Plan Review Details - Permit 18050021
Plan Review Stops For Permit 18050021
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-26 Cont ID  
Sent By rmcdouga Date 2018-07-26 Time 06:49 Rev Time 0.00
Received By rmcdouga Date 2018-07-26 Time 06:43 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2018-06-20 Time 08:43 Sent To  
Notes
2018-06-20 08:46:28PLAN REVIEW COMMENTS
 PREVIOUS COMMENTS WERE NOT ADDRESSED.
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR
 LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S
 DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526
 LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS
 GENERATOR. FBC-R 301.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By rmcdouga Date 2018-05-15 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2018-05-15 Time 08:09 Sent To I
Notes
2018-05-15 08:14:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR
 LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S
 DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526
 LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS
 GENERATOR. FBC-R 301.1
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By jpearson Date 2018-07-25 Time 13:44 Rev Time 0.00
Received By jpearson Date 2018-07-25 Time 13:44 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 13:48 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 13:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-07-26 Cont ID  
Sent By tklarge Date 2018-07-26 Time 06:25 Rev Time 0.00
Received By tklarge Date 2018-07-26 Time 06:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 07:54 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 07:24 Sent To  
Notes
2018-06-03 07:52:561) SHOW THE DISTANCE OF THE EXISTING GAS LINE FROM THE
 GAS METER TO THE FURTHEST GAS OUTLET ON THE SYSTEM.THE
 EXISTING PLAN ON FILE IN CITY RECORDS SHOWS 88 FEET TO
 THE FURTHEST OUTLET. THIS DISTANCE SHALL BE USED FOR
 SIZING THE PIPING FOR THE GENERATOR AND FOR THE CHEKING
 THE EXISTING SYSTEM.IF UNDERSIZED, THE EXISTING SYSTEM
 MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM WPB
 AMEND. TO FBC SEC. 107.2.1,
 2) HOW DO YOU PLAN ON SUPPLYING AN 1 1/4 INCH LINE WITH
 A 3/4 INCH LINE AT THE OUTLET OF THE GAS METER? THE
 LINE AT THE OUTLET OF THE METER SHALL BE A MINIMUM OF 1
 1/2 INCHES AS SHOWN ON THE EXISTING PLAN ON FILE WITH
 THE CITY.
 3) THE EXISTING PLAN ON FILE WITH THE CITY ALSO SHOWS A
 FUTURE BBQ THAT NEEDS TO BE LISTED AND ADDED ON THE BTU
 LOAD OF THE SUBMITTED GAS PLAN.2017 FBCR SEC. G2412.3,
 G2412.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By tklarge Date 2018-05-15 Time 06:45 Rev Time 0.00
Received By tklarge Date 2018-05-15 Time 06:38 Sent To  
Notes
2018-05-15 06:45:45 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE
 REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF
 THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE
 DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON
 THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF THE MP REGULATOR FFOR THE EXISTING LOADS.. 2017 FBCR
 SEC. G2420.4.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE SCH.
 40 METALLIC PIPE FOR LESS THAN A 2 PSI SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-26 Cont ID  
Sent By rmcdouga Date 2018-07-26 Time 06:50 Rev Time 0.00
Received By rmcdouga Date 2018-07-16 Time 14:40 Sent To  
Notes
2018-07-17 14:40:10RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2018-05-29 Time 14:05 Sent To  
Notes
2018-05-30 14:05:59RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-20 Cont ID  
Sent By cpuell Date 2018-06-20 Time 09:52 Rev Time 0.00
Received By cpuell Date 2018-06-20 Time 09:52 Sent To  
Notes
2018-05-02 09:52:00ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-07-23 Time 13:48 Rev Time 0.00
Received By mcruz Date 2018-07-23 Time 13:46 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-01 Cont ID  
Sent By mcruz Date 2018-06-01 Time 08:37 Rev Time 0.00
Received By mcruz Date 2018-06-01 Time 08:36 Sent To G
Notes
2018-06-01 08:37:16ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE
 AT LEAST 4' FROM SIDE PROPERTY LINE.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-05-08 Time   Rev Time  
Received By mcruz Date 2018-05-08 Time   Sent To B
Notes
2018-05-08 10:16:56ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE
 AT LEAST 4' FROM SIDE PROPERTY LINE.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]