Plan Review Stops For Permit 18050811 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2018-05-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-25 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-25 |
Time |
10:20 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-05-29 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-05-29 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-05-29 |
Time |
10:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2018-07-13 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-13 |
Time |
13:49 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-13 |
Time |
13:49 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2018-07-11 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-11 |
Time |
06:42 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-11 |
Time |
06:20 |
Sent To |
I |
|
Notes |
2018-07-11 06:37:21 | 1) THERE ARE TWO DIFFERENT GAS DRAWINGS SUBMITTED IN | | THIS PACKAGE. REMOVE ALL OLD DRAWINGS/DOCUMENTS AND | | COMPILE THE DOCUMENTS INTO TWO COMPLETE SETS OF PLANS | | FOR REVIEW. WPB AMEND. TO FBC SEC.107.1. 2ND REQUEST. | | 2) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED | | A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER | | BUILDING OPENINGS. THE SURVEY SHOWS 5 FEET. 2017 | | FBC-MECH. SEC.501.3.1 & MANUF. INSTALLATION MANUAL.3RD | | REQUEST. | | 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A | | NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING | | TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE | | USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE | | 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES | | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. 2ND | | REQUEST. | | 4) INDICATE THE ORIFICE SIZE ON THE REGULATOR SPECS SO | | THE ALLOWABLE BTU LOAD OF THE REGULATOR CAN BE CHECKED | | AGAINST THE BTU LOAD OF THE APPLIANCE/EQUIPMENT | | CONNECTED.2ND REQUEST. | | 5) THE NEW GAS DRAWING SHOWS AN EXISTING GAS METER AND | | THE SURVEY SHOWS A NEW GAS METER. WHICH IS IT? EXISTING | | CITY RECORDS DO NOT SHOW ANY PREVIOUS GAS SYSTEM AT | | THIS ADDRESS. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-06-19 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-19 |
Time |
06:33 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-19 |
Time |
06:16 |
Sent To |
I |
|
Notes |
2018-06-19 06:33:17 | 1) THERE ARE TWO DIFFERENT GAS DRAWINGS SUBMITTED IN | | THIS PACKAGE. REMOVE ALL OLD DRAWINGS/DOCUMENTS AND | | COMPILE THE DOCUMENTS INTO TWO COMPLETE SETS OF PLANS | | FOR REVIEW. WPB AMEND. TO FBC SEC.107.1. | | 2) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED | | A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER | | BUILDING OPENINGS. THE SURVEY SHOWS 5 FEET. 2017 | | FBC-MECH. SEC.501.3.1 & MANUF. INSTALLATION MANUAL. | | 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A | | NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING | | TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE | | USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE | | 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES | | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. | | 4) INDICATE THE ORIFICE SIZE ON THE REGULATOR SPECS SO | | THE ALLOWABLE BTU LOAD OF THE REGULATOR CAN BE CHECKED | | AGAINST THE BTU LOAD OF THE APPLIANCE/EQUIPMENT | | CONNECTED. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-05-31 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-05-31 |
Time |
06:26 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-05-31 |
Time |
05:26 |
Sent To |
I |
|
Notes |
2018-05-31 06:26:45 | 1) SUBMIT 2 COPIES OF SIZING TABLES FROM THE 2017 | | FBC-FUEL GAS CODE FOR THE GAS SYSTEM THAT ARE LEGIBLE. | | DO NOT TRY TO ENLARGE THIS TABLES AS THEY BECOME | | BLURRED. THESE COPIES WERE NOT ACCEPTABLE IN THE PAST | | AND ARE NOT ACCEPTABLE NOW.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 2) SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE 2017 | | FBC-FUEL GAS CODE BEING USED FOR THE LOW PRESSURE | | SYSTEM.2017 FBC-FUEL GAS SEC.402.1,402.3. | | 3) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED | | A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER | | BUILDING OPENINGS. 2017 FBC-MECH. SEC.501.3.1. | | 4) THE GAS DRAWINGS WERE PREPARED BY DIG-IT UNLIMITED. | | IF YOU ARE GOING TO USE THESE PLANS REMOVE ALL NOTES | | FROM THE GAS PLAN THAT REFERENCE DIG-IT UNLIMITED. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-07-11 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-11 |
Time |
06:42 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-06 |
Time |
13:47 |
Sent To |
|
|
Notes |
2018-07-09 13:47:24 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-19 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-19 |
Time |
06:34 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-12 |
Time |
13:33 |
Sent To |
|
|
Notes |
2018-06-13 13:33:26 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-05-31 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-05-31 |
Time |
06:27 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-05-17 |
Time |
11:04 |
Sent To |
|
|
Notes |
2018-05-18 11:04:25 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-05-23 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-05-23 |
Time |
|
Sent To |
PC |
|
Notes |
2018-05-23 09:46:16 | NOTE - SHALL BE AT LEAST 6 FEET FROM REAR PROPERTY | | LINE. | | | | M. CRUZ | | ASSOCIATE PLANNER | | 561-822-1442 | | [email protected] |
|
|