Plan Review Details - Permit 18051051
Plan Review Stops For Permit 18051051
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-07 Cont ID  
Sent By shill Date 2018-09-07 Time 18:13 Rev Time 0.00
Received By shill Date 2018-09-07 Time 18:13 Sent To  
Notes
2018-09-07 18:14:18SHEET SP01 REDLINED; COVERED PARKING CONFIGURATION DOES
 NOT MATCH ALS1.1 (LACKS ACCOMMODATION FOR ACCESSIBLE
 SPACE)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 18:28 Rev Time 0.00
Received By shill Date 2018-08-27 Time 18:28 Sent To  
Notes
2018-08-27 18:29:12***PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 A. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
  
 MONUMENT AND OTHER SIGNS
 PARKING LOT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 14:24 Rev Time 0.00
Received By shill Date 2018-06-30 Time 14:15 Sent To  
Notes
2018-06-30 14:24:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ALS 1.1, COVERED PARKING IS SHOWN, WITH NO
 ACCESSIBLE COVERED PARKING.
  
 SEE FBC A 208.3.1 AND ADVISORY. PRIOR TO RESUBMITTING,
 EITHER REVISE TO INCLUDE ACCESSIBLE PARKING IN THIS
 LOCATION OR SEND A SIGNED AND SEALED LETTER, OR LETTER
 PREPARED BY OWNER, DESCRIBING USE OF THIS PARKING AREA.
 IF THIS IS RESERVED PARKING, IT IS POSSIBLE THAT OWNER
 CAN AGREE TO PROVIDE COVERED ACCESSIBLE PARKING UPON
 REQUEST AS NEEDED. IF A FEE IS CHARGED FOR THIS
 PARKING, AN ADDITIONAL FEE CANNOT BE CHARGED FOR THE
 ACCESS AISLE.
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS. IF ACCESSIBLE
 PARKING IS NOT PROVIDED IN THIS LOCATION, PLEASE SEND
 LETTER PRIOR TO RESUBMITTAL FOR PRELIMINARY REVIEW AND
 APPROVAL BY BUILDING OFFICIAL.
  
 2. FBC A 236.1, 1004, REVISE PLAN TO SHOW COMPLIANCE
 (EXERCISE MACHINES).
  
 3. DOORS 100A, 103A, 104, REVISE PLAN TO SHOW 18"
 REQUIRED MANEUVERING CLEARANCE, PULL SIDE, FBC A FIGURE
 404.2.4.1(A).
  
 4. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
  
 MONUMENT AND OTHER SIGNS
 PARKING LOT
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-03 Cont ID  
Sent By jpearson Date 2018-07-03 Time 11:24 Rev Time 0.00
Received By jpearson Date 2018-07-03 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-20 Cont ID  
Sent By pleduc Date 2018-08-20 Time   Rev Time 0.00
Received By pleduc Date 2018-08-20 Time 09:30 Sent To  
Notes
2018-08-20 09:39:252ND REVIEW COMMENTS
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE APPEARS TO BE EXIT SIGNS ON THE LIFE SAFETY
 PLAN THAT DO NOT APPEAR ON THE ELECTICAL PLAN SHEETS.
  
 PLEASE ENSURE THAT THE EXIT SIGNS ARE CONSISTENT WITH
 LIFE SAFETY PLAN.
  
  
 2) PROVIDE REVISISED DRAWING TO SHOW ALL EXIT SIGNS
 LOCATIONS AS APPLICABLE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-06-12 Cont ID  
Sent By pleduc Date 2018-06-12 Time   Rev Time 0.00
Received By pleduc Date 2018-05-25 Time 16:32 Sent To  
Notes
2018-06-12 16:09:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE APPEARS TO BE EXIT SIGNS ON THE LIFE SAFETY
 PLAN THAT DO NOT APPEAR ON THE ELECTICAL PLAN SHEETS.
  
 PLEASE ENSURE THAT THE EXIT SIGNS ARE CONSISTENT WITH
 LIFE SAFETY PLAN.
  
