Plan Review Details - Permit 18050026
Plan Review Stops For Permit 18050026
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-23 Cont ID  
Sent By rmcdouga Date 2018-07-23 Time 17:33 Rev Time 0.00
Received By rmcdouga Date 2018-07-23 Time 17:29 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2018-06-20 Time 08:08 Sent To I
Notes
2018-06-20 08:08:22PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR
 G007043-0 AND G007042-0 THAT'S SPECIFICATIONS WERE
 SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE
 AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT
 BE USED WITH THIS GENERATOR. FBC-R 301.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2018-05-14 Time 09:26 Sent To I
Notes
2018-05-14 09:26:30PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR
 LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S
 DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526
 LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS
 GENERATOR. FBC-R 301.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By jpearson Date 2018-07-23 Time 17:06 Rev Time 0.00
Received By jpearson Date 2018-07-23 Time 17:06 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 14:31 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 14:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-07-24 Cont ID  
Sent By lcrespo Date 2018-07-24 Time 07:11 Rev Time 0.00
Received By lcrespo Date 2018-07-24 Time 07:11 Sent To  
Notes
2018-07-24 07:13:0107/23/18 APPROVED AND SENT TO PROCESSING, LAC

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-04 Cont ID  
Sent By tklarge Date 2018-06-04 Time 03:06 Rev Time 0.00
Received By tklarge Date 2018-06-04 Time 02:07 Sent To  
Notes
2018-06-04 03:05:591) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER
 TO THE MP REGULATOR FOR THE EXISTING INTERIOR LOAD.
 2017 FBC- FUEL GAS SEC.402.4.1.
 2) SHOW THE DISTANCE FROM THE OUTLET OF THE MP
 REGULATOR TO THE MOST REMOTE GAS OUTLET ON THE INTERIOR
 SECTION OF THE SYSTEM. 2017 FBC- FUEL GAS SEC.402.4.1.
 3) THE SHUTOFF VALVE ON THE LINE INTO THE STRUCTURE
 SHALL BE LOCATED IMMEDIATELY AHEAD OF THE REGULATOR.
 2017 FBC-FUEL GAS SEC. 409.4.
 4) THERE IS A GAS GRILL SHOWN ON THE ORIGINAL SET OF
 GAS PLANS ( PERMIT #99060584) ON FILE WITH THE CITY.
 THIS GRILL IS NOT SHOWN ON THE NEWLY SUBMITTED GAS
 PLAN. CLARIFY.
 5) THE EXISTING PLANS ON FILE WITH THE CITY FOR THIS
 ADDRESS SHOW THE LONGEST RUN AS 110 FEET. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By tklarge Date 2018-05-14 Time 05:31 Rev Time 0.00
Received By tklarge Date 2018-05-14 Time 05:00 Sent To  
Notes
2018-05-14 05:16:57 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE
 REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF
 THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE
 DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON
 THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF THE MP REGULATOR FFOR THE EXISTING LOADS.. 2017 FBCR
 SEC. G2420.4.
 5) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH
 GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND
 PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR
 SEC.G2415.9, G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION SHEETS FOR THE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2017 FBCR
 SEC.G2421.1, FBC-FUEL GAS SEC. 410.1.
 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-24 Cont ID  
Sent By lcrespo Date 2018-07-24 Time 07:12 Rev Time 0.00
Received By lcrespo Date 2018-07-16 Time 13:17 Sent To  
Notes
2018-07-18 13:17:50RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2018-05-29 Time 14:03 Sent To  
Notes
2018-05-30 14:04:12RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2018-05-01 Time 09:49 Sent To  
Notes
2018-05-02 09:49:11ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 4 Status P Date 2018-07-19 Cont ID  
Sent By mcruz Date 2018-07-19 Time 14:42 Rev Time 0.00
Received By mcruz Date 2018-07-19 Time 14:36 Sent To E
Notes
2018-07-19 14:37:44ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE
 AT LEAST 4' FROM SIDE PROPERTY LINE.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 14:39 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 14:39 Sent To G
Notes
2018-05-31 14:39:42ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE
 AT LEAST 4' FROM SIDE PROPERTY LINE.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 14:34 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 14:30 Sent To G
Notes
2018-05-31 14:34:57NOTE - SHALL BE AT LEAST 4' FROM SIDE PROPERTY LINE.
  
 M. CRUZ

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By mcruz Date 2018-05-08 Time   Rev Time  
Received By mcruz Date 2018-05-08 Time   Sent To B
Notes
2018-05-08 10:50:59ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE
 AT LEAST 4' FROM SIDE PROPERTY LINE.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]