Plan Review Details - Permit 18050001
Plan Review Stops For Permit 18050001
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 10:02 Rev Time 0.00
Received By rmcdouga Date 2018-05-14 Time 09:57 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-20 Cont ID  
Sent By jpearson Date 2018-05-20 Time 08:54 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 08:54 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 14:47 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 14:47 Sent To  
Notes
2018-05-10 14:47:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-07-12 Cont ID  
Sent By tklarge Date 2018-07-12 Time 09:50 Rev Time 0.00
Received By tklarge Date 2018-07-11 Time 06:47 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-06-18 Cont ID  
Sent By tklarge Date 2018-06-18 Time 13:03 Rev Time 0.00
Received By tklarge Date 2018-06-18 Time 12:40 Sent To I
Notes
2018-06-18 13:03:101) THE GAS PLAN SHOWS 1 1/4 INCH AND 3/4 INCH PIPING
 AND THE SHEET YOU HAVE SUBMITTED FOR THE REGULATOR
 SHOWS AN INLET SIZE OF 3/4 INCH AND AN OUTLET SIZE OF 1
 INCH. CLARIFY.
 2) SHOW THE ORIFICE SIZE FOR THE REGULATOR BEING USED
 SO THE BTU LOAD CAN BE CHECKED.
 3) THERE ARE TWO DIFFERENT SETS OF GAS PLANS IN THIS
 SUBMITTAL. REMOVE ALL OLD DOCUMENTS AND SUBMIT ONLY TWO
 SETS OF PLANS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-05-19 Cont ID  
Sent By tklarge Date 2018-05-19 Time 08:54 Rev Time 0.00
Received By tklarge Date 2018-05-19 Time 08:53 Sent To  
Notes
2018-05-19 08:54:16NONE OF THE COMMENTS BELOW HAVE BEEN ADDRESSED FROM THE
 FIRST REVIEW. COMPLY WITH ALL PREVIOUS COMMENTS.
  
 1) THE COPIES OF THE GAS SIZING TABLES THAT HAVE BEEN
 SUBMITTED ARE FROM THE 2014 FBC-FUEL GAS. SUBMIT THE
 PROPER SIZING TABLES FROM THE 2017 FBC-FUEL GAS. THESE
 TABLES HAVE CHANGED IN THE 2017 FBC-FUEL GAS SO ENSURE
 YOU CHECK THAT THE TABLES YOU ARE SUBMITTING ARE
 CORRECT. TABLE 402.4 (6) FOR SCH. 40 METALLIC PIPE IN
 THE 2017 CODE HAS AN INLET PRESSURE OF 3 PSI WITH A
 PRESSURE DROP OF 2.0 PSI AND TABLE 402.4 (22) FOR PE
 PIPE IN THE 2017 FBC-FUEL GAS IS FOR AN INLET PRESSURE
 OF 2 PSI WITH A PRESSURE DROP OF 1.0 PSI. IT IS OBVIOUS
 YOU CANNOT USE THESE TABLES THAT YOU HAVE SUBMITTED.
 ***NOTE***
 PLEASE DO NOT TRY TO ENLARGE THE GAS SIZING TABLES. THE
 PROCESS IS MAKING THE TABLES BLURRED AND VERY DIFFICULT
 TO READ.
 2) THE GAS DRAWING APPEARS TO SHOW A SECOND STAGE
 REGULATOR JUST DOWNSTREAM OF THE GAS METER ON THE
 CONSUMER SIDE. WHY WOULD IT BE LOCATED AT THE OUTLET OF
 THE GAS METER? THAT WOULD MAKE THE PSI TO THE EXISTING
 POOL HEATER LESS THAN 2 PSI. CLARIFY.
 3) THE GAS RISER IS SHOWING AN 1 1/4 INCH LINE AT 2 PSI
 TO THE EXISTING POOL HEATER WITH A 3/4 INCH SHUTOFF
 VALVE. CLARIFY.
 4) IS THE EXISTING 1 1/4 INCH GALVANIZED LINE
 UNDERGROUND? I UNDERSTAND IT IS EXISTING BUT GALVANIZED
 PIPING IS NOT PERMITTED TO BE INSTALLED UNDERGROUND.
 ZINC COATINGS (GALVANIZING)SHALL NOT BE DEEMED ADEQUATE
 PROTECTION FOR GAS PIPING UNDERGROUND. 2017 FBC-FUEL
 GAS SEC.404.11.
