Plan Review Details - Permit 18050879
Plan Review Stops For Permit 18050879
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-06-05 Cont ID  
Sent By rbrunell Date 2018-06-05 Time 13:59 Rev Time 0.00
Received By dharvey Date 2018-06-05 Time 13:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-06-05 Cont ID  
Sent By dharvey Date 2018-06-05 Time 13:59 Rev Time 0.00
Received By dharvey Date 2018-06-05 Time 13:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2018-06-05 Cont ID  
Sent By dharvey Date 2018-06-05 Time 13:59 Rev Time 0.00
Received By dharvey Date 2018-06-05 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-05 Cont ID  
Sent By dharvey Date 2018-06-05 Time 13:59 Rev Time 0.00
Received By dharvey Date 2018-05-30 Time 15:32 Sent To  
Notes
2018-06-01 14:54:59B33
2018-05-31 15:32:56RESUB OF REVISION ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-23 Cont ID  
Sent By thunt Date 2018-05-23 Time 06:32 Rev Time 0.00
Received By thunt Date 2018-05-18 Time 13:32 Sent To I
Notes
2018-05-21 13:32:44REVISION ROUTED TO THUNT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-06-05 Cont ID  
Sent By dharvey Date 2018-06-05 Time 14:00 Rev Time 0.00
Received By dharvey Date 2018-06-05 Time 14:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-06-05 Cont ID  
Sent By dharvey Date 2018-06-05 Time 14:00 Rev Time 0.00
Received By dharvey Date 2018-06-05 Time 14:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-06-01 Cont ID  
Sent By thunt Date 2018-06-01 Time 15:36 Rev Time 0.00
Received By thunt Date 2018-06-01 Time 15:36 Sent To  
Notes
2018-06-01 15:46:3106/01/2018 PLUMBING 2ND REVIEW**DENIED**
  
 *** NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT
 THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED
 CORRECTIONS***
  
 YOU HAVE FAILED TO EITHER NOT ADDRESS AT ALL OR NOT IN
 FULL ANY OF THE COMMENTS FROM THE LAST REVIEW. UNDER FL
 ST. STAUTE 553.80 (B) ANY PLAN REVIEW THAT IS DENIED
 FOR THE SAME COMMENTS 3X IS SUBJECT TO A 4X PLAN REVIEW
 FEE. I WOULD ADVISED YOU TO COME IN FOR A MEETING
 BEFORE RESUBMITTING AGAIN.
  
  
  
 A SEPARATE PERMIT APPLICATION IS REQUIRED FOR
 ELECTRICAL, MECHANICAL, AND FIRE PER FBC 105.1
  
 1) PROVIDE A FULL PLAN SHOW ALL DIMENSIONS REQUIRED
 UNDER THE SCOPE OF WORK. PLAN SHALL BE PREPARED SHOWING
 HOW YOU INTENT TO KEEP THE MASTER BATHROOM IN
 COMPLIANCE WITH FAIR HOUSING ACT SHOWING ALL THE
 REQUIRED CLEAR FLOOR SPACES AND NOW EXPANDING THE
 ACCESSIBLE ROUTE INTO BATHROOM #2 FOR ACCESS TO THE
 WASHER AND DRYER AS THIS DWELLING WAS DESIGNED UNDER
 SPECIFICATION B OF THE FHA. 24 CFR 100.205
  
 2) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS ARE PERMITTED TO BE SUBMITTED WHERE APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS. FBC 107.2.1
  
 3) PROVIDE A PLUMBING SANITARY RISER DRAWING AND SHOW
 HOW YOU INTENT TO CONNECT THE WASHING MACHINE STAND
 PIPE INTO THE EXISTING DRAINAGE SYSTEM. PLEASE BE
 ADVISE CONNECTING INTO THE BATHROOM HORIZONTAL WET VENT
 IS NOT ALLOWED UNDER FBC P 912.1
  
 4) YOU HAVE NOT PUT A VALUE ON THIS REVISION AND HAVE
 SIGNIFICANT CHANGES. PROVIDE A SIGNED BONA FIDE
 CONTRACT SHOW FULL VALUE OF ENTIRE JOB. WPB AMEND TO
 THE FBC 109.3
  
 5) PROVIDE WASHER AND DRYER INSTALLATION MANUALS/
 SPECIFICATION SHEETS. FBC 107.2.1
  
 6) SHOW DISTANCE THAT DRAIN IS TO BE MOVE (OFFSET) FROM
 EXISTING P-TRAP TO STAY IN COMPLIANCE WITH FBC P 1002.1
  
 7) PROVIDE A DETAIL CABINET DRAWING SHOW FINISHED
 ELEVATION AT MAX 34" FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By thunt Date 2018-05-23 Time 06:27 Rev Time 0.00
Received By thunt Date 2018-05-23 Time 06:26 Sent To  
Notes
2018-05-23 06:32:3205/23/2018 PLUMBING 1ST REVIEW**DENIED**
  
 *** NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT
 THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED
 CORRECTIONS***
  
 A SEPARATE PERMIT APPLICATION IS REQUIRED FOR
 ELECTRICAL, MECHANICAL, AND FIRE PER FBC 105.1
  
 1) PROVIDE A FULL PLAN SHOW ALL DIMENSIONS REQUIRED
 UNDER THE SCOPE OF WORK. PLAN SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES OR CHAPTER 481, FLORIDA
 STATUTES AND MUST SHOW HOW YOU INTENT TO KEEP THE
 MASTER BATHROOM IN COMPLIANCE WITH FAIR HOUSING ACT
 SHOWING ALL THE REQUIRED CLEAR FLOOR SPACES AND NOW
 EXPANDING THE ACCESSIBLE ROUTE INTO BATHROOM #2 FOR
 ACCESS TO THE WASHER AND DRYER AS THIS DWELLING WAS
 DESIGNED UNDER SPECIFICATION B OF THE FHA. 24 CFR
 100.205
  
 2) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS ARE PERMITTED TO BE SUBMITTED WHERE APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS. FBC 107.2.1
  
 3) PROVIDE A PLUMBING SANITARY RISER DRAWING AND SHOW
 HOW YOU INTENT TO CONNECT THE WASHING MACHINE STAND
 PIPE INTO THE EXISTING DRAINAGE SYSTEM. PLEASE BE
 ADVISE CONNECTING INTO THE BATHROOM HORIZONTAL WET VENT
 IS NOT ALLOWED UNDER FBC P 912.1
  
 4 )YOU HAVE NOT PUT A VALUE ON THIS REVISION AND HAVE
 SIGNIFICANT CHANGES. PROVIDE A SIGNED BONA FIDE
 CONTRACT SHOW FULL VALUE OF ENTIRE JOB. WPB AMEND TO
 THE FBC 109.3
  
 5) PROVIDE WASHER AND DRYER INSTALLATION MANUALS/
 SPECIFICATION SHEETS. FBC 107.2.1
  
 6) SHOW DISTANCE THAT DRAIN IS TO BE MOVE (OFFSET) FROM
 EXISTING P-TRAP TO STAY IN COMPLIANCE WITH FBC P 1002.1
  
 7) PROVIDE A DETAIL CABINET DRAWING SHOW FINISHED
 ELEVATION AT MAX 34" FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved