Plan Review Stops For Permit 18050019 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-26 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-26 |
Time |
09:03 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-20 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-06-20 |
Time |
07:57 |
Sent To |
I |
|
Notes |
2018-06-20 07:58:54 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE MODEL NUMBERS FOR THE GENERAC 22KW GENERATOR | | G007043-0 AND G007042-0 THAT'S SPECIFICATIONS WERE | | SUBMITTED ARE NOT LISTED IN THE GENERATOR TABLE ON THE | | AMERICAST PAD ENGINEERING. THEREFORE, THIS PAD CAN NOT | | BE USED WITH THIS GENERATOR. FBC-R 301.1 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-14 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-14 |
Time |
07:35 |
Sent To |
I |
|
Notes |
2018-05-14 09:04:09 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR | | LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S | | DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526 | | LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS | | GENERATOR. FBC-R 301.1 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-05-10 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-05-10 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-05-10 |
Time |
14:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2018-07-25 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-07-24 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-25 |
Time |
14:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-06-04 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-04 |
Time |
05:05 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-04 |
Time |
04:19 |
Sent To |
|
|
Notes |
2018-06-04 05:05:17 | 1) SHOW THE DISTANCE FROM THE EXISTING GAS METER TO THE | | MOST REMOTE GAS OUTLET ON THE SYSTEM. THE EXISTING GAS | | DRAWING ON FILE IN CITY RECORDS SHOWS THE FURTHEST | | DISTANCE AS 67 FT. THIS IS THE DISTANCE THAT IS TO BE | | USE FOR THE SIZING OF THIS SYTEM.2017 FBC-FUEL GAS | | SEC.402.4.1. | | 2) THE MINIMUM SIZE OF THE SCH. 40 METALLIC PIPE AT THE | | METER OUTLET SHALL BE 2 INCHES BASED ON THE TOTAL BTU | | LOAD AND THE EXISTING DISTANCE OF THE MOST REMOTE GAS | | OUTLET ON THIS SYSTEM. 2017 FBC-FUEL GAS SEC. 402.4.1, | | 401.3, 401. | | 3) THE EXISTING GAS PLAN ON FILE IN CITY RECORDS FOR | | THIS ADDRESS SHOWS THE SIZE OF THE PIPE ENTERING THE | | STRUCTURE AS 1 INCH AND YOUR PLAN SHOWSS 3/4 INCH. | | CLARIFY. | | 4) THE SUBMITTED GAS PLAN NOTES A 3/4 INCH LINE | | SUPPLYING AN EXISTING 1 1/4 INCH PE LINE TO THE POOL | | HEATER AND A NEW 1 1/4 SCH. 40 METALLIC LINE FOR THE | | GENERATOR. SUBMIT CALCULATIONS/DOCUMENTATION AS TO HOW | | YOU ARE GOING TO ACCOMPLISH THIS FEAT. WPBAMEND. TO FBC | | SEC. 107.2.1, 2017 FBC-FUEL GAS SEC.401.8, 402.2 | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-05-14 |
Time |
06:28 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-05-14 |
Time |
06:08 |
Sent To |
|
|
Notes |
2018-05-14 06:11:56 | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF | | THE 12" W.C.GAS METER . WPB AMEND. TO FBC SEC. | | 107.2.1.THE SIZE OF THE PIPE SHALL COMPLY WITH 2017 | | FBC-FUEL GAS FOR THE TOTAL BTU LOAD ON THE SYSTEM. 2017 | | FBC-FUEL GAS SEC.401.3, 401.4. | | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE SERVING | | THE EXISTING GAS LOAD.WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SHOW THE DISTANCE FROM GAS METER TO THE FURTHEST | | EXISTING OUTLET ON THE SYSTEM. THE GAS PLAN NOTES | | LONGEST RUN AS 10 FT. SHOW THIS ON THE DRAWING. DOES | | THIS INCLUDE THE FURTHEST OUTLET FROM THE METER ON THE | | EXISTING SYSTEM? CLARIFY ON THE PLANS. WPB AMEND. TO | | FBC SEC. 107.2.1. | | 4) SPECIFY ON THE GAS DRAWING HOW THE 1 INCH GALVANIZED | | PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND PIPING | | OUTDOORS SHALL COMPLY WITH 2017 FBCR SEC.G2415.9, | | G2415.11. | | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | GENERATOR. 2017 FBCR SEC. G2422.1 (8). | | 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 | | FBCR SEC.G2419.4. | | 8) IF THE TOTAL LOAD IS 806,000 BTU'S AT THE OUTLET OF | | THE GAS METER, THEN THE MINIMUM PIPE SIZE FROM THE | | METER SHALL BE A MINIMUM OF 1 1/4 INCH PER TABLE 402.4 | | (2) DEPENDDING ON THE DISTANCE OF THE FURTHEST GAS | | OUTLET FROM THE GAS METER. | | 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE | | CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. | | TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-26 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-16 |
Time |
14:46 |
Sent To |
|
|
Notes |
2018-07-17 14:47:10 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-20 |
Time |
08:07 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-29 |
Time |
13:54 |
Sent To |
|
|
Notes |
2018-05-30 13:54:14 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-14 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-01 |
Time |
09:44 |
Sent To |
|
|
Notes |
2018-05-02 09:44:19 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-07-24 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-07-24 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-07-24 |
Time |
10:26 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-05-08 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-05-08 |
Time |
|
Sent To |
B |
|
Notes |
2018-05-08 10:34:50 | ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE | | AT LEAST 4' FROM SIDE PROPERTY LINE. | | M. CRUZ | | ASSOCIATE PLANNER | | 561-822-1442 | | [email protected] |
|
|