Plan Review Details - Permit 18051191
Plan Review Stops For Permit 18051191
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 10:10 Rev Time 0.00
Received By shill Date 2018-11-06 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 21:27 Rev Time 0.00
Received By shill Date 2018-11-02 Time 21:27 Sent To  
Notes
2018-11-02 21:31:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE NEW ARCHITECTURAL SHEETS ARE SIGNED BUT NOT
 SEALED, FS481.
  
 PLEASE CONTACT ME TO DISCUSS THE BEST RESOLUTION TO
 AVOID A 4TH REVIEW CYCLE. IF ARCHITECTURAL PAGES ARE
 REPLACED, THIS WILL NEED ZONING, BUILDING, FIRE, AND
 PLUMBING REVIEWS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 15:37 Rev Time 0.00
Received By shill Date 2018-09-22 Time 15:37 Sent To  
Notes
2018-09-22 15:38:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, PROVIDE TWO IDENTICAL SETS OF PLANS FOR
 PERMIT ISSUANCE. ONE SET IS MISSING PAGES.
  
 2. DUE TO THE ISSUES WITH THE ADDRESS AT THIS LOCATION,
 PROVIDE A SITE PLAN SHOWING THIS UNIT RELATIVE TO THE
 ENTIRE SITE. THIS CAN BE DONE USING AN AERIAL, SITE
 PLAN OR SURVEY.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-08 Cont ID  
Sent By shill Date 2018-06-08 Time 18:06 Rev Time 0.00
Received By shill Date 2018-06-08 Time 18:03 Sent To  
Notes
2018-06-08 18:13:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC A 803, REVISE PLAN TO SHOW COMPLIANCE (DRESSING
 ROOMS).
  
 2. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC B
 1603.1.4.
  
 3. THE SECOND EXIT IS THROUGH THE STORAGE AREA; SEE FBC
 B 1016.2(5). REVISE PLAN TO CLARIFY COMPLIANCE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-03 Cont ID  
Sent By jpearson Date 2018-09-03 Time 09:42 Rev Time 0.00
Received By jpearson Date 2018-09-03 Time 09:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By jpearson Date 2018-06-07 Time 16:10 Rev Time 0.00
Received By jpearson Date 2018-06-07 Time 14:56 Sent To  
Notes
2018-06-07 16:10:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE SHOW WINDOW OUTLETS AND CIRCUIT PER NEC
 210.62
 2. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION FOR SIGN AND SHOW WINDOW
 OUTLETS. FBC EC C405.2.5
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 5. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63
 6. WATER HEATER LOAD DOES NOT MATCH THE SPECIFIED
 TANKLESS HEATER ON SHEET P-1. PROVIDE CORRECTION. NEC
 220; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-10-12 Cont ID  
Sent By pleduc Date 2018-10-12 Time   Rev Time 0.00
Received By pleduc Date 2018-10-12 Time 11:33 Sent To I
Notes
2018-10-12 11:35:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 0.10 - THE LIFE SAFETY PLAN INDICATES REAR
 EXIT SIGNS LEADING THRU THE STORAGE AREA.
  
 COMPLIED
  
  
  
 2) ANY WORK OF THE FIRE SPRINKLER AND/OR FIRE ALARM
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By pleduc Date 2018-08-29 Time   Rev Time 0.00
Received By pleduc Date 2018-08-28 Time 16:16 Sent To  
Notes
2018-08-28 16:22:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 0.10 - THE LIFE SAFETY PLAN INDICATES REAR
 EXIT SIGNS LEADING THRU THE STORAGE AREA.
  
 PER NFPA 101, CHAPTER 7,MEANS OF EGRESS
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE THROUGH ADJOINING OR INTERVENING ROOMS
 OR AREAS, PROVIDED THAT SUCH ROOMS OR AREAS ARE
 ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE CONSTRUED AS INTERVENING ROOMS. EXIT
 ACCESS SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO
 PASS THROUGH ANY AREA IDENTIFIED UNDER PROTECTION FROM
 HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 A STORAGE ROOM IS IDENTIFIED AS ONE OF THESE AREAS.
  
 HOWEVER, ONLY ONE EXIT IS REQUIRED FROM THE MAIN
 MERCANTILE AREA AND ONE FROM THE STORAGE ROOM.
  
