2018-05-09 12:28:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. SEE UNDERLAYMENT PRODUCT APPROVAL, 5.6.4.2, ENHANCED | | FASTENING CALCULATIONS PREPARED BY A DESIGN | | PROFESSIONAL IS REQUIRED. -94.4 PSF REQUIRED (HIP & | | RIDGE), ASSEMBLY HAS A LIMITATION OF -45PSF, FBC R 301. | | |
|
|