Plan Review Details - Permit 18050114
Plan Review Stops For Permit 18050114
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-03 Cont ID  
Sent By thunt Date 2018-05-03 Time 17:41 Rev Time 0.00
Received By thunt Date 2018-05-02 Time 15:34 Sent To I
Notes
2018-05-02 15:34:37ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-03 Cont ID  
Sent By thunt Date 2018-05-03 Time 17:25 Rev Time 0.00
Received By thunt Date 2018-05-03 Time 17:24 Sent To  
Notes
2018-05-03 17:40:5205/03/2016 1ST PLUMBING REVIEW**DENIED**
  
 1) CLEAN OUT REQUIRED ON MAIN HOUSE. REVISE YOUR
 ISOMETRIC TO COMPLY WITH FBC-R P3005.2.3
  
 2) A STUDOR VENT ON THE GUEST HOUSE IS NOT PERMITTED.
 THE VENT SYSTEM SERVICING EACH BUILDING DRAIN SHALL NOT
 HAVE LESS THEN 1 VENT THAT EXTENDS TO THE OUTDOORS.
 FBC-R P 3102.1
  
 3) SHOW FIXTURE LOAD (DFU'S)ON EACH BRANCH LINE SIZING
 WITH TABLE FBC-R P3004.1
  
 4) SHOW FIXTURE LOAD (DFU'S) ON SEWER LINE SIZING USING
 TABLE FBC-R P 3005.4.2
  
 5) TESTING OF ALL NEW WORK WILL COMPLY FULLY WITH FBC-R
 P SECTION 2503 REQUIRING A HEAD TEST ALEAST UP TO THE
 POINT OF EXISTING FITTING'S. THIS IS NOT A MUILT
 DWELLING APARTMENT BUILDING BUT A SINGLE FAMILY HOME
 PERMITTED UNDER #15081144 C.O WAS GIVEN ON 04/20/2017
 AS A SINGLE FAMILY OCCUPANCY. THE INSPECTOR WILL WORK
 AROUND THE FAMILY'S SCHEDULE TO ACCOMMODATETHE TIME YOU
 WILL NEED TO TEST.
  
 6) PLANS DRAWN IN PENCIL ARE NOT PERMITTED AND DO NOT
 MEET MIN PLAN REVIEW CRITERIA. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  