Plan Review Details - Permit 18050401
Plan Review Stops For Permit 18050401
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-30 Cont ID  
Sent By fgiaquin Date 2018-08-30 Time 08:42 Rev Time 0.00
Received By fgiaquin Date 2018-08-30 Time 06:59 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By fgiaquni Date 2018-05-14 Time 05:52 Rev Time 0.00
Received By fgiaquin Date 2018-05-11 Time 06:35 Sent To I
Notes
2018-05-14 05:52:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE RISER DIAGRAM OF EXISTING SERVICE.
 NEC 215.5; WPB FBC 107.2.1
  
 2. (4), 750MCM IN A 5'' CONDUIT CAN'T SUPPORT AN 800AMP
 SERVICE AS SHOWN IN EXISTING RISER DIAGRAM. NEC 230.31,
 NEC 310.15B16
  
 3. MARK OCP FOR EXISTING PANEL "A" IN MDP ON EXISTING
 RISER DIAGRAM.
  
 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
  
 5. TRIANGLE NOTE #2 IN ELECTRICAL LEGEND STATES
 (ELECTRICAL PANEL), THE NOTE IS ON THE PLAN SEVERAL
 TIMES IN MULTIPLE LOCATIONS. PLEASE CORRECT.
  
 6. VALUE OF WORK TOO LOW. PROVIDE COPY OF SIGNED
 CONTRACT (BY OWNER AND ELECTICAL COMPANY) WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR.
 FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-30 Cont ID  
Sent By fgiaquin Date 2018-08-30 Time 08:42 Rev Time 0.00
Received By fgiaquin Date 2018-08-27 Time 12:43 Sent To  
Notes
2018-08-29 12:43:22RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By cpuell Date 2018-05-14 Time 10:42 Rev Time 0.00
Received By cpuell Date 2018-05-09 Time 14:36 Sent To  
Notes
2018-05-09 14:36:50REVISION ROUTED TO FG