2018-05-15 16:33:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE DOES NOT APPEAR TO BE ANY NOTIFICATION DEVICES |
| IN THE TENANT SPACES. |
| |
| PER NFPA 101, CHAPTER 31, EXISTING APARTMENT BUILDINGS. |
| |
| |
| 31.3.4.3 NOTIFICATION. |
| 31.3.4.3.1 OCCUPANT NOTIFICATION SHALL BE PROVIDED |
| AUTOMATICALLY IN |
| ACCORDANCE WITH SECTION 9.6, AND ALL OF THE FOLLOWING |
| SHALL ALSO APPLY: |
| (1) VISIBLE SIGNALS SHALL BE INSTALLED IN UNITS |
| DESIGNED FOR THE HEARING |
| IMPAIRED. |
| (2) POSITIVE ALARM SEQUENCE IN ACCORDANCE WITH 9.6.3.4 |
| SHALL BE |
| PERMITTED. |
| (3) EXISTING APPROVED PRESIGNAL SYSTEMS SHALL BE |
| PERMITTED IN |
| ACCORDANCE WITH 9.6.3.3. |
| |
| |
| 9.6.3 OCCUPANT NOTIFICATION. |
| 9.6.3.1 OCCUPANT NOTIFICATION SHALL BE PROVIDED TO |
| ALERT OCCUPANTS |
| OF A FIRE OR OTHER EMERGENCY WHERE REQUIRED BY OTHER |
| SECTIONS OF |
| THIS CODE. |
| 9.6.3.2 OCCUPANT NOTIFICATION SHALL BE IN ACCORDANCE |
| WITH 9.6.3.3 |
| THROUGH 9.6.3.10.2, UNLESS OTHERWISE PROVIDED IN |
| 9.6.3.2.1 THROUGH |
| 9.6.3.2.4. |
| |
| 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH |
| 9.6.3.5.8, |
| NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE |
| AUDIBLE, AND |
| VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL |
| FIRE ALARM |
| AND SIGNALING CODE. AND ICC/ANSI A117.1, AMERICAN |
| NATIONAL |
| STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS AND |
| FACILITIES, OR |
| OTHER MEANS OF NOTIFICATION ACCEPTABLE TO THE AUTHORITY |
| HAVING |
| JURISDICTION SHALL BE PROVIDED. |
| |
| |
| 9.6.3.6 THE GENERAL EVACUATION ALARM SIGNAL SHALL |
| OPERATE IN |
| ACCORDANCE WITH ONE OF THE METHODS PRESCRIBED BY |
| 9.6.3.6.1 |
| THROUGH 9.6.3.6.3. |
| 9.6.3.6.1 THE GENERAL EVACUATION ALARM SIGNAL SHALL |
| OPERATE |
| THROUGHOUT THE ENTIRE BUILDING OTHER THAN THE LOCATIONS |
| DESCRIBED |
| IN 9.6.3.6.4 AND 9.6.3.6.5. |
| |
| PER NFPA 72 |
| |
| 18.4.5 SLEEPING AREA REQUIREMENTS. |
| 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO |
| PROVIDE |
| SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND |
| LEVEL OF AT |
| LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 |
| DB |
| ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT |
| LEAST |
| 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, |
| WHICHEVER IS |
| GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA |
| REQUIRED TO BE |
| SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). |
| 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR |
| RETRACTABLE |
| PARTITION, IS LOCATED BETWEEN THE NOTIFICATION |
| APPLIANCE AND |
| THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED |
| WITH THE |
| BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW. |
| |
| 18.4.5.3* EFFECTIVE JANUARY 1, 2014, AUDIBLE APPLIANCES |
| PROVIDED |
| FOR THE SLEEPING AREAS TO AWAKEN OCCUPANTS SHALL |
| PRODUCE A LOW |
| FREQUENCY ALARM SIGNAL THAT COMPLIES WITH THE |
| FOLLOWING: |
| (1) THE ALARM SIGNAL SHALL BE A SQUARE WAVE OR PROVIDE |
| EQUIVALENT |
| AWAKENING ABILITY. |
| (2) THE WAVE SHALL HAVE A FUNDAMENTAL FREQUENCY OF 520 |
| HZ |
| ? 10 PERCENT. |
| |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC CODE |
| JUSTIFICATION FOR NOT PROVIDING VISUAL AND AUDIBLE |
| NOTIFICATION IN EACH TENANT SPACE. |
| |
| |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |