Plan Review Details - Permit 18050041
Plan Review Stops For Permit 18050041
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2018-08-21 Cont ID  
Sent By cthroop Date 2018-08-21 Time 11:49 Rev Time 0.00
Received By cthroop Date 2018-08-21 Time 11:42 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2018-08-08 Cont ID  
Sent By cthroop Date 2018-08-08 Time 14:44 Rev Time 0.00
Received By cthroop Date 2018-08-08 Time 14:43 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-27 Cont ID  
Sent By cthroop Date 2018-07-27 Time 12:55 Rev Time 0.00
Received By cthroop Date 2018-07-27 Time 12:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-27 Cont ID  
Sent By cthroop Date 2018-06-27 Time 12:37 Rev Time 0.00
Received By cthroop Date 2018-06-27 Time 12:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-05 Cont ID  
Sent By cthroop Date 2018-06-05 Time 14:50 Rev Time 0.00
Received By cthroop Date 2018-06-05 Time 12:58 Sent To  
Notes
2018-06-05 14:53:36BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SUBMITTAL NOW HAS TWO PLANS FROM DIFFERENT SIGN
 COMPANIES. PLEASE REMOVE DESIGN THAT DOES NOT COMPLY
 WITH THIS SUBMITTAL.
 2. ADDRESS BLDG. REVIEW COMMENTS FROM 1ST REVIEW AND
 RE-SUBMIT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By ajones Date 2018-05-14 Time 16:15 Rev Time 0.00
Received By cthroop Date 2018-05-14 Time 10:56 Sent To  
Notes
2018-05-14 11:04:14BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE WIND DESIGN LOADS FOR PROPOSED SIGN.
 FBC 107.3.5.1.1(8) ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 2. PROVIDE FASTENER SCHEDULE BASED ON WIND DESIGN DATA
 AND EXISTING WALL TYPE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 3. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
  
  
  
2018-05-10 16:17:24FAILED- STAMPED APPROVED PLANS OR A LETTER FROM THE PB
 OUTLETS REQUIRED.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2018-08-21 Cont ID  
Sent By fgiaquin Date 2018-08-21 Time 06:00 Rev Time 0.00
Received By fgiaquin Date 2018-08-21 Time 05:59 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2018-08-06 Cont ID  
Sent By fgiaquin Date 2018-08-06 Time 06:34 Rev Time 0.00
Received By fgiaquin Date 2018-08-06 Time 06:29 Sent To B
Notes
2018-08-06 06:33:36ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 4X THE PLAN REVIEW FEE HAS BEEN ADDED TO THIS FOR THE
 SAME DEFECIENCIES ON PLAN REVIEW DOCUMENTS FOR 6
 REVIEWS AS PER F.S. 553.802B
  
 1. 6TH PLAN REVIEW WITH SAME DEFICIENCIES.
  
 2. HIGH VOLTAGE AND LOW VOLTAGE TOGETHER IN J-BOX.
 725.136B NEC
  
 3. DISCONNECT REQUIRED WITHIN SIGHT OF SIGN THAT
 DISCONNECTS THE BRANCH CIRCUIT/FEEDER CONDUCTORS BEFORE
 IT ENTERS THE SIGN. NEC 600.6A1
  
 4. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC
 AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE
 HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR
 LICENSE. PLEASE HAVE LICENSED ELECTRICIAN PULL
 SUB-ELECTRICAL PERMIT.
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2018-07-25 Cont ID  
Sent By fgiaquin Date 2018-07-25 Time 06:35 Rev Time 0.00
Received By fgiaquin Date 2018-07-25 Time 06:12 Sent To B
Notes
2018-07-25 06:24:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. 5TH PLAN REVIEW WITH SAME DEFICIENCIES. THERE WILL
 BE NO FURTHER PLAN REVIEWS OF THIS PERMIT (FOR
 ELECTRICAL) UNTIL I HAVE SPOKEN TO EITHER THE QUALIFIER
 FOR FERRIGN SIGNS OR THE ENGINEER OF RECORD FOR THIS
 PROJECT. PLEASE CONTACT ME DIRECTLY ON MY CELL PHONE
 561-657-1653
  
 2. HIGH VOLTAGE AND LOW VOLTAGE TOGETHER IN J-BOX.
 725.136B NEC
  
 3. DISCONNECT REQUIRED AS PER NEC 600.6A1
  
 4. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC
 AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE
 HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR
 LICENSE.
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
 5. THERE IS A NOTE ON THE PLAN THAT STATES "TIME CLOCK
 IS EXISTING" TIME CLOCK MUST STILL CONFORM TO FBC CE
 405.2.4 (ASTRONOMICAL TIME CLOCK NEEDED)
  
 6. SIGNATURE AND SEAL ON PLAN IS PHOTO COPIED. NOT
 CONSIDERED TO BE SIGNED AND SEALED.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2018-07-13 Cont ID  
Sent By fgiaquin Date 2018-07-13 Time 06:26 Rev Time 0.00
Received By fgiaquin Date 2018-07-13 Time 05:36 Sent To I
Notes
2018-07-13 06:25:55SAME VIOLATIONS AS PREVIOUS PLAN REVIEW. PLEASE SEE
 COMMENTS BELOW.
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN STILL DOES NOT MEET DISCONNECT REQUIRMENTS OF
 600.6A(1) NEC.
  
