2018-05-29 12:47:59 | 05/29/2018 1ST GAS REVIEW**DENIED** |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| |
| 1) SHOW WHAT SECTIONS OF PIPING IS CSST AND WHAT IS |
| GALV. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, |
| ALL PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING |
| (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| FBC SEC.107.2.1. |
| |
| 2) CITY RECORDS SHOWS EXISTING POOL HEATER. LIST THE |
| BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS.401.8, |
| 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR 2017 |
| FBC-RES. SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1 ) |
| THROUGH G2413.4 (21). |
| |
| 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| |
| 4) FOR THE GAS COOK TOP SUBMIT COMBUSTION AIR |
| CALCULATIONS FOR THE ADDED GAS APPLIANCES. WHERE |
| COMBUSTION AIR IS PROVIDED BY THE BUILDING?S MECHANICAL |
| VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE THE |
| SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS SEC.304.9.3 |
| OR FBCR G2407.9.3 |
| |
| 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. |
| |
| |
| TIM HUNT |
| PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| 561-805-6695 |
| [email protected] |
| |