Plan Review Details - Permit 18050186
Plan Review Stops For Permit 18050186
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-17 Cont ID  
Sent By cthroop Date 2018-07-17 Time 14:43 Rev Time 0.00
Received By cthroop Date 2018-07-17 Time 14:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 17:26 Rev Time 0.00
Received By shill Date 2018-07-05 Time 12:44 Sent To  
Notes
2018-07-05 17:26:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC R 301
  
 1-2. OK
  
 3. PANELS: SHEET 1 SPECIFIES 12D EDGE DISTANCE OR PER
 MANUFACTURER SPEC. 3" REQUIRED FOR A 1/4" ANCHOR.
 MANUFACTURER SPEC ONLINE REQUIRES 3-3/4" WITH REDUCTION
 FACTOR FOR OTHER EDGE DISTANCES. REVISE THE
 INSTALLATION SCHEDULE TO SPEC FASTENER DIAMETER AND
 REVISE EDGE DISTANCE ACCORDINGLY. SPEC SHEET FROM
 MANUFACTURER MAY BE REQUIRED.
  
 4. WINDOWS AND SHUTTERS SPANS ARE SPECIFIED AS WIDTH X
 HEIGHT. THE SHUTTER ORIENTATION (HORIZ/VERT) FOR THE
 PANELS IS NOT CONSISTENT WITH THE SPANS AND OPENING
 SIZE. FOR INSTANCE: OPENING 1, 86.25 X 54, HORIZONTAL,
 54" SPAN. THE 54" DIMENSION IS THE WINDOW HEIGHT.
  
 COMPLIANCE NOT CLEAR. FOR INSTANCE: OPENING 7, 116.25
 WIDTH. SPAN IS 49", BUT THAT IS THE HEIGHT. IF SPAN IS
 ACTUALLY 116.25, PER SHEET2 THIS SPAN IS LIMITED TO
 -30PSF.
  
 5. IT IS NOT CLEAR WHICH INSTALLATION METHOD IS
 PROPOSED; DIRECT MOUNT AT BOTH ENDS, OR DIRECT MOUNT AT
 ONE END ONLY.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-26 Cont ID  
Sent By shill Date 2018-05-26 Time 09:19 Rev Time 0.00
Received By shill Date 2018-05-26 Time 09:19 Sent To  
Notes
2018-05-26 11:06:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FROM PREVIOUS LIST: PROVIDE A PLAN TO SHOW MEANS OF
 ESCAPE REQUIRED BY FBC R 310.4; INCLUDE ROOM
 DESIGNATION.
  
 IT IS NOT CLEAR HOW THIS WAS ADDRESSED AS NONE OF THE
 OPENINGS ARE NOTED AS "EGRESS"; PLEASE REVISE.
  
 2. FL17733 IS VERY DIFFICULT TO READ; IS IT POSSIBLE TO
 OBTAIN A LEGIBLE DOCUMENT FROM THE INTERNET? FBC 107.
  
 3. THE PANELS ARE NOTED AS HORIZONTAL INSTALLATION,
 CONCRETE. UNLESS THIS HOUSE IS FORMED AND POURED
 CONCRETE, THE WINDOW OPENINGS HAVE FILLED CELLS
 (CONCRETE BLOCK SUBSTRATE). PLEASE VERIFY AND REVISE IF
 NECESSARY.
  
 IT IS POSSIBLE THAT THE RESUBMITTAL WILL BE ACCEPTED
 VIA EMAIL; PLEASE EMAIL CORRECTED DOCUMENTS DIRECTLY TO
 ME IN THE NEXT WEEK WITH THE PERMIT NUMBER IN THE
 SUBJECT LINE AND "RESUBMITTAL". IF RESUBMITTED AFTER
 THE NEXT WEEK, PLEASE SUBMIT AT THE COUNTER.
  
 IF APPLICANT PREFERS PAPER RESUBMITTAL, THAT IS
 ACCEPTABLE.
  
 4. NOTICE - AFTER REVIEW HAS PASSED, THIS PERMIT WILL
 BE ISSUED VIA EMAIL. PLEASE NOTIFY IF CONTRACTOR
 OBJECTS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-04 Cont ID  
Sent By shill Date 2018-05-04 Time 18:14 Rev Time 0.00
Received By shill Date 2018-05-04 Time 18:14 Sent To  
Notes
2018-05-04 18:14:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 THE SPREADSHEET PROVIDED DOES NOT INCLUDE ALL
 INFORMATION SUCH AS SUBSTRATE, EDGE DISTANCE, ETC.
  
 2. PROVIDE A PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY
 FBC R 310.4; INCLUDE ROOM DESIGNATION.
  
 3. PROVIDE A PLAN TO SHOW LOCATION OF PROPOSED SHUTTERS
 TO CORRELATE WITH THE SCHEDULE , FBC 107.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-17 Cont ID  
Sent By cthroop Date 2018-07-17 Time 14:43 Rev Time 0.00
Received By cthroop Date 2018-07-09 Time 11:47 Sent To I
Notes
2018-07-11 11:48:16RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-05 Cont ID  
Sent By shill Date 2018-07-05 Time 17:26 Rev Time 0.00
Received By shill Date 2018-06-29 Time 16:15 Sent To  
Notes
2018-07-02 16:15:55RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-26 Cont ID  
Sent By shill Date 2018-05-26 Time 11:07 Rev Time 0.00
Received By shill Date 2018-05-11 Time 14:34 Sent To  
Notes
2018-05-14 14:34:58RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-04 Cont ID  
Sent By shill Date 2018-05-04 Time 18:14 Rev Time 0.00
Received By shill Date 2018-05-03 Time 10:29 Sent To B
Notes
***NONE***