Plan Review Details - Permit 18050811
Plan Review Stops For Permit 18050811
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-25 Cont ID  
Sent By rmcdouga Date 2018-05-25 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2018-05-25 Time 10:20 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-29 Cont ID  
Sent By jleahy Date 2018-05-29 Time 10:08 Rev Time 0.00
Received By jleahy Date 2018-05-29 Time 10:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-07-13 Cont ID  
Sent By tklarge Date 2018-07-13 Time 13:49 Rev Time 0.00
Received By tklarge Date 2018-07-13 Time 13:49 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-07-11 Cont ID  
Sent By tklarge Date 2018-07-11 Time 06:42 Rev Time 0.00
Received By tklarge Date 2018-07-11 Time 06:20 Sent To I
Notes
2018-07-11 06:37:211) THERE ARE TWO DIFFERENT GAS DRAWINGS SUBMITTED IN
 THIS PACKAGE. REMOVE ALL OLD DRAWINGS/DOCUMENTS AND
 COMPILE THE DOCUMENTS INTO TWO COMPLETE SETS OF PLANS
 FOR REVIEW. WPB AMEND. TO FBC SEC.107.1. 2ND REQUEST.
 2) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED
 A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER
 BUILDING OPENINGS. THE SURVEY SHOWS 5 FEET. 2017
 FBC-MECH. SEC.501.3.1 & MANUF. INSTALLATION MANUAL.3RD
 REQUEST.
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE
 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. 2ND
 REQUEST.
 4) INDICATE THE ORIFICE SIZE ON THE REGULATOR SPECS SO
 THE ALLOWABLE BTU LOAD OF THE REGULATOR CAN BE CHECKED
 AGAINST THE BTU LOAD OF THE APPLIANCE/EQUIPMENT
 CONNECTED.2ND REQUEST.
 5) THE NEW GAS DRAWING SHOWS AN EXISTING GAS METER AND
 THE SURVEY SHOWS A NEW GAS METER. WHICH IS IT? EXISTING
 CITY RECORDS DO NOT SHOW ANY PREVIOUS GAS SYSTEM AT
 THIS ADDRESS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-19 Cont ID  
Sent By tklarge Date 2018-06-19 Time 06:33 Rev Time 0.00
Received By tklarge Date 2018-06-19 Time 06:16 Sent To I
Notes
2018-06-19 06:33:171) THERE ARE TWO DIFFERENT GAS DRAWINGS SUBMITTED IN
 THIS PACKAGE. REMOVE ALL OLD DRAWINGS/DOCUMENTS AND
 COMPILE THE DOCUMENTS INTO TWO COMPLETE SETS OF PLANS
 FOR REVIEW. WPB AMEND. TO FBC SEC.107.1.
 2) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED
 A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER
 BUILDING OPENINGS. THE SURVEY SHOWS 5 FEET. 2017
 FBC-MECH. SEC.501.3.1 & MANUF. INSTALLATION MANUAL.
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE
 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
 4) INDICATE THE ORIFICE SIZE ON THE REGULATOR SPECS SO
 THE ALLOWABLE BTU LOAD OF THE REGULATOR CAN BE CHECKED
 AGAINST THE BTU LOAD OF THE APPLIANCE/EQUIPMENT
 CONNECTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By tklarge Date 2018-05-31 Time 06:26 Rev Time 0.00
Received By tklarge Date 2018-05-31 Time 05:26 Sent To I
Notes
2018-05-31 06:26:451) SUBMIT 2 COPIES OF SIZING TABLES FROM THE 2017
 FBC-FUEL GAS CODE FOR THE GAS SYSTEM THAT ARE LEGIBLE.
 DO NOT TRY TO ENLARGE THIS TABLES AS THEY BECOME
 BLURRED. THESE COPIES WERE NOT ACCEPTABLE IN THE PAST
 AND ARE NOT ACCEPTABLE NOW.WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE 2017
 FBC-FUEL GAS CODE BEING USED FOR THE LOW PRESSURE
 SYSTEM.2017 FBC-FUEL GAS SEC.402.1,402.3.
 3) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED
 A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER
 BUILDING OPENINGS. 2017 FBC-MECH. SEC.501.3.1.
 4) THE GAS DRAWINGS WERE PREPARED BY DIG-IT UNLIMITED.
 IF YOU ARE GOING TO USE THESE PLANS REMOVE ALL NOTES
 FROM THE GAS PLAN THAT REFERENCE DIG-IT UNLIMITED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-11 Cont ID  
Sent By tklarge Date 2018-07-11 Time 06:42 Rev Time 0.00
Received By tklarge Date 2018-07-06 Time 13:47 Sent To  
Notes
2018-07-09 13:47:24RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-19 Cont ID  
Sent By tklarge Date 2018-06-19 Time 06:34 Rev Time 0.00
Received By tklarge Date 2018-06-12 Time 13:33 Sent To  
Notes
2018-06-13 13:33:26RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-31 Cont ID  
Sent By tklarge Date 2018-05-31 Time 06:27 Rev Time 0.00
Received By tklarge Date 2018-05-17 Time 11:04 Sent To  
Notes
2018-05-18 11:04:25ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By mcruz Date 2018-05-23 Time   Rev Time  
Received By   Date 2018-05-23 Time   Sent To PC
Notes
2018-05-23 09:46:16NOTE - SHALL BE AT LEAST 6 FEET FROM REAR PROPERTY
 LINE.
  
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]