Plan Review Stops For Permit 18050016 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-26 |
Time |
07:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-26 |
Time |
06:57 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-06-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-19 |
Time |
18:30 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-06-19 |
Time |
18:27 |
Sent To |
I |
|
Notes |
2018-06-19 18:28:59 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PREVIOUS COMMENTS WERE NOT ADDRESSED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-14 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-14 |
Time |
09:06 |
Sent To |
I |
|
Notes |
2018-05-14 09:20:00 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SPECIFICATIONS FOR THE GENERAC 22KW GENERATOR | | LISTS A UNIT WEIGHT OF 466 LBS. AND THE ENGINEER'S | | DRAWINGS FOR THE PAD REQUIRE A MINIMUM WEIGHT OF 526 | | LBS. THEREFORE, THIS PAD CAN NOT BE USED WITH THIS | | GENERATOR. FBC-R 301.1 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-07-25 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-07-25 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-07-25 |
Time |
13:59 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-05-10 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-05-10 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-05-10 |
Time |
14:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-07-26 |
Time |
|
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-07-26 |
Time |
05:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-06-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-03 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-03 |
Time |
07:56 |
Sent To |
|
|
Notes |
2018-06-03 08:46:16 | 1) THE EXISTING PLANS ON FILE WITH THE CITY SHOW A BBQ | | GRILL AND ALSO A POOL HEATER. THE BTU LOADS OF THESE | | APPLIANCES MUST BE ADDED INTO THE TOTAL BTU LOAD FOR | | THIS SYSTEM. 2017 FBCR SEC. G2412.3, 2412.4 G2412.8. IF | | UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO | | ENSURE A SAFE OPERATING SYSTEM. | | 2) THE SHUTOFF VALVE ON THE LINE TO THE INTERIOR OF THE | | STRUCTURE SHALL BE LOCATED IMMEDIATELY AHEAD OF THE | | REGULATOR, NOT AFTER THE REGULATOR. 2017 FBCR SEC. | | G2420.4. | | 3) SHOW THE DISTANCE FROM THE MP REGULATOR FOR THE | | EXISTING LOAD INTO THE STRUCTURE TO THE FURTHEST OUTLET | | ON THAT SECTION OF THE SYSTEM. COMPLY WITH 2017 FBCR | | SEC. G2413.4.1. | | 4) INDICATE ON THE PLANS WHICH GAS SIZING TABLE IS USED | | FOR THE LOW PRESSURE SYSTEM. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-05-14 |
Time |
06:04 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-05-14 |
Time |
05:56 |
Sent To |
|
|
Notes |
2018-05-14 06:01:58 | | | 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF | | THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE | | REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO | | FBC SEC. 107.2.1. | | 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF | | THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE | | DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON | | THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. | | 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD | | OF THE MP REGULATOR FOR THE EXISTING LOADS.. 2017 FBCR | | SEC. G2420.4. | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | GENERATOR. 2017 FBCR SEC. G2422.1 (8). | | 6) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 | | FBCR SEC.G2419.4. | | 7) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE | | CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. | | TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-07-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-07-26 |
Time |
07:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-07-16 |
Time |
14:43 |
Sent To |
|
|
Notes |
2018-07-17 14:44:04 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-19 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-03 |
Time |
08:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-29 |
Time |
13:59 |
Sent To |
|
|
Notes |
2018-05-30 13:59:50 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-14 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-01 |
Time |
09:45 |
Sent To |
|
|
Notes |
2018-05-02 09:45:43 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-07-23 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-07-23 |
Time |
13:33 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-05-31 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-05-31 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-05-31 |
Time |
16:37 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-07-23 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-05-08 |
Time |
|
Rev Time |
|
Received By |
mcruz |
Date |
2018-05-08 |
Time |
|
Sent To |
B |
|
Notes |
2018-05-08 10:41:42 | ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE | | AT LEAST 4' FROM SIDE PROPERTY LINE. | | M. CRUZ | | ASSOCIATE PLANNER | | 561-822-1442 | | [email protected] |
|
|