  
 2) PROVIDE REVISISED DRAWING TO SHOW ALL EXIT SIGNS
 LOCATIONS AS APPLICABLE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-17 Cont ID  
Sent By cpuell Date 2018-09-17 Time 09:12 Rev Time 0.00
Received By cpuell Date 2018-09-07 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-31 Cont ID  
Sent By lmarchan Date 2018-08-31 Time 14:55 Rev Time 0.00
Received By lmarchan Date 2018-08-07 Time 15:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-25 Cont ID  
Sent By lmarchan Date 2018-07-25 Time 12:54 Rev Time 0.00
Received By lmarchan Date 2018-05-23 Time 10:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-09-17 Cont ID  
Sent By cpuell Date 2018-09-17 Time 09:11 Rev Time 0.00
Received By cpuell Date 2018-09-13 Time 14:09 Sent To  
Notes
2018-09-17 09:12:03PASSED BY IMPACT FEE OFFICE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-12 Cont ID  
Sent By shill Date 2018-06-30 Time 14:25 Rev Time 0.00
Received By shill Date 2018-06-30 Time 14:25 Sent To  
Notes
2018-09-12 14:55:32PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-31 Cont ID  
Sent By skennedy Date 2018-08-31 Time 13:32 Rev Time 0.00
Received By skennedy Date 2018-08-31 Time 13:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-25 Cont ID  
Sent By ccole Date 2018-06-25 Time 15:06 Rev Time 0.00
Received By ccole Date 2018-06-25 Time 15:02 Sent To  
Notes
2018-06-25 15:29:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051051
 6/25/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.1: THE O/A CALCULATIONS FOR AHU-1 ARE
 INCORRECT ACCORDING TO TABLE 403.3.1.1 FBC M. THE TOTAL
 NUMBER OF PEOPLE FOR CONFERENCE ROOMS IS BASED ON 50
 PERSONS PER SQ. FT. PLEASE CORRECT THE CALCULATIONS AND
 THE OUTDATED CODE REFERENCE.
  
 2) M2.1: PLEASE REVISE NOTE #2 TO INDICATE THE ACCESS
 HATCH WILL BE SIZED LARGE ENOUGH TO REMOVE AND REPLACE
 THE AIRHANDLER, AND A LEVEL WORKING SPACE NOT LESS THAN
 30 INCHES DEEP AND 30 INCHES WIDE SHALL BE PROVIDED IN
 FRONT OF THE CONTROL SIDE OF THE UNIT- SECTION 306.1
 FBC M.
  
 3) M2.1: PLEASE PROVIDE A NOTE ON THE PLAN TO INDICATE
 THE EXTERIOR CONDENSERS WILL BE INSTALLED TO PROVIDE
 WORKING CLEARANCES PER THE MANUFACTURER, AND IN
 ACCORDANCE WITH SECTION 306.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-09-14 Cont ID  
Sent By tklarge Date 2018-09-14 Time 10:35 Rev Time 0.00
Received By tklarge Date 2018-09-11 Time 03:20 Sent To  
Notes
2018-09-14 10:36:05WITH PROVISOS.

Review Stop P PLUMBING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-08-26 Time   Rev Time 0.00
Received By gjohnson Date 2018-08-24 Time 14:51 Sent To  
Notes
2018-08-28 07:50:082ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE VENT MAYBE REQUIRED TO BE LARGER THAN 2IN. .
 VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH SHALL BE
 INCREASED BY ONE NOMINAL PIPE SIZE FOR THE ENTIRE
 DEVELOPED LENGTH OF THE VENT PIPE. INDICATE LENGTH OF
 ALL CONNECT VENTS ON PLAN. PER FBC PL 906.2
  
 2. THE DRINKING FOUNTAIN IS MISSING FROM THE WATER
 ISOMETRIC PLEASE CLARIFY.WPB AMEND TO FBC 107.2.1
  
 3. PREVIOUS COMMENT: ON THE SANITARY ISOMETRIC THE
 SHOWER IN THE STAFFF BATHROOM IS STILL LABELED AS A
 FLOOR DRAIN WITH A TRAP PRIMER PLEASE LABEL ALL FIXTURE
 TO MATCH THE FIXTURES THEY SERVE. PER WPB AMEND TO FBC
 107.2.1
  
 4. ON THE SANITARY ISOMETRIC PLEASE CORRECT THE
 FOLLOWING THE LAVATORY IN THE STAF BATHROOM IS NOT
 MARKED, THE BREAKROOM SINK AND THE MOP SINK ARE MARKED
 AS A LAVATORY. PER WPB AMEND TO FBC 107.2.1
  
 5. ON THE SANITARY ISOMETRIC IN THE STAFF BATHROOM WITH
 THE SHOWER THE LAVATORY BRANCH DRAIN SHALL CONNECT
 BETWEEN THE TOILET AND SHOWER, TWO FIXTURE ARE NPT
 PERMITTED UP STREAM OF THE VENT ON A WET VENT SYSTEM.
 PER FBC PL 912.1
  
 6. THE DRINKING FOUNTAIN IS MISSING THE VENT ON THE
 ISOMETRIC DRAWING. PLEASE CLARIFY. PER FBC PL 901.2.1
  
 7. ON SHT. A9.0.2 IT APPEARS THAT THE INSIDE CLEAR
 DIMENSION OF THE TRANSFER SHOWER IN THE STAFF BATHROOM
 IS SHOWING 3'-11/4" IT SHALL BE 36" INSIDE DIMENSION.
 FBC ACC 608.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2018-08-27 09:49:53REVIEW BY GEORGE JOHNSON.

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-13 Cont ID  
Sent By tklarge Date 2018-07-13 Time 12:12 Rev Time 0.00
Received By tklarge Date 2018-07-02 Time 05:05 Sent To  
Notes
2018-07-05 14:51:431) INDICATE THE LEVEL OF ALTERATION ON BOTH SETS OF
 PLANS PER THE 2017 FBC-EXISTING SECTION 301.1.
 2) SHT. L-3 - SHOW THE LOCATION OF THE IRRIGATION PUMP,
 CONTROLLER AND RAIN SENSOR. ALSO, SHOW THE WATER SOURCE
 FOR THE IRRIGATION SYSTEM ON THE PLAN. IF CONNECTED TO
 CITY WATER, A REDUCED PRESSURE ZONE BACKFLOW PREVENTION
 DEVICE WILL BE REQUIRED ON THE IRRIGATION SYSTEM.CWPB
 CROSS-CONNECTION CONTROL MANUAL & WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) PLACE A NOTE ON SHT. L-3 THAT IRRIGATION HEADS SHALL
 BE PLACED A MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE
 SIDEWALL. 2017 FBC- PLUMBING SEC.318.1.
 4) SHT. ALS 1.1 - PLUMBING FIXTURE REQUIREMENTS - THE
 TOILET FACILITIES ARE NOTED AS "UNISEX." THE TOILET
 ROOMS MUST BE DESIGNATED AS "MALE" AND "FEMALE" IN
 ACCORDANCE WITH THE 2017 FBC-PLUMBING SEC. 403.2.
 5) SHT. A9.0.2 - SHOW THE CLEAR INSIDE DIMENSIONS ( L X
 W ) OF THE ALL THE TOILET ROOMS ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SHT. A9.0.2. - SHOW THE INSIDE CLEAR DIMENSIONS OF
 THE ACCESSIBLE SHOWER IN THE STAFF TOILET ROOM ON THE
 PLANS. COMPLY WITH 2017 FBC-ACCESS. SEC.608.2.
 7) SHOW THE DIMENSIONS OF THE CLEAR FLOOR SPACES FOR
 THE HANDICAPPED ACCESSIBLE FIXTURES. COMPLY WITH 2017
 FBC-ACCESS. SECS. 608.2.1, 604.3, 606.2
 8) SHT. A9.0.1 - THE STAFF ROOM SINK SHALL COMPLY WITH
 2017 FBC-ACCESSIBILITY SEC.606.2.
 9) SUBMIT A RAINWATER RISER AND SHOW THE SIZE OF THE
 ROOF DRAINS ON SHT. A2.0.1 AND HOW YOU ARRIVED AT THE
 ROOF DRAIN SIZE. COMPLY WITH 2017 FBC-PLUMBING
 SEC.1106.2.
 10) SHT. A5.0.2 - SUBMIT CALCULATIONS FOR THE SIZING OF
 THE INTEGRAL GUTTERS AT THE ROOF EDGE. COMPLY WITH
 TABLE 1106.6 OF THE 2017 FBC-PLUMBING.
 11) SHT. A9.0.1 -THE REFRESHMENT CENTER CABINET HEIGHT
 SHALL BE A MAXIMUM OF 34 INCHES IN HEIGHT. 2017
 FBC-ACCESS. SEC.902.3. IDENTIFY THE REFRESHMENT CENTER
 ON SHT. A9.0.2.
 12) SHT.A9.0.1 - TTHE MAXIMUM HEIGHT OF THE SINK
 CABINET IN THE STAFF LOUNGE SHALL BE 34 INCHES MAXIMUM
 PER 2017 FBC-ACCESS. SEC.902.3.
 13) SHT. A9.0.2 - DETAILS A, B & C - DETAIL A NOTES THE
 TOILET ROOMS AS #104 & #105 BUT THE FLOOR PLAN SHOWS
 #118 & 119.THE SAME TYPE OF DISCREPANCY OCCURS ON
 DETAILS B & C. CLARIFY.
 14) TOILET ROOM #111 - THE DOOR CANNOT SWING INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY PER THE 2017
 FBC-ACCESS. SEC.603.2.3.
 15) SHT. A9.0.2 - SHOW THE HEIGHT OF THE SHOWER SEAT.
 COMPLY WITH 2017 FBC- ACCESS. SECS. 610.3, 610.3.2.
 16) THE GRAB BARS IN THE TRANSFER SHOWER SHALL COMPLY
 WITH 2017 FBC-ACCESS. SEC.608.3.1 ANSD FIG.608.3.1.
 17) THE LOCATION OF THE SHOWER CONTROLS IN THE STAFF
 TOILET SHOWER SHALL COMLY WITH 2017 FBC-ACCESS.
 SEC.608.5.1.
 18) THE SHOWER SPRAY UNIT IN THE STAFF TOILET SHOWER
 SHALL COMPLY WITH 2017 FBC-ACCESS. SEC.608.6.
 19) SUBMIT DETAILS FOR THE REQUIRED REINFORCEMENT FOR
 FUTURE GRAB BARS IN THE PRIVATE TOILET. SHOW THE TYPE
 OF MATERIAL, LENGTH, WIDTH AND HEIGHT OF THE
 REINFORCEMENT. 2017 FBC-ACCESS. SECS.604.5, 609.8.
 22) SHT. A10.0.1 - DETAIL #11 - THE SHOWER FLOOR SHALL
 BE PITCHED A MINIMUM OF 1/4 INCH PER FOOT TO THE DRAIN.
 2017 FBC-PLUMBING SEC.417.5.2.
