Plan Review Details - Permit 18050170
Plan Review Stops For Permit 18050170
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-11 Cont ID  
Sent By shill Date 2018-05-11 Time 15:41 Rev Time 0.00
Received By shill Date 2018-05-11 Time 15:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-09 Cont ID  
Sent By shill Date 2018-05-09 Time 10:12 Rev Time 0.00
Received By shill Date 2018-05-09 Time 10:12 Sent To  
Notes
2018-05-09 10:15:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE NEW SCHEDULE IS ACCEPTABLE, BUT ONE SET OF FIRST
 SUBMITTAL WAS DISCARDED,THE OTHER MARKED VOID. THERE
 ARE NO LONGER TWO FLOOR PLANS AND TWO SETS OF
 ENGINEERING. PLEASE PROVIDE.
  
 WHEN RESUBMITTING, PLEASE PROVIDE TWO IDENTICAL PERMIT
 PACKAGES FOR PERMIT ISSUANCE.
  
 FBC 107.
  
 2. UPON REQUEST, THE REVIEW CAN BE A WALK THROUGH IF
 SCHEDULED WITHIN THE NEXT TWO WEEKS. IF YOU WOULD LIKE
 A WALK THROUGH, SEND AN EMAIL WITH "WALK THROUGH
 REQUEST" AND PERMIT NUMBER IN THE SUBJECT LINE, PROVIDE
 THE DAY AND TIME YOU WOULD LIKE TO SUBMIT, AND AN
 APPOINTMENT WILL BE MADE FOR YOU.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-03 Cont ID  
Sent By shill Date 2018-05-03 Time 18:04 Rev Time 0.00
Received By shill Date 2018-05-03 Time 18:01 Sent To  
Notes
2018-05-03 18:04:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. INSTALLATION SCHEDULE EDGE DISTANCE STATES "NA".
 THIS INFORMATION IS REQUIRED. NOTE THAT PAGE 13 HAS A
 TABLE OF FACTORS FOR REDUCED EDGE DISTANCE. PROPOSED
 SPACING MAY NOT COMPLY DEPENDING ON EDGE DISTANCE.
  
 FOR TAPCONS, EDGE DISTANCE LESS THAN 3" REQUIRES A .35
 FACTOR APPLIED TO THE SPACING WHICH IS NOT POSSIBLE FOR
 THE OPTIONS SELECTED. FBC R 301.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-09 Cont ID  
Sent By shill Date 2018-05-09 Time 10:15 Rev Time 0.00
Received By shill Date 2018-05-04 Time 13:17 Sent To  
Notes
2018-05-07 13:17:13RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-03 Cont ID  
Sent By shill Date 2018-05-03 Time 18:04 Rev Time 0.00
Received By shill Date 2018-05-03 Time 16:43 Sent To B
Notes
***NONE***