 36.2.4 NUMBER OF MEANS OF EGRESS.
 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH
 36.2.4.5:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
  
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 MOVE ONE EXIT SIGN IN THE HALL LEADING TO THE FRONT
 EXIT AND REMOVE THE ONE OVER THE STORAGE ROOM DOOR.
  
  
 2) ANY WORK OF THE FIRE SPRINKLER AND/OR FIRE ALARM
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-29 Cont ID  
Sent By pleduc Date 2018-05-29 Time   Rev Time 0.00
Received By pleduc Date 2018-05-29 Time 13:47 Sent To  
Notes
2018-05-29 15:00:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 0.10 - THE LIFE SAFETY PLAN INDICATES REAR
 EXIT SIGNS LEADING THRU THE STORAGE AREA.
  
 PER NFPA 101, CHAPTER 7,MEANS OF EGRESS
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE THROUGH ADJOINING OR INTERVENING ROOMS
 OR AREAS, PROVIDED THAT SUCH ROOMS OR AREAS ARE
 ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE CONSTRUED AS INTERVENING ROOMS. EXIT
 ACCESS SHALL BE ARRANGED SO THAT IT IS NOT NECESSARY TO
 PASS THROUGH ANY AREA IDENTIFIED UNDER PROTECTION FROM
 HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 A STORAGE ROOM IS IDENTIFIED AS ONE OF THESE AREAS.
  
 HOWEVER, ONLY ONE EXIT IS REQUIRED FROM THE MAIN
 MERCANTILE AREA AND ONE FROM THE STORAGE ROOM.
  
 36.2.4 NUMBER OF MEANS OF EGRESS.
 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH
 36.2.4.5:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
  
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 MOVE ONE EXIT SIGN IN THE HALL LEADING TO THE FRONT
 EXIT AND REMOVE THE ONE OVER THE STORAGE ROOM DOOR.
  
  
 2) ANY WORK OF THE FIRE SPRINKLER AND/OR FIRE ALARM
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 21:27 Rev Time 0.00
Received By shill Date 2018-10-10 Time 09:55 Sent To  
Notes
2018-10-12 09:56:01B29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 15:38 Rev Time 0.00
Received By shill Date 2018-08-24 Time 13:45 Sent To  
Notes
2018-08-27 13:45:45B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-13 Cont ID  
Sent By gjohnson Date 2018-06-13 Time 09:58 Rev Time 0.00
Received By gjohnson Date 2018-05-24 Time 13:59 Sent To  
Notes
2018-05-25 13:59:47B28

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-05 Cont ID  
Sent By ccole Date 2018-09-05 Time 10:26 Rev Time 0.00
Received By ccole Date 2018-09-05 Time 10:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By ccole Date 2018-05-31 Time 17:23 Rev Time 0.00
Received By ccole Date 2018-05-31 Time 14:47 Sent To  
Notes
2018-05-31 17:36:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051191
 5/31/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2: THE ARCHITECTURAL PLANS SHOW THREE
 DRESSING ROOMS WHICH ARE REQUIRED TO HAVE EXHAUST
 VENTILATION AT A RATE OF 0.25 CFMS PER SF- TABLE
 403.3.1.1 FBC M.
  
 2) M-2, KEYED NOTE #4: THE CONDENSATE FROM THE AIR
 HANDLER CANNOT DRAIN INTO THE SANITARY SYSTEM PER
 SECTION 90-126 WEST PALM BEACH CODE OF ORDINANCES.
 PLEASE PROVIODE AN APPROVED PLACE OF DISPOSAL, AND SHOW
 THE PIPING RUN AND DISCHARGE LOCATION IN ACCORDANCE
 WITH SECTION 307.2.1 FBC M.
  
