Plan Review Details - Permit 18050851
Plan Review Stops For Permit 18050851
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:43 Rev Time 0.00
Received By shill Date 2018-06-16 Time 15:43 Sent To  
Notes
2018-06-16 16:00:05****CORRECTIONS****
 REVISED 6/20/18
 REVISED 6/28/18
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. PROVIDE INFORMATION ABOUT THE PREVIOUS PERMITTED
 OCCUPANCY; IS THIS A CHANGE OF OCCUPANCY? IF YES,
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER 10.
  
 3. THIS PROPERTY HAS A NUMBER OF EXPIRED PERMITS;
 PLEASE RESOLVE AT THIS TIME. AS DISCUSSED, AT LEAST
 THREE OF THE PERMITS WERE FOR THE SUBJECT UNIT. THERE
 IS AN EXPIRED ELECTRICAL PERMIT WHICH FAILED
 INSPECTION.
  
 4. PLAN SHOW OCCUPANCY AS "WAREHOUSE" WITH 500 SF PER
 PERSON, BUT THE PLAN ALSO STATES THAT THIS IS A
 "SHOWROOM". A SHOWROOM IS MERCANTILE FBC B 309.1, 60 SF
 PER PERSON, FBC B 1004.
  
 5. PROVIDE A DETAIL FOR THE BREAK ROOM SINK, FBC A
 212.3, 606.
  
 6. PLAN STATES THAT ADA BATHROOM IS "EXISTING", BUT THE
 DETAILS ARE STANDARD DETAILS. PROVIDE DETAILS OF THE
 EXISTING TO SHOW COMPLIANCE, FBC 107.
  
 7. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC 107.
  
 8. DOES THIS SPACE HAVE AN ACCESSIBLE ROUTE, FROM
 ACCESSIBLE PARKING TO THE ENTRANCE? FBC A 202.4. REVISE
 PLAN TO SHOW COMPLIANCE.
  
 9. REVISED 6/28/18 PURSUANT TO MEETING WITH DOUG
 HARVEY, ABO, RICHARD COHEN ATTY, & OWNER
  
 THIS BUILDING HAS A NUMBER OF EXPIRED PERMITS. AS
 DISCUSSED, INCORPORATE THE PERMITS WHICH AFFECT THIS
 UNIT INTO THIS PERMIT:
  
 05011183, CUT WALL AND INSTALL GARAGE DOOR 9'X8'
 06082252, TAKE DOWN WALL IN BAY 2-3 AND BUILD FIRE
 RATED WALL
 06082253, ELECTRICAL FOR 06082252
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO; RESOLUTION OF
 EXPIRED ELECTRICAL PERMIT 08070213 REQUIRED PRIOR TO
 FINAL INSPECTION.
  
 10. (NEW 6/28) THE PLAN INDICATES "EXISTING FIRE
 WALLS". PLEASE SEE EXPIRED PERMITS 06082252, 10070718.
 AS FINAL INSPECTIONS WERE NOT OBTAINED, THE WALLS ARE
 NOT CONSIDERED "EXISTING". THIS WORK SHOULD BE
 INCORPORATED INTO THIS PERMIT.
  
 11. (NEW 6/28) PROVIDE INFORMATION TO SHOW COMPLIANCE
 WITH FBC B TABLE 506.2. IS THE BUILDING SPRINKLERED?
 WHAT IS THE BUILDING TYPE?
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By jpearson Date 2018-06-15 Time 15:16 Rev Time 0.00
Received By jpearson Date 2018-06-15 Time 13:20 Sent To  
Notes
2018-06-15 15:16:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MANY AREAS OF PLAN ARE DIFFICULT TO READ. PROVIDE
 PLAN THAT IS LEGIBLE PER WPB FBC 107.2.1.3.
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 5. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. THE
 GFCI DEVICE MUST BE READILY ACCESSIBLE. NEC 422.5,
 422.52
 6. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-07-18 Cont ID  
Sent By pleduc Date 2018-07-18 Time   Rev Time 0.00
Received By pleduc Date 2018-07-18 Time 11:10 Sent To  
Notes
2018-07-18 11:45:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PREVIOUS COMMENTS OF FIRE PREVENTION WERE NOT
 SPECIFICALLY ADDRESSED AND WILL BE RE-ENTERED BELOW
  
 *******************************************************
 *******************************************************
 ****************
  
  
 1) THE OCCUPANCY IS INDICATED AS WAREHOUSE; HOWEVER,
 MINI SHOWROOMS ARE INDICATED WITH AN OPEN FLOOR SPACE
 INDICATED AS SHOWROOM. THIS CHANGE OF OCCUPANCY APPEARS
 TO BE MERCANTILE IN THE LIFE SAFETY CODE.
  
