2018-06-15 12:22:10BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE FOUNDATION PLAN WITH MANUFACTURERS
 INSTALLATION INSTRUCTIONS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-05 Cont ID  
Sent By fgiaquin Date 2018-06-05 Time 05:52 Rev Time 0.00
Received By fgiaquin Date 2018-06-05 Time 05:24 Sent To  
Notes
2018-06-05 05:52:27ROUTED TO GENERATOR/POOLS INBOX.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-06-25 Cont ID  
Sent By lcrespo Date 2018-06-25 Time 13:46 Rev Time 0.00
Received By lcrespo Date 2018-06-25 Time 13:46 Sent To  
Notes
2018-06-25 13:47:4706/25/18 APPROVED BY PLUMBING AND SENT TO PROCESSING,
 LAC

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 06:45 Rev Time 0.00
Received By tklarge Date 2018-06-02 Time 06:08 Sent To  
Notes
2018-06-02 06:45:351) NFPA 58-2014 SEC. 6.3.2.3 - NO PART OF AN
 UNDERGROUND OR MOUNDED ASME CONTAINER SHALL BE LESS
 THAN 10 FT (3 M) FROM A BUILDING OR LINE OF ADJOINING
 PROPERTY THAT CAN BE BUILT UPON. SHOW THE DDISTANCE OF
 THE LP TANK FROM THE STRUCTURE.
 2) A SHUTOFF VALVE IS REQUIRED UPSTREAM OF THE PRESSURE
 REGULATORS.
 3) SUBMIT MANUF. SPECS FOR THE FLEX CONNECTORS.THE FLEX
 CONNECTOR SHALL BE APPROVED TO FLOW THE MAXIMUM BTU
 LOAD FOR THE GENERATOR. 2017 FBCR SEC. G2422.1 (8).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-25 Cont ID  
Sent By lcrespo Date 2018-06-25 Time 13:46 Rev Time 0.00
Received By lcrespo Date 2018-06-15 Time 12:57 Sent To  
Notes
2018-06-18 12:57:36RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-15 Cont ID  
Sent By cthroop Date 2018-06-15 Time 12:22 Rev Time 0.00
Received By cthroop Date 2018-05-24 Time 11:15 Sent To I
Notes
2018-05-25 11:16:09ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-20 Cont ID  
Sent By mcruz Date 2018-06-20 Time 09:46 Rev Time 0.00
Received By mcruz Date 2018-06-20 Time 09:46 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-30 Cont ID  
Sent By mcruz Date 2018-05-30 Time 15:37 Rev Time 0.00
Received By mcruz Date 2018-05-30 Time 15:19 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved