Plan Review Stops For Permit 18050021 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-26 |
Time |
06:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-26 |
Time |
06:43 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-20 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-06-20 |
Time |
08:43 |
Sent To |
|
|
Notes |
2018-06-20 08:46:28 | PLAN REVIEW COMMENTS | | PREVIOUS COMMENTS WERE NOT ADDRESSED. | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR | | LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S | | DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526 | | LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS | | GENERATOR. FBC-R 301.1 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-15 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-15 |
Time |
08:09 |
Sent To |
I |
|
Notes |
2018-05-15 08:14:48 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR | | LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S | | DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526 | | LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS | | GENERATOR. FBC-R 301.1 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-07-25 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-07-25 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-07-25 |
Time |
13:44 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-05-10 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-05-10 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-05-10 |
Time |
13:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-07-26 |
Time |
06:25 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-26 |
Time |
06:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-06-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-03 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-03 |
Time |
07:24 |
Sent To |
|
|
Notes |
2018-06-03 07:52:56 | 1) SHOW THE DISTANCE OF THE EXISTING GAS LINE FROM THE | | GAS METER TO THE FURTHEST GAS OUTLET ON THE SYSTEM.THE | | EXISTING PLAN ON FILE IN CITY RECORDS SHOWS 88 FEET TO | | THE FURTHEST OUTLET. THIS DISTANCE SHALL BE USED FOR | | SIZING THE PIPING FOR THE GENERATOR AND FOR THE CHEKING | | THE EXISTING SYSTEM.IF UNDERSIZED, THE EXISTING SYSTEM | | MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM WPB | | AMEND. TO FBC SEC. 107.2.1, | | 2) HOW DO YOU PLAN ON SUPPLYING AN 1 1/4 INCH LINE WITH | | A 3/4 INCH LINE AT THE OUTLET OF THE GAS METER? THE | | LINE AT THE OUTLET OF THE METER SHALL BE A MINIMUM OF 1 | | 1/2 INCHES AS SHOWN ON THE EXISTING PLAN ON FILE WITH | | THE CITY. | | 3) THE EXISTING PLAN ON FILE WITH THE CITY ALSO SHOWS A | | FUTURE BBQ THAT NEEDS TO BE LISTED AND ADDED ON THE BTU | | LOAD OF THE SUBMITTED GAS PLAN.2017 FBCR SEC. G2412.3, | | G2412.4. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-05-15 |
Time |
06:45 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-05-15 |
Time |
06:38 |
Sent To |
|
|
Notes |
2018-05-15 06:45:45 | | | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF | | THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE | | REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO | | FBC SEC. 107.2.1. | | 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF | | THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE | | DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON | | THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. | | 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD | | OF THE MP REGULATOR FFOR THE EXISTING LOADS.. 2017 FBCR | | SEC. G2420.4. | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | GENERATOR. 2017 FBCR SEC. G2422.1 (8). | | 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 | | FBCR SEC.G2419.4. | | 8) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE SCH. | | 40 METALLIC PIPE FOR LESS THAN A 2 PSI SYSTEM. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-26 |
Time |
06:50 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-16 |
Time |
14:40 |
Sent To |
|
|
Notes |
2018-07-17 14:40:10 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-20 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-29 |
Time |
14:05 |
Sent To |
|
|
Notes |
2018-05-30 14:05:59 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-06-20 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-06-20 |
Time |
09:52 |
Sent To |
|
|
Notes |
2018-05-02 09:52:00 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-07-23 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-07-23 |
Time |
13:46 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-06-01 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-06-01 |
Time |
08:37 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-06-01 |
Time |
08:36 |
Sent To |
G |
|
Notes |
2018-06-01 08:37:16 | ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE | | AT LEAST 4' FROM SIDE PROPERTY LINE. | | M. CRUZ | | ASSOCIATE PLANNER | | 561-822-1442 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-05-08 |
Time |
|
Rev Time |
|
Received By |
mcruz |
Date |
2018-05-08 |
Time |
|
Sent To |
B |
|
Notes |
2018-05-08 10:16:56 | ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE | | AT LEAST 4' FROM SIDE PROPERTY LINE. | | M. CRUZ | | ASSOCIATE PLANNER | | 561-822-1442 | | [email protected] |
|
|