 3) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE NEW CONDENSER TO THE EXISTING
 STAND, AND SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE ANCHORING CLIP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-31 Cont ID  
Sent By gjohnson Date 2018-10-31 Time 17:01 Rev Time 0.00
Received By gjohnson Date 2018-10-31 Time 16:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-09-13 Cont ID  
Sent By shill Date 2018-09-13 Time 14:33 Rev Time 0.00
Received By jesmith Date 2018-09-13 Time 14:25 Sent To  
Notes
2018-09-13 14:33:342ND REVIEW: FBC 2017 6TH EDITION
 PERMIT 18051191
 PLUMBING COMMENTS: DENIED
  
 1. A DRINKING FOUNTAIN IS REQUIRED. PER FBC PLUMBING
 403.1 AND SHALL COMPLY WITH FBC ACC 602, 211.2
 A. THE ARCHITECT'S RESPONSE TO THE INITIAL REQUIREMENT
 ALONG WITH THE LETTER STATING THE OCCUPANCY WOULD BE
 LESS THAN 15 DOES NOT CHANGE THE FACT THAT THE NUMBER
 OF OCCUPANTS (DEEMED 22) SHALL BE DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING PER FBC PLUMBING 403.1
 B. THE ONLY EXCEPTION FOR APPROVAL FOR A REDUCED
 OCCUPANCY LOAD IS NOTED IN FBC BUILDING 1004.1.2 AND
 NEEDS TO BE ADDRESSED TO THE BUILDING OFFICIAL FOR
 APPROVAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-13 Cont ID  
Sent By gjohnson Date 2018-06-13 Time 09:39 Rev Time 0.00
Received By gjohnson Date 2018-06-13 Time 09:09 Sent To  
Notes
2018-06-13 09:58:301ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE
 WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
  
 4. THE SERVICE SINK CANNOT DISCHARGE THRU THE WET VENT
 OF THE BATHROOM GROUP, THE FIXTURE BRANCH FOR THE
 SERVICE SICK SHALL CONNECT DOWN STREAM OF THE BATHROOM
 GROUP. PER FBC PL 912.1
  
 5. THE LAVATORY IN THE BATHROOM SHALL ONLY HAVE
 TEMPERED WATER DELIVERED THRU A TEMPERATURE LIMITING
 DEVISE COMPILING WITH ASSE 1070 OR CSA B125.3 AND NSF
 372. PER FBC 416.5 AND 605.2.1
  
 6. A DRINKING FOUNTAIN IS REQUIRED. PER FBC PL 403.1
 AND SHALL COMPLY WITH FBC ACC 602, 211.2
  
 7. SHT. P-3 PROVIDE FIRE STOPPING DETAIL FOR PVC PIPE
 AND COPPER THRU GYPSUM WALL BOARD ASSEMBLY'S. PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By eschneid Date 2018-10-30 Time 15:57 Rev Time 0.25
Received By eschneid Date 2018-10-30 Time 15:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-08-31 Cont ID  
Sent By eschneid Date 2018-08-31 Time 15:42 Rev Time 0.25
Received By eschneid Date 2018-08-31 Time 15:42 Sent To  
Notes
2018-08-31 15:45:26FAILED
  
 1) RESOLUTION NO. 358-16 REQUIRES THAT WITHIN VILLAGE
 COMMONS, ALL NEW MECHANICAL EQUIPMENT, WHETHER GROUND
 OR ROOF MOUNTED, MUST BE SCREENED FROM VIEW OF THE
 PUBLIC. PLEASE PROVIDE VERIFICATION THAT THE NEW ROOF
 MOUNTED EQUIPMENT (CU) MEETS THIS REQUIREMENT. --- THIS
 REQUIREMENT DOES NOT ONLY APPLY TO THE FRONT BUT ALSO
 THE REAR PROPERTY. PROVIDE EVIDENCE THAT YOU ARE
 INSTALLING A LOWER PROFILE (I.E. SMALLER) CONDENSING
 UNIT THAN WHAT PREVIOUSLY EXISTS OR YOU WILL NEED TO
 INSTALL SCREENING MATERIAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-11 Cont ID  
Sent By eschneid Date 2018-06-11 Time 16:59 Rev Time 0.25
Received By eschneid Date 2018-06-11 Time 15:54 Sent To  
Notes
2018-06-11 16:59:59FAILED
  
 1) RESOLUTION NO. 358-16 REQUIRES THAT WITHIN VILLAGE
 COMMONS, ALL NEW MECHANICAL EQUIPMENT, WHETHER GROUND
 OR ROOF MOUNTED, MUST BE SCREENED FROM VIEW OF THE
 PUBLIC. PLEASE PROVIDE VERIFICATION THAT THE NEW ROOF
 MOUNTED EQUIPMENT (CU) MEETS THIS REQUIREMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]