 PER NFPA 101, CHAPTER 6, CLASSIFICATION OF OCCUPANCY.
  
 6.1.10.1* DEFINITION - MERCANTILE OCCUPANCY. AN
 OCCUPANCY USED
 FOR THE DISPLAY AND SALE OF MERCHANDISE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE
 CODE REFERENCES.
  
  
  
 2ND REVIEW COMMENT:
  
 1A) SHEET T 1 APPEARS TO HAVE BEEN CHANGED TO GROUP.
 THERE IS NO OCCUPANCY CLASSIFICATION IN THE FFPC
 INDICATED AS GROUP.
  
 IT CAN BE MIXED; SEPARATED OR NON SEPARATED OR MULTIPLE
 OCCUPANCY. THE LIFE SAFETY REQUIREMENTS WOULD NEED TO
 BE COMPARED AND APPLY THE MOST STRICT.
  
  
  
  
  
 2) THERE IS A HAND WRITTEN INDICATION THAT THE
 OCCUPANCY IS "BETWEEN FIRE WALLS". THERE ARE NO
 INDICATIONS ON THE PLAN SET DRAWINGS OR LISTING
 CALL-OUTS THAT THE EXISTING WALLS ARE FIRE RATED.
  
 WHAT IS THE SEPARATION CLASSIFICATION OF THE
 SURROUNDING OCCUPANCIES? A 2 HOUR RATING IS REQUIRED.
  
 PER NFPA 101, CHAPTER 6
  
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS
 3-HOUR FIRE
 RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR
 1-HOUR FIRE
 RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF
 CHAPTER 8.
 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED
 IN TABLE
 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE
 PERMITTED TO BE
 REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED
 TO LESS THAN 1
 HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 9.7.1.1(1) AND
 SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED
 BY THE
 DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES.
 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL,
 HORIZONTAL, OR
 BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED
 TO PROVIDE
 COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE
 BUILDING.
 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING
 SHALL COMPLY
 WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN.
  
 PLEASE PROVIDE SPECIFIC DETAILS OF THE SEPARATIONS AND
 FIRE RATING OR JUSTIFY WITH SPECIFIC FIRE CODE
 REFERENCES.
  
  
  
  
 2A) SHEET 2 A - THERE IS A DOOR INDICATED WITHIN THE
 INDICATED FIRE WALL; HOWEVER, THE DOOR SCHEDULE DOES
 NOT INDICATE ANY FIRE RATING FOR THESE DOORS
  
 PLEASE CORRECT OR JUSTIFY.
  
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-05-25 Cont ID  
Sent By pleduc Date 2018-05-25 Time   Rev Time 0.00
Received By pleduc Date 2018-05-25 Time 12:11 Sent To  
Notes
2018-05-25 14:25:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE OCCUPANCY IS INDICATED AS WAREHOUSE; HOWEVER,
 MINI SHOWROOMS ARE INDICATED WITH AN OPEN FLOOR SPACE
 INDICATED AS SHOWROOM. THIS CHANGE OF OCCUPANCY APPEARS
 TO BE MERCANTILE IN THE LIFE SAFETY CODE.
  
 PER NFPA 101, CHAPTER 6, CLASSIFICATION OF OCCUPANCY.
  
 6.1.10.1* DEFINITION ? MERCANTILE OCCUPANCY. AN
 OCCUPANCY USED
 FOR THE DISPLAY AND SALE OF MERCHANDISE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE
 CODE REFERENCES.
  
  
  
 2) THERE IS A HAND WRITTEN INDICATION THAT THE
 OCCUPANCY IS "BETWEEN FIRE WALLS". THERE ARE NO
 INDICATIONS ON THE PLAN SET DRAWINGS OR LISTING
 CALL-OUTS THAT THE EXISTING WALLS ARE FIRE RATED.
  
 WHAT IS THE SEPARATION CLASSIFICATION OF THE
 SURROUNDING OCCUPANCIES? A 2 HOUR RATING IS REQUIRED.
  
 PER NFPA 101, CHAPTER 6
  
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS
 3-HOUR FIRE
 RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR
 1-HOUR FIRE
 RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF
 CHAPTER 8.
 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED
 IN TABLE
 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE
 PERMITTED TO BE
 REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED
 TO LESS THAN 1
 HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 9.7.1.1(1) AND
 SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED
 BY THE
 DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES.
 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL,
 HORIZONTAL, OR
 BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED
 TO PROVIDE
 COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE
 BUILDING.
 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING
 SHALL COMPLY
 WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN.
  
