Plan Review Details - Permit 18050024
Plan Review Stops For Permit 18050024
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-24 Cont ID  
Sent By rmcdouga Date 2018-07-24 Time 08:48 Rev Time 0.00
Received By rmcdouga Date 2018-07-24 Time 08:41 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-19 Cont ID  
Sent By rmcdouga Date 2018-06-19 Time 18:20 Rev Time 0.00
Received By rmcdouga Date 2018-06-19 Time 18:20 Sent To I
Notes
2018-06-19 18:25:32PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR
 G007043-0 AND G007042-0 THAT SPECIFICATIONS WERE
 SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE
 AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT
 BE USED WITH THIS GENERATOR. FBC-R 301.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 09:20 Rev Time 0.00
Received By rmcdouga Date 2018-05-14 Time 09:20 Sent To I
Notes
2018-05-14 09:20:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR
 LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S
 DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526
 LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS
 GENERATOR. FBC-R 301.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By jpearson Date 2018-07-23 Time 16:11 Rev Time 0.00
Received By jpearson Date 2018-07-23 Time 16:11 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 14:21 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 14:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 11:27 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 11:27 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 09:41 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 08:57 Sent To  
Notes
2018-06-03 09:41:401) THE SUBMITTED GAS PLAN SHOWS AN EXISTING 3/4 INCH
 GAS LINE FROM THE METER SUPPLYING AN 1 1/4 INCH
 GALVANIZED. PROVIDE ADDITIONAL DETAILS AS TO HOW THIS
 FEAT WILL BE ACCOMPLISHED.THE EXISTING PLANS ON FILE
 SHOW AN 1 1/2 INCH GALVANIZED PIPE AT THE METER.
 2) THE SUBMITTED GAS PLAN SHOWS A 12 INCH WATER COLUMN
 NATURAL GAS METER BUT THERE IS ALSO A NOTE STATING IT
 IS A 2 PSI SYSTEM. WHICH IS IT? CLARIFY.
 3) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER
 TO THE MOST REMOTE GAS OUTLET INTO THE STRUCTURE AND
 THE LOAD ON THAT SECTION.2017 FBCR SEC. G2413.4.1. THE
 EXISTING PLANS ON FILE WITH THE CITY SHOW A DISTANCE OF
 200 FEET FROM THE METER TO THE FURTHEST OUTLET ON THE
 SYSTEM WHICH IS THE POOL HEATER. THIS DISTANCE SHALL BE
 USED FOR THE SIZING OF THIS SYSTEM.
 4) THE MINIMUM SIZE SCH. 40 METALLIC PIPE AT THE METER
 SHALL BE 2 1/2 INCHES PER THE TOTAL BTU LOAD AND THE
 DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET.2017
 FBCR SEC. G2413.4.1, TABLE G2413.4 (1).
 5) IF THIS IS A LOW PRESSURE SYSTEM, WHY ARE YOU
 SUBMITTING SPECS FOR REGULATORS? CLARIFY.
 6) IF THIS IS GOING TO BE A 2 PSI SYSTEM SUBMIT THE
 APPLICABLE SIZING TABLE FOR THE SYSTEM AND SHOW THE
 DISTANCE FROM EACH MP REGULATOR TO THE FURTHEST OUTLET
 AND BTU LOAD ON THAT SECTION. 2017 FBCR SEC. G2413.4.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By tklarge Date 2018-05-14 Time 05:55 Rev Time 0.00
Received By tklarge Date 2018-05-14 Time 05:36 Sent To  
Notes
2018-05-14 05:55:121) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 12" W.C.GAS METER . WPB AMEND. TO FBC SEC.
 107.2.1.THE SIZE OF THE PIPE SHALL COMPLY WITH 2017
 FBC-FUEL GAS FOR THE TOTAL BTU LOAD ON THE SYSTEM. 2017
 FBC-FUEL GAS SEC.401.3, 401.4.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING
 THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHOW THE DISTANCE FROM GAS METER TO THE FURTHEST
 EXISTING OUTLET ON THE SYSTEM. THE GAS PLAN NOTES
 LONGEST RUN AS 10 FT. SHOW THIS ON THE DRAWING. DOES
 THIS INCLUDE THE FURTHEST OUTLET FROM THE METER ON THE
 EXISTING SYSTEM? CLARIFY ON THE PLANS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SPECIFY ON THE GAS DRAWING HOW THE 1 INCH GALVANIZED
 PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND PIPING
 OUTDOORS SHALL COMPLY WITH 2017 FBCR SEC.G2415.9,
 G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) IF THE TOTAL LOAD IS 806,000 BTU'S AT THE OUTLET OF
 THE GAS METER, THEN THE MINIMUM PIPE SIZE FROM THE
 METER SHALL BE A MINIMUM OF 1 1/4 INCH PER TABLE 402.4
 (2) DEPENDDING ON THE DISTANCE OF THE FURTHEST GAS
 OUTLET FROM THE GAS METER.
 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
  
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 11:27 Rev Time 0.00
Received By tklarge Date 2018-07-16 Time 13:56 Sent To  
Notes
2018-07-17 13:57:02RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-19 Cont ID  
Sent By rmcdouga Date 2018-06-19 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2018-05-29 Time 13:55 Sent To  
Notes
2018-05-30 13:56:10RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 09:21 Rev Time 0.00
Received By rmcdouga Date 2018-05-01 Time 09:50 Sent To  
Notes
2018-05-02 09:50:58ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-19 Cont ID  
Sent By mcruz Date 2018-07-19 Time 14:10 Rev Time 0.00
Received By mcruz Date 2018-07-19 Time 14:10 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 16:36 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 16:31 Sent To G
Notes
2018-05-31 16:36:19ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) RESPOND TO COMMENTS IN WRITING. PREVIOUS COMMENT NOT
 ADDRESSED.
 2) INDICATE SETBACK OF GENERATOR TO SIDE PROPERTY LINE.
 MUST BE AT LEAST 3.5 FEET.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-05-08 Time   Rev Time  
Received By   Date 2018-05-08 Time   Sent To B
Notes
2018-05-08 11:45:32ZONING REVIEW FAILED, GENERATOR MUST BE A MINIMUM OF
 3.5' FROM PROPERTY LINE, BASED ON CALCULATIONS THE
 PROPOSED GENERATOR .5' OVER INTO SETBACK. PLEASE SHOW
 ON SURVEY THAT LOCATION IS FEASIBLE TO MEET ZONING
 SETBACK REQUIREMENTS. CALLED APPLICANT AND LEFT A
 MESSAGE.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]