Plan Review Details - Permit 18041368
Plan Review Stops For Permit 18041368
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-08 Cont ID  
Sent By shill Date 2018-07-08 Time 12:34 Rev Time 0.00
Received By shill Date 2018-07-08 Time 12:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 11:14 Rev Time 0.00
Received By shill Date 2018-06-15 Time 11:07 Sent To  
Notes
2018-06-15 11:15:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PLUMBING COMMENTS; FBC ACCESSIBILITY COMMENTS
 ARE APPLICABLE FOR BUILDING REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-12 Cont ID  
Sent By ppetty Date 2018-07-12 Time 10:09 Rev Time 0.00
Received By ppetty Date 2018-07-12 Time 10:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By jpearson Date 2018-06-07 Time 10:07 Rev Time 0.00
Received By jpearson Date 2018-06-07 Time 09:37 Sent To  
Notes
2018-06-07 10:06:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E3.2 IS MISSING THE SEAL/SIGNATURE FROM
 DESIGNER. IT HAS BEEN SIGNED/SEALED BY THE ARCHITECT,
 HOWEVER IT MUST BE SIGNED/SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC
 107.2.1
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-02 Cont ID  
Sent By scaldero Date 2018-07-02 Time 11:51 Rev Time 0.00
Received By scaldero Date 2018-07-02 Time 11:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-07 Cont ID  
Sent By scaldero Date 2018-05-07 Time 13:12 Rev Time 0.00
Received By scaldero Date 2018-05-07 Time 13:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-03 Cont ID  
Sent By gjohnson Date 2018-08-03 Time 08:59 Rev Time 0.00
Received By gjohnson Date 2018-06-25 Time 15:43 Sent To  
Notes
2018-06-27 15:43:27C24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 11:15 Rev Time 0.00
Received By shill Date 2018-04-30 Time 16:04 Sent To  
Notes
2018-05-01 16:04:14C10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-03 Cont ID  
Sent By ccole Date 2018-07-03 Time 16:46 Rev Time 0.00
Received By ccole Date 2018-07-03 Time 16:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-29 Cont ID  
Sent By ccole Date 2018-05-29 Time 14:54 Rev Time 0.00
Received By ccole Date 2018-05-29 Time 14:52 Sent To  
Notes
2018-05-29 15:20:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18041368
 5/29/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SECTION 301.15 FBC MC- WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. PLEASE PROVIDE DETAILS AND
 SUBMIT A FL, PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE
 ROOF STANDS- RULE 9N-3 FAC
  
 2) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLERS- SECTION 307.2 FBC MC
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-03 Cont ID  
Sent By gjohnson Date 2018-08-03 Time 08:59 Rev Time 0.00
Received By gjohnson Date 2018-08-02 Time 17:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-08 Cont ID  
Sent By gjohnson Date 2018-06-08 Time 10:31 Rev Time 0.00
Received By gjohnson Date 2018-06-07 Time 16:03 Sent To  
Notes
2018-06-08 12:21:441ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC 604.5.2 REAR WALL.THE
 REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND
 EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 2. TOILET PAPER DISPENSERS OUTLET OF THE DISPENSER
 SHALL BE 15 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR . PER FBC ACC 604.7
  
 3.PLEASE LABEL DIMENSIONS ON THE CLEAR SPACE FOR THE
 TOILET LAVATORY AND WATER FOUNTAIN. PER FBC ACC 604.3.1
 , 606.2 , 602.2
  
 4. SHT.LS-1 SHOWS A TABLE AND CHAIRS ENCROACHING INTO
 THE CLEAR FLOOR SPACE OF THE WATER FOUNTAIN PLEASE SHAW
 THE CLEAR FLOOR SPACE CLEAR OF ANY OBSTRUCTIONS. PER
 FBC ACC 606.2
  
 5. THE SINK IN THE BUSINESS LOUNGE SHALL COMPLY WITH
 FBC ACC 606.2, 606.3
  
 6. SHT. P0.1 THE DRINKING FOUNTAIN IS MISSING FROM THE
 WATER AND SANITARY ISOMETRIC PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.3.5.1.3
  
 7. ON THE SANITARY RISER THE DRINKING FOUNTAIN AND THE
 BREAK ROOM SINK SHALL CONNECT DOWN STREAM OF THE
 BATHROOM GROUPS WET VENTS. PER FBC ACC 912.1
  
 8. ONLY THE FIXTURES OF 2 BATHROOM GROUP CAN CONNECT TO
 A SINGLE WET VENT SYSTEM AS IT IS DRAIN NOW THERE IS 3
 THE EXECUTIVE BATHROOM SHOULD BE VENT BY THE LAVATORY
 AND INCLUDE THE TOILET AND SHOWER CONNECTED TO THAT
 BRANCH. PER FBC PL 912.1, 912.2.1
  
 9. THE SHOWER SHALL COMPLY WITH FBC ACC 608
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2018-05-14 Time   Rev Time 0.00
Received By pgreilic Date 2018-05-11 Time 14:24 Sent To  
Notes
2018-05-14 16:27:06PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]