Plan Review Details - Permit 18051171
Plan Review Stops For Permit 18051171
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-06-27 Cont ID  
Sent By rsklarew Date 2018-06-27 Time 14:49 Rev Time 0.00
Received By rsklarew Date 2018-06-27 Time 14:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 06:46 Rev Time 0.00
Received By tklarge Date 2018-06-02 Time 06:46 Sent To  
Notes
2018-06-02 06:46:311) NFPA 58-2014 SEC. 6.3.2.3 - NO PART OF AN
 UNDERGROUND OR MOUNDED ASME CONTAINER SHALL BE LESS
 THAN 10 FT (3 M) FROM A BUILDING OR LINE OF ADJOINING
 PROPERTY THAT CAN BE BUILT UPON. SHOW THE DDISTANCE OF
 THE LP TANK FROM THE STRUCTURE.
 2) A SHUTOFF VALVE IS REQUIRED UPSTREAM OF THE PRESSURE
 REGULATORS.
 3) SUBMIT MANUF. SPECS FOR THE FLEX CONNECTORS.THE FLEX
 CONNECTOR SHALL BE APPROVED TO FLOW THE MAXIMUM BTU
 LOAD FOR THE GENERATOR. 2017 FBCR SEC. G2422.1 (8).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 06:46 Rev Time 0.00
Received By tklarge Date 2018-06-02 Time 06:46 Sent To  
Notes
***NONE***