL SIGNS AND OUTLINE
 LIGHTING. THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE
 THE PROVISION OF, OR ANY ELECTRICAL WORK BEYOND, THE
 LAST DISCONNECT MEAN OR TERMINAL POINTS. HOWEVER, A
 CONTRACTOR CERTIFIED UNDER THIS SECTION MAY PROVIDE THE
 ELECTRICAL ENTRANCE REQUIREMENTS FOR METERING AND MAIN
 DISCONNECT OF REMOTE BILLBOARDS OR SIGNS WHICH ARE
 INDEPENDENT OF ANY STRUCTURE OR BUILDING AND WHICH
 REQUIRE NO MORE THAN TWENTY-FIVE (25) KILOWATTS AT TWO
 HUNDRED FIFTY (250) VOLTS MAXIMUM.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-08 Cont ID  
Sent By fgiaquin Date 2018-06-14 Time 06:15 Rev Time 0.00
Received By fgiaquin Date 2018-06-14 Time 05:47 Sent To I
Notes
2018-06-14 06:11:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. (ELECTRICAL NOTES M-10, M-11) ON SUBMITTED PLAN ARE
 BEYOND THE SCOPE OF WORK FOR AN ES LICENSE HOLDER.
 ELECTRICAL SUB-PERMIT CANNOT BE ISSUED. AN ER OR EC
 LICENSE HOLDER MUST PERFORM WORK NEEDED TO MEET
 DISCONNECT REQUIREMENTS OF NEC 600.6A(1)
  
 PLEASE SEE SCOPE OF WORK FOR ES LICENSE:
  
 F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 SIGN
 CONTRACTORS SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR) THE SCOPE OF CERTIFICATION
 INCLUDES THE STRUCTURAL FABRICATION INCLUDING CONCRETE
 FOUNDATION, ERECTION, INSTALLATION, ALTERATION, REPAIR,
 SERVICE AND WIRING OF ELECTRICAL SIGNS AND OUTLINE
 LIGHTING. THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE
 THE PROVISION OF, OR ANY ELECTRICAL WORK BEYOND, THE
 LAST DISCONNECT MEAN OR TERMINAL POINTS. HOWEVER, A
 CONTRACTOR CERTIFIED UNDER THIS SECTION MAY PROVIDE THE
 ELECTRICAL ENTRANCE REQUIREMENTS FOR METERING AND MAIN
 DISCONNECT OF REMOTE BILLBOARDS OR SIGNS WHICH ARE
 INDEPENDENT OF ANY STRUCTURE OR BUILDING AND WHICH
 REQUIRE NO MORE THAN TWENTY-FIVE (25) KILOWATTS AT TWO
 HUNDRED FIFTY (250) VOLTS MAXIMUM.
  
 2. F.A.C. 61G15-23.004 (3)(C)(3) A PHYSICAL COPY OF AN
 ELECTRONICALLY OR DIGITALLY SIGNED, DATED AND SEALED
 DOCUMENT IS NOT A VALID SIGNED, DATED AND SEALED
 DOCUMENT. SIMILARLY, AN ELECTRONIC DOCUMENT (PDF, SCAN
 OR FAX COPY) OF A PHYSICALLY SIGNED, DATED AND SEALED
 DOCUMENT IS NOT A VALID SIGNED, DATED AND SEALED
 DOCUMENT.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-08 Cont ID  
Sent By fgiaquin Date 2018-07-08 Time 07:37 Rev Time 0.00
Received By fgiaquin Date 2018-06-27 Time 13:10 Sent To  
Notes
2018-06-28 13:10:59RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-18 Cont ID  
Sent By cpuell Date 2018-06-18 Time 16:25 Rev Time 0.00
Received By cpuell Date 2018-05-25 Time 09:31 Sent To  
Notes
2018-06-16 12:12:016/16 TO ZONING BOX
  
2018-05-30 09:31:52ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-02 Cont ID  
Sent By mcruz Date 2018-07-02 Time 13:35 Rev Time 0.00
Received By mcruz Date 2018-07-02 Time 13:34 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-18 Cont ID  
Sent By mcruz Date 2018-06-18 Time 10:44 Rev Time 0.00
Received By mcruz Date 2018-06-18 Time 10:44 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 13:40 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 11:58 Sent To E
Notes
2018-05-31 13:39:12ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PROVIDE ACCURATE SIGN CALCULATION. THE MEASUREMENT
 SHOULD INCLUDE ALL LETTERS, INCLUDING THE LETTERS THAT
 EXTEND DOWN, SUCH AS THE "G" IN "DECORATING".
 2) CONFIRM BUILDING LENGTH, IT DOES NOT MATCH WITH
 MEASUREMENT TAKEN ON THE PROPERTY APPRAISER WEBSITE.
 3) PROVIDE THE HEIGHT OF THE BUILDING.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]