Plan Review Details - Permit 18050019
Plan Review Stops For Permit 18050019
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-26 Cont ID  
Sent By rmcdouga Date 2018-07-26 Time 09:03 Rev Time 0.00
Received By rmcdouga Date 2018-07-26 Time 09:03 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 07:58 Rev Time 0.00
Received By rmcdouga Date 2018-06-20 Time 07:57 Sent To I
Notes
2018-06-20 07:58:54PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR
 G007043-0 AND G007042-0 THAT'S SPECIFICATIONS WERE
 SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE
 AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT
 BE USED WITH THIS GENERATOR. FBC-R 301.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2018-05-14 Time 07:35 Sent To I
Notes
2018-05-14 09:04:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR
 LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S
 DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526
 LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS
 GENERATOR. FBC-R 301.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 14:08 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 14:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-07-25 Cont ID  
Sent By mcruz Date 2018-07-24 Time 10:26 Rev Time 0.00
Received By tklarge Date 2018-07-25 Time 14:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-04 Cont ID  
Sent By tklarge Date 2018-06-04 Time 05:05 Rev Time 0.00
Received By tklarge Date 2018-06-04 Time 04:19 Sent To  
Notes
2018-06-04 05:05:171) SHOW THE DISTANCE FROM THE EXISTING GAS METER TO THE
 MOST REMOTE GAS OUTLET ON THE SYSTEM. THE EXISTING GAS
 DRAWING ON FILE IN CITY RECORDS SHOWS THE FURTHEST
 DISTANCE AS 67 FT. THIS IS THE DISTANCE THAT IS TO BE
 USE FOR THE SIZING OF THIS SYTEM.2017 FBC-FUEL GAS
 SEC.402.4.1.
 2) THE MINIMUM SIZE OF THE SCH. 40 METALLIC PIPE AT THE
 METER OUTLET SHALL BE 2 INCHES BASED ON THE TOTAL BTU
 LOAD AND THE EXISTING DISTANCE OF THE MOST REMOTE GAS
 OUTLET ON THIS SYSTEM. 2017 FBC-FUEL GAS SEC. 402.4.1,
 401.3, 401.
 3) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS FOR
 THIS ADDRESS SHOWS THE SIZE OF THE PIPE ENTERING THE
 STRUCTURE AS 1 INCH AND YOUR PLAN SHOWSS 3/4 INCH.
 CLARIFY.
 4) THE SUBMITTED GAS PLAN NOTES A 3/4 INCH LINE
 SUPPLYING AN EXISTING 1 1/4 INCH PE LINE TO THE POOL
 HEATER AND A NEW 1 1/4 SCH. 40 METALLIC LINE FOR THE
 GENERATOR. SUBMIT CALCULATIONS/DOCUMENTATION AS TO HOW
 YOU ARE GOING TO ACCOMPLISH THIS FEAT. WPBAMEND. TO FBC
 SEC. 107.2.1, 2017 FBC-FUEL GAS SEC.401.8, 402.2
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By tklarge Date 2018-05-14 Time 06:28 Rev Time 0.00
Received By tklarge Date 2018-05-14 Time 06:08 Sent To  
Notes
2018-05-14 06:11:561) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 12" W.C.GAS METER . WPB AMEND. TO FBC SEC.
 107.2.1.THE SIZE OF THE PIPE SHALL COMPLY WITH 2017
 FBC-FUEL GAS FOR THE TOTAL BTU LOAD ON THE SYSTEM. 2017
 FBC-FUEL GAS SEC.401.3, 401.4.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING
 THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHOW THE DISTANCE FROM GAS METER TO THE FURTHEST
 EXISTING OUTLET ON THE SYSTEM. THE GAS PLAN NOTES
 LONGEST RUN AS 10 FT. SHOW THIS ON THE DRAWING. DOES
 THIS INCLUDE THE FURTHEST OUTLET FROM THE METER ON THE
 EXISTING SYSTEM? CLARIFY ON THE PLANS. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SPECIFY ON THE GAS DRAWING HOW THE 1 INCH GALVANIZED
 PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND PIPING
 OUTDOORS SHALL COMPLY WITH 2017 FBCR SEC.G2415.9,
 G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) IF THE TOTAL LOAD IS 806,000 BTU'S AT THE OUTLET OF
 THE GAS METER, THEN THE MINIMUM PIPE SIZE FROM THE
 METER SHALL BE A MINIMUM OF 1 1/4 INCH PER TABLE 402.4
 (2) DEPENDDING ON THE DISTANCE OF THE FURTHEST GAS
 OUTLET FROM THE GAS METER.
 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-26 Cont ID  
Sent By rmcdouga Date 2018-07-26 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2018-07-16 Time 14:46 Sent To  
Notes
2018-07-17 14:47:10RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By rmcdouga Date 2018-06-20 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2018-05-29 Time 13:54 Sent To  
Notes
2018-05-30 13:54:14RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2018-05-01 Time 09:44 Sent To  
Notes
2018-05-02 09:44:19ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-24 Cont ID  
Sent By mcruz Date 2018-07-24 Time 10:26 Rev Time 0.00
Received By mcruz Date 2018-07-24 Time 10:26 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-05-08 Time   Rev Time  
Received By   Date 2018-05-08 Time   Sent To B
Notes
2018-05-08 10:34:50ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE
 AT LEAST 4' FROM SIDE PROPERTY LINE.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]