 2. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC
 AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE
 HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR
 LICENSE.
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-06-24 Cont ID  
Sent By fgiaquin Date 2018-06-24 Time 08:16 Rev Time 0.00
Received By fgiaquin Date 2018-06-24 Time 07:51 Sent To B
Notes
2018-06-24 08:16:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN STILL DOES NOT MEET DISCONNECT REQUIRMENTS OF
 600.6A(1) NEC.
  
 2. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC
 AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE
 HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR
 LICENSE.
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
 3. CONTRACT DOES NOT INCLUDE ALL FEES. PROCUREMENT FEE,
 "FINAL INSPECTION" FEE, AND ENGINEERING FEES ARE TO BE
 INCLUDED IN PRICE. VALUE HAS BEEN UPDATED TO 2650$. FBC
 109.3
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-04 Cont ID  
Sent By fgiaquin Date 2018-06-04 Time 07:23 Rev Time 0.00
Received By fgiaquin Date 2018-06-04 Time 06:56 Sent To B
Notes
2018-06-04 07:22:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INITIAL PLAN FAILED DUE TO THE NEED FOR A DISCONNECT
 AND VALUE BEING TOO LOW. NOW A NEW PLAN HAS BEEN
 SUBMITTED SEPARATELY WITH A DIFFERENT SIGN CONTRACTOR
 NAME (RAMSAY) INSTEAD OF FERRIN SIGNS AS IS ON PERMIT
 APPLICATION. CORRECT CONFLICTING ERRORS ON PLANS.
 CANNOT HAVE 2 DIFFERENT PLANS, ZONING AND BUILDING MUST
 REVIEW NEW PLAN SUBMITTED.
  
 2. NEW PLAN SUBMITTED IS NOT SIGNED. ELECTRICAL PLAN IS
 REQUIRED TO BE DESIGNED AND SIGNED/SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC
 107.1
  
 3. VALUE TOO LOW, PROVIDE COPY OF SIGNED CONTRACT WITH
 SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND
 LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-11 Cont ID  
Sent By jleahy Date 2018-05-11 Time 15:20 Rev Time 0.00
Received By jleahy Date 2018-05-11 Time 15:20 Sent To B
Notes
2018-05-11 15:22:39FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SIGN NEEDS A DISCONNECT IN ACCORDANCE WITH 600.6(A)(1)
  
 VALUE FOR SIGN TO LOW.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED
 BY INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PLEASE SUBMIT A SIGNED CONTRACT FOR TOTAL SIGN
 INSTALLATION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2018-08-21 Cont ID  
Sent By cthroop Date 2018-08-21 Time 11:49 Rev Time 0.00
Received By cthroop Date 2018-08-09 Time 11:19 Sent To  
Notes
2018-08-10 11:19:37RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-08-08 Cont ID  
Sent By cthroop Date 2018-08-08 Time 14:44 Rev Time 0.00
Received By cthroop Date 2018-07-30 Time 14:07 Sent To  
Notes
2018-07-31 14:08:05RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-07-27 Cont ID  
Sent By cthroop Date 2018-07-27 Time 12:55 Rev Time 0.00
Received By cthroop Date 2018-07-18 Time 14:46 Sent To I
Notes
2018-07-19 14:46:59RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-13 Cont ID  
Sent By fgiaquin Date 2018-07-13 Time 06:26 Rev Time 0.00
Received By fgiaquin Date 2018-07-11 Time 16:00 Sent To  
Notes
2018-07-12 16:00:23RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-27 Cont ID  
Sent By cthroop Date 2018-06-27 Time 12:37 Rev Time 0.00
Received By cthroop Date 2018-06-13 Time 14:30 Sent To I
Notes
2018-06-14 14:30:51RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-05 Cont ID  
Sent By cthroop Date 2018-06-05 Time 14:53 Rev Time 0.00
Received By cthroop Date 2018-05-22 Time 13:05 Sent To I
Notes
2018-05-23 13:05:38RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By cthroop Date 2018-05-14 Time 11:04 Rev Time 0.00
Received By cthroop Date 2018-05-01 Time 10:17 Sent To I
Notes
2018-05-02 10:17:35ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 6 Status P Date 2018-08-16 Cont ID  
Sent By mcruz Date 2018-08-16 Time 16:19 Rev Time 0.00
Received By mcruz Date 2018-08-16 Time 16:14 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2018-08-02 Cont ID  
Sent By mcruz Date 2018-08-02 Time 08:08 Rev Time 0.00
Received By mcruz Date 2018-08-01 Time 16:59 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-07-23 Time 17:14 Rev Time 0.00
Received By mcruz Date 2018-07-23 Time 17:12 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-19 Cont ID  
Sent By mcruz Date 2018-06-19 Time 09:24 Rev Time 0.00
Received By mcruz Date 2018-06-19 Time 09:23 Sent To E
Notes
2018-06-19 09:24:42WRITTEN APPROVAL FROM PALM BEACH OUTLETS WAS PROVIDED
 BY APPLICANT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By mcruz Date 2018-05-25 Time   Rev Time 0.00
Received By   Date 2018-05-25 Time   Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By ajones Date 2018-05-10 Time 16:15 Rev Time 0.00
Received By ajones Date 2018-05-10 Time 16:15 Sent To E
Notes
2018-05-10 16:18:28FAILED- STAMPED APPROVED PLANS OR A LETTER FROM THE PB
 OUTLETS REQUIRED.
  