Plan Review Details - Permit 18051002
Plan Review Stops For Permit 18051002
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-08 Cont ID  
Sent By fgiaquin Date 2018-06-08 Time 07:07 Rev Time 0.00
Received By fgiaquin Date 2018-06-08 Time 06:20 Sent To I
Notes
2018-06-08 07:05:46THE PLAN HAS BEEN PASSED PROVISIONALLY: FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECT FEE(S)
  
 1. PROVIDE PANEL SCHEDULE AND LOAD CALCULATION BY FINAL
 INSPECTION. PERMIT REFERENCED BY CONTRACTOR #18040526
 IS A STAND ALONE SERVICE CHANGE PERMIT WITH NO PANEL
 SCHEDULE OR LOAD CALCULATION.
  
 2. EGRESS LIGHTING REQUIRED AT ALL ENTRANCES/EXIT DOORS
 TO THE DWELLING EXECPT THE (VEHICLE DOOR) FOR THE
 GARAGE. FOR DWELLING UNITS, ATTACHED GARAGES, AND
 DETACHED GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3
  
 3. VALUE HAS BEEN ADJUSTED TO 4500$ THE INCREASED VALUE
 OF 1000$ ADDED TO THE INITIAL 2000$ TO MAKE 3000$ TOTAL
 IS INSUFFICIENT.
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-25 Cont ID  
Sent By fgiaquin Date 2018-05-25 Time 07:29 Rev Time 0.00
Received By fgiaquin Date 2018-05-25 Time 07:29 Sent To I
Notes
2018-05-25 07:29:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE
 REVIEW THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC:
  
 (A) PROVIDE CLEARLY DRAWN PLAN. LABEL ALL ROOMS SO THE
 LOCATIONS OF NECESSARY SMOKE ALARMS CAN BE ASCERTAINED.
 (B) PROVIDE LOCATIONS OF ANY DOORS PROVIDING EGRESS SO
 EGRESS LIGHTING CAN BE ADDRESSED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2. ADDRESS MUST BE ON PLAN
  
 3. (PRINT, SIGN, AND LICENSE #) ELECTRICAL PLAN IS
 REQUIRED TO BE DESIGNED AND SIGNED/SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC
 107.1
  
 4. PROVIDE LOAD CALCULATION. PROVIDE PANEL SCHEDULE
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. NEC
 210.8, 210.12, 215.5, 408.4; WPB FBC 107.3.5; FBC RE
 E3706.2, E3902
  
 5. VALUE TOO LOW. ADJUST VALUE OR CITY OF WPB WILL
 ADJUST TO THE APPROPRIATE VALUE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-08 Cont ID  
Sent By fgiaquin Date 2018-06-08 Time 07:07 Rev Time 0.00
Received By fgiaquin Date 2018-06-06 Time 11:36 Sent To I
Notes
2018-06-07 11:36:24RESUB ROUTED TO FGIAQUIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-25 Cont ID  
Sent By fgiaquin Date 2018-05-25 Time 07:29 Rev Time 0.00
Received By fgiaquin Date 2018-05-22 Time 11:48 Sent To I
Notes
2018-05-24 11:48:49ELEC <5K