Plan Review Details - Permit 18050854
Plan Review Stops For Permit 18050854
Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-06-25 Cont ID  
Sent By spalmer Date 2018-06-25 Time 11:56 Rev Time 0.00
Received By spalmer Date 2018-06-25 Time 11:56 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 04:34 Rev Time 0.00
Received By tklarge Date 2018-06-02 Time 04:34 Sent To I
Notes
2018-06-02 04:34:161) ) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 2) THE GAS PLAN SHOWS A LESS THAN 2 PSI SYSTEM SO WHY
 IS THERE A REGULATOR AT THE GENERATOR? CLARIFY.
 3) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE GAS METER.
 4) SUBMIT THE MANUF. SPECIFICATIONS FOR THE GAS FLEX
 CONNECTOR FOR THE GENERATOR.THE FLEX CONNECTOR SHALL BE
 APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 5) THE TRACER WIRE OR TAPE SHALL NOT BE IN DIRECT
 CONTACT WITH
 THE POLYAMIDE OR POLYETHYLENE PIPE PER NFPA-15
 SEC.6.9.4.6.
 6) SEDIMENT TRAP IS REQUIRED PER 2017 FBC - FUEL GAS
 SEC. 408.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 04:33 Rev Time 0.00
Received By tklarge Date 2018-06-02 Time 04:33 Sent To  
Notes
***NONE***