 23) SHT.A10.0.2. - DETAIL #7 - THE MAXIMUM HEIGHT OF
 THE CABINET AT THE STAFF LOUNGE SHALL BE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR.2017 FBC-ACCESS.
 SEC.902.3.
 24) THE REACH RANGES AT THE CABINETS SHALL COMPLY WITH
 2017 FBC-ACCESS. SEC.308.3.2,
 25) SHT. P2.1 SHOWS ALL THE VENTS THROUGH THE ROOF AND
 ALSO LOOPED TOGETHER. WHICH IS IT? CLARIFY. A MINIMUM
 OF ONE MMAIN VENT THROUGH THE ROOF IS REQUIRED. 2017
 FBC-PLUMBING SEC.904.1.
 26) SHT. P0.1 - THE SHOWERS ARE SHOWN AS FLOOR DRAINS
 WITH TRAP PRIMERS ON THE SANITARY RISERS. REVISE THE
 RISER AND CORRECTLY IDENTIFY ALLL THE FIXTURES ON THE
 SANITARY RISER.ID
 27) SHT.P0.1 - PLUMBING NOTES - THERE ARE SEVERAL NOTES
 THAT REFER TO THE 2010 FBC. CORRECT THE NOTES TO REFER
 TO THE 2017 FBC. THIS ALSO OCCURS AT THE WATER HEATER
 DETAIL.
 28) THE WATER HEATER TEMPERATURE AND RELIEFF LIINE
 SHALL DISCHARGE TO THROUGH AN AIR GAP LOCATED IN THE
 SAME ROOM AS THE WATTER HEATER. 2017 FBC-PLUMBING
 SEC.504.6 (2)
 29) TEMPERED WATER IS REQUIRED TO THE LAVATORIES IN THE
 TOILET ROOMS.2017 FBC-PLUMBING SEC.607.1. TEMPERED
 WATER SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070. 2017
 FBC-PLUMBING SEC.607.1.2.
 30 ) HOT WATER IS REQUIRED TO THE STAFF LOUNGE SINK AND
 THE MOP SINK. 2017 FBC-PLUMBING SEC. 607.1.
 31) THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER
 PIPING FROM THE HOT WATER SOURCE TO THE FIXTURES SHALL
 NOT EXCEED 50 FEET.2017 FBC-PLUMBING SEC.607.2.
 32) HOT WATER PIPE SHALL BE INSULATED IN ACCORDANCE
 WITH FBC-PLUMBING SEC.607.5.
 33) SHOW THE SIZE OF THE EXPANSION TANK ON THE WATER
 HEATER DETAIL.
 34) SHOW THE WIDTH OF THE PROPOSED ADAPTABLE SHOWER IN
 THE PRIVATE TOILET.
 35) A 30 INCH WIDE MINIMUM BY 48 INCH LONG MINIMUM
 CLEARANCE SHALL BE PROVIDED ADJACENT TO THE OPEN FACE
 OF THE SHOWER COMPARTMENT. THE SHOWER DOES NOT COMPLY
 DUE TO THE LOCATION OF THE WATER CLOSET. 2017 FBC
 -ACCESS. SECS. 608.2.2.1 & FIGURE 608.2.2.
 36) A CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48 INCHES
 LONG MINIMUM MEAURED FROM THE CONTROL WALL SHALL BE
 PROVIDED FOR THE ACCESSIBLE SHOWER IN THE STAFF TOILET.
 2017 FBC _ ACCESS. SEC.608.2.1 & FIGURE 608.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By gjohnson Date 2018-08-24 Time 14:59 Rev Time 0.00
Received By gjohnson Date 2018-08-24 Time 14:59 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 14:15 Rev Time 0.00
Received By shill Date 2018-06-30 Time 14:15 Sent To  
Notes
2018-06-30 14:15:48MIN R20, TPO OVER METAL DECK SPECIFIED
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD ARE TO
 BE SUBMITTED WITH THE ROOF PERMIT APPLICATION PRIOR TO
 INSTALLATION.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-09-14 Cont ID  
Sent By shill Date 2018-09-14 Time 13:42 Rev Time 0.00
Received By shill Date 2018-09-14 Time 13:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 18:32 Rev Time 0.00
Received By shill Date 2018-08-27 Time 18:31 Sent To  
Notes
2018-08-27 18:32:41A M E P SHEETS OK
 ENERGY CALCS OK
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 13:51 Rev Time 0.00
Received By shill Date 2018-06-30 Time 13:51 Sent To  
Notes
2018-06-30 13:52:39SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES) ARE IN
 ACCORDANCE WITH FS 471, FS 481 AS (A,S,M,E,P). NEW
 SHEETS SUBMITTED IN THE NEXT REVIEW CYCLE REQUIRE
 REVIEW.
  
