Plan Review Details - Permit 18041364
Plan Review Stops For Permit 18041364 |
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-11-15 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-11-15 |
Time |
05:06 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-11-02 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-11-02 |
Time |
08:19 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-11-01 |
Time |
16:36 |
Sent To |
I |
|
Notes |
2018-11-02 07:05:27 | 1) THE PLAN DRAWING SHOWS A 30,000 LOG LIGHTER BUT IT | | IS NOT SHOWN ON THE GAS DRAWING. CLARIFY. | | 2) SHOW THE EHD OF THE 1/2 INCH CSST. | | 3) SUBMIT MANUF. SPECS FOR THE LOG LIGHTER IF IT IS TO | | BE INSTALLED. THE LOG LIGHTER SHALL BE LISTED AND | | LABELED. | | 4) THE 1 INCH PE PIPE SUPPLYING THE TWO TANKLESS WATER | | HEATERS IS UNDESIZED. IT MUST BE INCREASED TO 1 1/4 | | INCHES. PER 2017 FBC-FUEL GAS TABLE 402.4(16) THE | | MAXIMUM BTU LOAD AT 40 FEET IS 343,000 BTU'S. THE TWO | | WATER HEATERS TOTAL 370,000 BTU'S. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-05-07 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2018-05-07 |
Time |
07:45 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2018-05-07 |
Time |
07:45 |
Sent To |
|
|
Notes |
2018-05-07 07:57:00 | 05/07/2018 1ST GAS REVIEW**DENIED** | | | | 1) PLANS THAT BEAR THE TILTE BLOCK OF A LICENSE | | ENGINEER REQUIRES PLANS TO BE SEALED AND SIGED PER FL | | ADMIN CODE 61G15-23.001 | | | | 2) SUPPLY TANKLESS INSTALLATION MANUAL SHOW MIN | | DISTANCE REQUIRED FROM A DOOR OR WINDOW THAT OPEN'S. | | SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | 3) SUPPLY WHAT APPROVING BODIES THE STOVE IS LISTED AND | | LABEL UNDER. GAS APPLIANCES SHALL BE LISTED AND | | LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | 4) THE PLAN SHOW TANKLESS WATER HEATER IN 3 DIFFERENT | | LOCATION'S FOR A TOTAL OF 4. YOUR PERMIT APPLICATION IS | | FOR 2 HWH. PLEASE REVISE PLAN TO CLEARIFY. FBC 107.2.1 | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-11-15 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-11-09 |
Time |
14:43 |
Sent To |
|
|
Notes |
2018-11-13 14:44:55 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-11-02 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-11-02 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-10-30 |
Time |
16:07 |
Sent To |
|
|
Notes |
2018-10-31 16:07:29 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-05-07 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2018-05-07 |
Time |
07:57 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2018-04-30 |
Time |
14:22 |
Sent To |
|
|
Notes |
2018-05-01 14:22:22 | PLUMB <5K |
|
|
|