Plan Review Details - Permit 18051217
Plan Review Stops For Permit 18051217
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-30 Cont ID  
Sent By fgiaquin Date 2018-06-30 Time 07:36 Rev Time 0.00
Received By fgiaquin Date 2018-06-30 Time 07:28 Sent To I
Notes
2018-06-30 07:35:57INFORMATIONAL NOTE: ELECTRICAL PERMIT REQUIRED FOR 120V
 CONNECTION TO POWER SUPPLY. OUTSIDE OF SCOPE OF EF
 LICENSE. FS 489.505(7)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-12 Cont ID  
Sent By fgiaquin Date 2018-06-12 Time 06:28 Rev Time 0.00
Received By fgiaquin Date 2018-06-12 Time 06:12 Sent To I
Notes
2018-06-12 06:28:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SEE NOTES FROM FIRE MARSHALL.
  
 2. PROVIDE A MORE ACCURATE ADDRESS FOR LOCATION OF WORK
 ON APPLICATION. REFERENCING THE WHOLE BUILDING ( 701
 NORTHPOINT PKWY) WHEN THE WORK PROPOSED APPEARS TO BE
 LOCATED ON THE 5TH FLOOR IS UNACCEPTACLE.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5)
  
 3. A SEPARATE ELECTRICAL PERMIT WILL BE REQUIRED FOR
 120V CONNECTION ( BY CONTRACTOR THAT HOLDS AN EC OR ER
 LICENSE) TO POWER SUPPLY (AND/OR) SURGE PROTECTOR.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-29 Cont ID  
Sent By pleduc Date 2018-06-29 Time   Rev Time 0.00
Received By pleduc Date 2018-06-29 Time 12:56 Sent To E
Notes
2018-06-29 15:03:58PASSED PENDING INSPECTION AND TESTING OF ALL THE
 REQUIREMENTS OF THE CODE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-05-29 Cont ID  
Sent By pleduc Date 2018-05-29 Time   Rev Time 0.00
Received By pleduc Date 2018-05-29 Time 13:47 Sent To  
Notes
2018-05-29 15:36:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE TWO ELECTRONIC DOOR STRIKES LOCATED IN TWO
 SEPARATE STAIRWELLS.
  
 THESE STAIRWELLS ARE RATED AND NO EQUIPMENT IS TO BE
 LOCATED IN THESE STAIRWELLS UNLESS IT IS RELATED TO
 FUNCTION OF THE STAIRWELL.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT
 SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2.
  
 7.1.3.2 EXITS.
  
 (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE
 ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING:
 (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9)
 (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE
 (C) REQUIRED EXIT DOOR OPENINGS
 (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT
 STAIR PRESSURIZATION
 (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR
 COOLING OF THE EXIT ENCLOSURE
 (F) SPRINKLER PIPING
 (G) STANDPIPES
 (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH
 8.3.5
 (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS
 ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE
 PROTECTED IN ACCORDANCE WITH 8.3.5
  
  
 THERE IS NO INDICATIONS IN THE CODE FOR THIS EQUIPMENT.
  
  
 PLEASE REVIEW AND JUSTIFY WITH SPECIFIC CODE REFERENCES
 AND NARRATIVE.
  
  
  
 2) ADDITIONALLY TO #1 ABOVE, THERE ARE NO INDICATIONS
 OF EXIT RE-ENTRY ON THIS FLOOR OR ANY OTHER FLOOR WHERE
 THIS MAY BE ALLOWED.
  
 PER NFPA 1 & 101
  
 14.5.2.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE THAN
 FOUR STORIES, UNLESS PERMITTED BY 14.5.2.8.2, SHALL
 MEET ONE OF THE
 FOLLOWING CONDITIONS:
 (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR
 OF THE BUILDING
 SHALL BE PROVIDED.
 (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE
 INITIATION OF THE
 BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO UNLOCK
 ALL STAIR
 ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY.
 (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE
 WITH
 14.5.2.8.1.
 [101:7.2.1.5.8]
  
 PLEASE REVIEW AND JUSTIFY WITH SPECIFIC CODE REFERENCES
 AND NARRATIVE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-30 Cont ID  
Sent By fgiaquin Date 2018-06-30 Time 07:36 Rev Time 0.00
Received By fgiaquin Date 2018-06-27 Time 13:18 Sent To  
Notes
2018-06-28 13:18:35RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-12 Cont ID  
Sent By fgiaquin Date 2018-06-12 Time 06:28 Rev Time 0.00
Received By fgiaquin Date 2018-05-24 Time 11:29 Sent To  
Notes
2018-05-25 11:29:30ROUTED TO FIRE INBOX