Plan Review Stops For Permit 18050024 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-07-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-24 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-24 |
Time |
08:41 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-06-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-19 |
Time |
18:20 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-06-19 |
Time |
18:20 |
Sent To |
I |
|
Notes |
2018-06-19 18:25:32 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR | | G007043-0 AND G007042-0 THAT SPECIFICATIONS WERE | | SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE | | AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT | | BE USED WITH THIS GENERATOR. FBC-R 301.1 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-14 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-14 |
Time |
09:20 |
Sent To |
I |
|
Notes |
2018-05-14 09:20:47 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR | | LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S | | DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526 | | LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS | | GENERATOR. FBC-R 301.1 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-07-23 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-07-23 |
Time |
16:11 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-05-10 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-05-10 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-05-10 |
Time |
14:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-26 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-26 |
Time |
11:27 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-06-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-03 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-03 |
Time |
08:57 |
Sent To |
|
|
Notes |
2018-06-03 09:41:40 | 1) THE SUBMITTED GAS PLAN SHOWS AN EXISTING 3/4 INCH | | GAS LINE FROM THE METER SUPPLYING AN 1 1/4 INCH | | GALVANIZED. PROVIDE ADDITIONAL DETAILS AS TO HOW THIS | | FEAT WILL BE ACCOMPLISHED.THE EXISTING PLANS ON FILE | | SHOW AN 1 1/2 INCH GALVANIZED PIPE AT THE METER. | | 2) THE SUBMITTED GAS PLAN SHOWS A 12 INCH WATER COLUMN | | NATURAL GAS METER BUT THERE IS ALSO A NOTE STATING IT | | IS A 2 PSI SYSTEM. WHICH IS IT? CLARIFY. | | 3) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER | | TO THE MOST REMOTE GAS OUTLET INTO THE STRUCTURE AND | | THE LOAD ON THAT SECTION.2017 FBCR SEC. G2413.4.1. THE | | EXISTING PLANS ON FILE WITH THE CITY SHOW A DISTANCE OF | | 200 FEET FROM THE METER TO THE FURTHEST OUTLET ON THE | | SYSTEM WHICH IS THE POOL HEATER. THIS DISTANCE SHALL BE | | USED FOR THE SIZING OF THIS SYSTEM. | | 4) THE MINIMUM SIZE SCH. 40 METALLIC PIPE AT THE METER | | SHALL BE 2 1/2 INCHES PER THE TOTAL BTU LOAD AND THE | | DISTANCE FROM THE METER TO THE MOST REMOTE OUTLET.2017 | | FBCR SEC. G2413.4.1, TABLE G2413.4 (1). | | 5) IF THIS IS A LOW PRESSURE SYSTEM, WHY ARE YOU | | SUBMITTING SPECS FOR REGULATORS? CLARIFY. | | 6) IF THIS IS GOING TO BE A 2 PSI SYSTEM SUBMIT THE | | APPLICABLE SIZING TABLE FOR THE SYSTEM AND SHOW THE | | DISTANCE FROM EACH MP REGULATOR TO THE FURTHEST OUTLET | | AND BTU LOAD ON THAT SECTION. 2017 FBCR SEC. G2413.4.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-05-14 |
Time |
05:55 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-05-14 |
Time |
05:36 |
Sent To |
|
|
Notes |
2018-05-14 05:55:12 | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF | | THE 12" W.C.GAS METER . WPB AMEND. TO FBC SEC. | | 107.2.1.THE SIZE OF THE PIPE SHALL COMPLY WITH 2017 | | FBC-FUEL GAS FOR THE TOTAL BTU LOAD ON THE SYSTEM. 2017 | | FBC-FUEL GAS SEC.401.3, 401.4. | | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING | | THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SHOW THE DISTANCE FROM GAS METER TO THE FURTHEST | | EXISTING OUTLET ON THE SYSTEM. THE GAS PLAN NOTES | | LONGEST RUN AS 10 FT. SHOW THIS ON THE DRAWING. DOES | | THIS INCLUDE THE FURTHEST OUTLET FROM THE METER ON THE | | EXISTING SYSTEM? CLARIFY ON THE PLANS. WPB AMEND. TO | | FBC SEC. 107.2.1. | | 4) SPECIFY ON THE GAS DRAWING HOW THE 1 INCH GALVANIZED | | PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND PIPING | | OUTDOORS SHALL COMPLY WITH 2017 FBCR SEC.G2415.9, | | G2415.11. | | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | GENERATOR. 2017 FBCR SEC. G2422.1 (8). | | 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 | | FBCR SEC.G2419.4. | | 8) IF THE TOTAL LOAD IS 806,000 BTU'S AT THE OUTLET OF | | THE GAS METER, THEN THE MINIMUM PIPE SIZE FROM THE | | METER SHALL BE A MINIMUM OF 1 1/4 INCH PER TABLE 402.4 | | (2) DEPENDDING ON THE DISTANCE OF THE FURTHEST GAS | | OUTLET FROM THE GAS METER. | | 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE | | CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. | | TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1. | | | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-26 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-16 |
Time |
13:56 |
Sent To |
|
|
Notes |
2018-07-17 13:57:02 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-19 |
Time |
18:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-29 |
Time |
13:55 |
Sent To |
|
|
Notes |
2018-05-30 13:56:10 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-14 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-01 |
Time |
09:50 |
Sent To |
|
|
Notes |
2018-05-02 09:50:58 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-07-19 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-07-19 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-07-19 |
Time |
14:10 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-05-31 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-05-31 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-05-31 |
Time |
16:31 |
Sent To |
G |
|
Notes |
2018-05-31 16:36:19 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | 1) RESPOND TO COMMENTS IN WRITING. PREVIOUS COMMENT NOT | | ADDRESSED. | | 2) INDICATE SETBACK OF GENERATOR TO SIDE PROPERTY LINE. | | MUST BE AT LEAST 3.5 FEET. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ | | ASSOCIATE PLANNER | | 561-822-1442 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-05-08 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-05-08 |
Time |
|
Sent To |
B |
|
Notes |
2018-05-08 11:45:32 | ZONING REVIEW FAILED, GENERATOR MUST BE A MINIMUM OF | | 3.5' FROM PROPERTY LINE, BASED ON CALCULATIONS THE | | PROPOSED GENERATOR .5' OVER INTO SETBACK. PLEASE SHOW | | ON SURVEY THAT LOCATION IS FEASIBLE TO MEET ZONING | | SETBACK REQUIREMENTS. CALLED APPLICANT AND LEFT A | | MESSAGE. | | M. CRUZ | | ASSOCIATE PLANNER | | 561-822-1442 | | [email protected] |
|
|