Plan Review Details - Permit 18051156
Plan Review Stops For Permit 18051156
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-29 Cont ID  
Sent By pleduc Date 2018-05-29 Time   Rev Time 0.00
Received By pleduc Date 2018-05-29 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-06-22 Time   Rev Time 0.00
Received By lmarchan Date 2018-06-19 Time 14:26 Sent To  
Notes
2018-06-20 14:26:32RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-06-11 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-24 Time 14:01 Sent To  
Notes
2018-05-25 14:02:03ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-06-22 Cont ID  
Sent By ccole Date 2018-06-22 Time 12:17 Rev Time 0.00
Received By ccole Date 2018-06-22 Time 12:17 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-11 Cont ID  
Sent By ccole Date 2018-06-11 Time 07:30 Rev Time 0.00
Received By ccole Date 2018-06-08 Time 17:13 Sent To I
Notes
2018-06-11 07:45:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051156
 6/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 508.1.1 FBC M AND SHOW COMPLIANCE.
 MAKEUP AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10F (6C)
 EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS OF THE
 MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE HVAC
 SYSTEM.
  
 ADVISORY: IF CHOOSING TO MEET THE EXCEPTION AS STATED
 IN THE CODE SECTION ABOVE, AC LOAD CALCULATIONS MUST BE
 SUBMITTED THAT INCLUDE THE ADDED HEAT LOAD OF THE
 MAKEUP AIR. PLEASE CONTACT CAPTIVEAIRE FOR DATA
 INDICATING THE PERCENTAGE OF MAKEUP AIR THAT IS
 EXHAUSTED, AND THE PERCENTAGE THAT SPILLS OVER INTO THE
 KITCHEN SPACE.
  
 2) SUBMIT THE NOA'S FOR THE ROOF FANS- RULE 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  