 IN THE FUTURE, PLEASE ATTEMPT TO SUBMIT GAS DRAWINGS
 THAT ARE EXPANDED SO THAT ALL THE INFORMATION IS NOT
 CRAMMED TOGETHER . WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOTE: I SUGGEST THE A REPRESENTATIVE FROM DIG IT
 UNLIMITED CONTACT ME TO SET UP A MEETING TO GO OVER
 THESE COMMENTS BECAUSE THE COMMENT REGARDING THE SIZING
 TABLES IS APPEARING IN OTHER PLAN REVIEWS FOR DIG IT
 AND I WOULD LIKE TO GET THE ISSUE RESOLVED SO WE CAN
 TRY TO GET YOUR PERMITS ISSUED AND GET YOUR PROJECTS
 GOING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By tklarge Date 2018-05-14 Time 04:59 Rev Time 0.00
Received By tklarge Date 2018-05-14 Time 04:00 Sent To  
Notes
2018-05-14 04:59:141) THE COPIES OF THE GAS SIZING TABLES THAT HAVE BEEN
 SUBMITTED ARE FROM THE 2014 FBC-FUEL GAS. SUBMIT THE
 PROPER SIZING TABLES FROM THE 2017 FBC-FUEL GAS. THESE
 TABLES HAVE CHANGED IN THE 2017 FBC-FUEL GAS SO ENSURE
 YOU CHECK THAT THE TABLES YOU ARE SUBMITTING ARE
 CORRECT. TABLE 402.4 (6) FOR SCH. 40 METALLIC PIPE IN
 THE 2017 CODE HAS AN INLET PRESSURE OF 3 PSI WITH A
 PRESSURE DROP OF 2.0 PSI AND TABLE 402.4 (22) FOR PE
 PIPE IN THE 2017 FBC-FUEL GAS IS FOR AN INLET PRESSURE
 OF 2 PSI WITH A PRESSURE DROP OF 1.0 PSI. IT IS OBVIOUS
 YOU CANNOT USE THESE TABLES THAT YOU HAVE SUBMITTED.
 ***NOTE***
 PLEASE DO NOT TRY TO ENLARGE THE GAS SIZING TABLES. THE
 PROCESS IS MAKING THE TABLES BLURRED AND VERY DIFFICULT
 TO READ.
 2) THE GAS DRAWING APPEARS TO SHOW A SECOND STAGE
 REGULATOR JUST DOWNSTREAM OF THE GAS METER ON THE
 CONSUMER SIDE. WHY WOULD IT BE LOCATED AT THE OUTLET OF
 THE GAS METER? THAT WOULD MAKE THE PSI TO THE EXISTING
 POOL HEATER LESS THAN 2 PSI. CLARIFY.
 3) THE GAS RISER IS SHOWING AN 1 1/4 INCH LINE AT 2 PSI
 TO THE EXISTING POOL HEATER WITH A 3/4 INCH SHUTOFF
 VALVE. CLARIFY.
 4) IS THE EXISTING 1 1/4 INCH GALVANIZED LINE
 UNDERGROUND? I UNDERSTAND IT IS EXISTING BUT GALVANIZED
 PIPING IS NOT PERMITTED TO BE INSTALLED UNDERGROUND.
 ZINC COATINGS (GALVANIZING)SHALL NOT BE DEEMED ADEQUATE
 PROTECTION FOR GAS PIPING UNDERGROUND. 2017 FBC-FUEL
 GAS SEC.404.11.
 IN THE FUTURE, PLEASE ATTEMPT TO SUBMIT GAS DRAWINGS
 THAT ARE EXPANDED SO THAT ALL THE INFORMATION IS NOT
 CRAMMED TOGETHER . WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOTE: I SUGGEST THE A REPRESENTATIVE FROM DIG IT
 UNLIMITED CONTACT ME TO SET UP A MEETING TO GO OVER
 THESE COMMENTS BECAUSE THE COMMENT REGARDING THE SIZING
 TABLES IS APPEARING IN OTHER PLAN REVIEWS FOR DIG IT
 AND I WOULD LIKE TO GET THE ISSUE RESOLVED SO WE CAN
 TRY TO GET YOUR PERMITS ISSUED AND GET YOUR PROJECTS
 GOING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-12 Cont ID  
Sent By tklarge Date 2018-07-12 Time 09:51 Rev Time 0.00
Received By tklarge Date 2018-07-06 Time 13:31 Sent To  
Notes
2018-07-09 13:31:21RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-18 Cont ID  
Sent By tklarge Date 2018-06-18 Time 13:03 Rev Time 0.00
Received By tklarge Date 2018-06-12 Time 10:57 Sent To  
Notes
2018-06-13 10:57:31RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-05-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-17 Time 11:01 Sent To  
Notes
2018-05-18 11:02:06RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By rmcdouga Date 2018-05-14 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2018-05-01 Time 09:47 Sent To  
Notes
2018-05-02 09:47:54ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-07-23 Time 08:55 Rev Time 0.00
Received By mcruz Date 2018-07-23 Time 08:51 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-05-08 Time   Rev Time  
Received By mcruz Date 2018-05-08 Time   Sent To B
Notes
2018-05-08 10:47:36ZONING REVIEW PASSED - PLEASE NOTE GENERATOR SHALL BE
 AT LEAST 4' FROM SIDE PROPERTY LINE.
 M. CRUZ
 ASSOCIATE PLANNER
 561-822-1442
 [email protected]