 2. ENERGY CALCS S&S (IN SUPPORTING DOCUMENTS FOLDER) IS
 OK; NEED RE-REVIEW IF REPLACED BY A NEW DOCUMENT.
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-09-11 Time   Rev Time 0.00
Received By pgreilic Date 2018-09-11 Time 09:21 Sent To  
Notes
2018-09-11 09:23:071) SEPARATE PERMITS WILL BE REQUIRED FOR LANDSCAPING,
 SIGNAGE, DUMPSTER, FENCING ETC.
 2) LANDSCAPE PERMIT REQUIRED
 3) WPB WAYFINDING SIGN TO BE REPLACED, WILL RESEND
 DETAIL
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-08-31 Time   Rev Time 0.00
Received By pgreilic Date 2018-08-31 Time 14:28 Sent To  
Notes
2018-08-31 14:30:401.) UNCLEAR WHERE ON SITE BIKE RACK IS BEING PROPOSED,
 PLEASE CLARIFY ON REVISION
 2.) SIGNAGE. RESPONSE LETTER REFERENCES PALM BEACH
 COUNTY CODE. NOT APPLICABLE HERE. SIGNS LIMITED TO 10'
 MAX.
 3.) WPB WAYFINDING SIGN TO BE REPLACED AND UPDATED WITH
 DETAIL PROVIDED
 4.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2018-07-19 Time   Rev Time 0.00
Received By pgreilic Date 2018-07-19 Time 16:49 Sent To  
Notes
2018-07-19 16:49:391) LANDSCAPE PERMIT REQUIRED. LANDSCAPING ON SITE WILL
 BE REQUIRED TO MEET REGULATIONS OUTLINED IN ARTICLE XIV
 OF THE CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS.
 2) SEPARATE PERMITS WILL BE REQUIRED FOR LANDSCAPING,
 SIGNAGE, DUMPSTER, FENCING ETC. PLEASE NOTE MONUMENT
 SIGNS LOCATED IN GENERAL COMMERCIAL ZONING DISTRICTS
 ARE LIMITED TO 10 FEET IN HEIGHT.
 3) PROVIDE A BIKE RACK NEAR THE BUILDING ENTRANCE PER
 SEC. 94-485 AND INCLUDE CORRESPONDING DETAIL ON PLANS
 4) DIMENSION ALL RELEVANT COMPONENTS OF THE SITE PLAN
 INCLUDING PARKING SPACES, WALKWAYS, TERMINAL ISLANDS,
 DRIVE AISLES ETC.
 5) REMOVE PARKING SPACE AT NORTHEASTERN MOST CORNER OF
 THE SITE
 6) CONSIDER REDUCING THE WIDTH OF THE CENTRAL DRIVE
 AISLE TO 24 FEET PER SEC. 94-485
 7) CONSIDER CLOSURE OF WESTERNMOST DRIVEWAY
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  