Plan Review Details - Permit 18051040
Plan Review Stops For Permit 18051040
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-18 Cont ID  
Sent By jpearson Date 2018-07-18 Time 14:27 Rev Time 0.00
Received By jpearson Date 2018-07-18 Time 14:27 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-10 Cont ID  
Sent By jpearson Date 2018-07-10 Time 07:18 Rev Time 0.00
Received By jpearson Date 2018-07-10 Time 07:18 Sent To I
Notes
2018-07-10 07:18:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR REVISION WORK STATED ON PERMIT APPLICATION
 APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR.
 FBC 109.3 (NOT PROVIDED. CONTRACT SUBMITTED DOES NOT
 DETAIL THE ITEMS ADDED TO THIS LOT OR WHAT THE
 ADDITIONAL COST WILL BE.)
 2. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 (ORIGINAL PLANS WERE DRAWN TO A SCALE THAT IS
 ACCEPATABLE, BUT THE RE-SUBMISSION WAS ON A 8 1/2 X 11
 PIECE OF PAPER AND IS NOT ACCEPTABLE. PER WPB FBC
 107.2.1.3, QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. ORIGINAL PLANS NEED
 SIGNATURE, OR NEW SUBMISSION WITH SIGNATURES NEEDS TO
 BE SUPPLIED THAT MEET THE MINIMUM REQUIREMENTS.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By jpearson Date 2018-06-05 Time 10:59 Rev Time 0.00
Received By jpearson Date 2018-06-05 Time 10:59 Sent To I
Notes
2018-06-05 10:59:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR REVISION WORK STATED ON PERMIT APPLICATION
 APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR.
 FBC 109.3
 2. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-07-18 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-16 Time 13:33 Sent To  
Notes
2018-07-17 13:33:47RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-07-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-03 Time 15:45 Sent To  
Notes
2018-07-05 15:45:51RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-06-05 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-22 Time 14:12 Sent To  
Notes
2018-05-23 14:12:59REVISION ROUTED TO JPEARSON