 PLEASE PROVIDE SPECIFIC DETAILS OF THE SEPARATIONS AND
 FIRE RATING OR JUSTIFY WITH SPECIFIC FIRE CODE
 REFERENCES.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-25 Cont ID  
Sent By skennedy Date 2018-07-25 Time 15:27 Rev Time 0.00
Received By skennedy Date 2018-07-16 Time 14:11 Sent To  
Notes
2018-07-17 14:12:04B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-21 Cont ID  
Sent By mcruz Date 2018-06-21 Time 16:00 Rev Time 0.00
Received By mcruz Date 2018-06-21 Time 16:00 Sent To PC
Notes
2018-05-24 14:08:32B21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:48 Rev Time 0.00
Received By shill Date 2018-06-16 Time 15:48 Sent To  
Notes
2018-06-16 15:48:20SEE BUILDING REVIEW
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-06-18 Cont ID  
Sent By ccole Date 2018-06-18 Time 17:06 Rev Time 0.00
Received By ccole Date 2018-06-18 Time 16:18 Sent To  
Notes
2018-06-18 17:17:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050851
 6/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX= FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVBIDE MECHANICAL PLANS SHOWING ALL
 REQUIRED ALTERATIONS TO THE EXISTING SYSTEMS TO
 ACCOMODATE THE NEW FLOOR PLAN LAYOUT AND THE CHANGE OF
 OCCUPANCY. PLEASE INCLUDE VENTILATUION CALCULATIONS FOR
 ALL ROOMS AND SPACES IN COMPLIANCE WITH TABLE 403.3.1
 FBC M.
  
 2) AS STATED IN COMMENT #1 ABOVE, THE PROPOSED PROJECT
 APPEARS TO BE A CHANGE OF OCCUPANCY AS DEFINED IN
 SECTION 202 FBC EX. PLEASE SEE CHAPTER 10 FOR ALL
 REQUIRED COMPLIANCES, AND INDICATE THE CLASSIFICATION
 OF WORK ON COVER SHEET T-1 PER SECTION 506 FBC EX.
  
 3) REFER TO SECTION C505.1 FBC EC SND SUBMIT AN ENERGY
 COMPLIANCE REPORT FOR THWE PROPOSED CHANGE OF
 OCCUPANCY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 15:47 Rev Time 0.00
Received By shill Date 2018-06-16 Time 15:47 Sent To  
Notes
2018-06-16 15:48:02NOT SUBSTANTIAL IMPROVEMENT
 5 YEAR CUMULATIVE IMPROVEMENTS = $47,394
 PAPA 2017 VALUE FOR STRUCTURE $770,273

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-20 Cont ID  
Sent By gjohnson Date 2018-06-20 Time 11:49 Rev Time 0.00
Received By gjohnson Date 2018-06-19 Time 15:18 Sent To  
Notes
2018-06-20 11:49:111ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY AND SHALL
 STATE THAT ON THE PLAN PER FBC EX 506 AND SHALL COMPLY
 WITH FBCEX CH 10
  
 2. PLEASE SHOW THE REQUIRED FLOOR SPACE IN THE ADA
 BATHROOM AND LABEL CLEAR FLOOR SPACE WITH DIMENSIONS
 PER FBC ACC 304.3.1, 604.3.1 , 606.2
  
 3. PLEASE LABEL THE DRINKING FOUNTAIN AND SERVICE SINK
 ON THE FLOOR PLAN. PER WPB AMEND TO FBC 107.2.1
  
 4. THE DRINKING FOUNTAIN SHALL HAVE A SPOUT FOR A
 STANDING PERSON AND A LOWER ONE FOR SOMONE IN A WHEEL
 CHAIR A HILO DRINKING FOUNTAIN COMPLIES PER FBC ACC
 211.2
  
 5. SHT. A-2 THE THE DETAIL FOR THE CLEAR FLOOR SPACE
 AROUND THE TOILET IS NON COMPLIANT PLEASE SHOW
 COMPLIANT DIMENSIONS PER FBC ACC 604.3.1
  
 6. THE GRAB BARS SHALL BE MEASURE FROM THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR PER FBC ACC 609.4
  
 7. PROVIDE A WATER ISOMETRIC. WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 8, THE BREAK ROOM SINK SHALL BE ACCESSIBLE AND COMPLY
 WITH FBC ACC 212.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2018-06-21 Cont ID  
Sent By MC Date 2018-06-21 Time 15:58 Rev Time 0.00
Received By mcruz Date 2018-06-21 Time 15:58 Sent To PC
Notes
2018-06-21 16:00:20ZONING REVIEW N/A, PERMIT VALUATION DOES NOT EXCEED 50%
 VALUE OF PROPERTY.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  