Plan Review Stops For Permit 18041305 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-08-29 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-08-29 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-08-29 |
Time |
08:55 |
Sent To |
|
|
Notes |
2018-08-29 09:04:48 | SHELL ONLY |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-06-05 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-06-05 |
Time |
11:11 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-06-05 |
Time |
09:49 |
Sent To |
|
|
Notes |
2018-06-05 09:54:38 | SHELL ONLY, SECOND REVIEW CHECKLIST. | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | | | ORIGINAL COMMENT: | | 1- PROVIDE ALL THE WIND DESIGN DATA AS REQUIRED BY SEC. | | 1603.1.4 FBC. | | | | SEC. 1603.1.4 WIND DESIGN DATA. | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | STRUCTURE: | | 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, | | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION | | 1609.3.1. | | 2.RISK CATEGORY. | | 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN | | ONE WIND EXPOSURE IS UTILIZED. | | 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY | | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL | | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF | | (KN/M2). | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. PLANS CALL FOR | | REPLACEMENT OF EXISTING STOREFRONT. ALL WIND DESIGN | | DATA IS REQUIRED. PLANS NEED TO BE CLEAR ON THE SCOPE | | OF WORK TO AVOID CONFLICTS/DELAYS. REVISE INFORMATION | | ON PLANS AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | ORIGINAL COMMENT: | | 2- A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED | | BY FAC 61G20-3.001 FOR THE NEW EXTERIOR DOOR #1. | | | | ORIGINAL COMMENT: | | B) DOOR #2 SHOWN ON FLOOR PLAN AT THE ENTRY DOESN'T | | MATCH DOOR SHOWN ON THE DOOR SCHEDULE ON SHEET 1.0A. | | REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | ORIGINAL COMMENT: | | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | ORIGINAL COMMENT: | | 4- REVISE OCCUPANT LOAD NUMBER. NUMBER OF PEOPLE IS | | ROUNDED UP NOT ROUNDED DOWN. 3475 SF DIVIDED BY 100 | | EQUALS 34.75. THEREFORE NUMBER OF PEOPLE IS 35. REVISE | | AS REQUIRED. TABLE 1004.1.2 FBC. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | ORIGINAL COMMENT: | | 5- SHEET 1.0A: | | A) PROVIDE ALL DIMENSIONS FOR RESTROOM LOCATED IN THE | | CENTER OF THE SPACE AND SHOW THE TURNING SPACE REQUIRED | | BY SEC. 603.2.1 FBC-ACCESSIBILITY. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY | | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-05-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-05-18 |
Time |
19:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-05-18 |
Time |
19:13 |
Sent To |
|
|
Notes |
2018-05-21 09:49:23 | SHELL ONLY, BUILDING REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- PROVIDE ALL THE WIND DESIGN DATA AS REQUIRED BY SEC. | | 1603.1.4 FBC. | | | | SEC. 1603.1.4 WIND DESIGN DATA. | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE | | STRUCTURE: | | 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), | | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, | | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION | | 1609.3.1. | | 2.RISK CATEGORY. | | 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN | | ONE WIND EXPOSURE IS UTILIZED. | | 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT. | | 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR | | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY | | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL | | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF | | (KN/M2). | | | | 2- A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED | | BY FAC 61G20-3.001 FOR THE NEW EXTERIOR DOOR #1. | | | | B) DOOR #2 SHOWN ON FLOOR PLAN DOESN'T MATCH DOOR SHOWN | | ON THE DOOR SCHEDULE ON SHEET 1.0A. REVISE AS REQUIRED | | TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. | | | | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS | | | | 4- REVISE OCCUPANT LOAD NUMBER. NUMBER OF PEOPLE IS | | ROUNDED UP NOT ROUNDED DOWN. 3475 SF DIVIDED BY 100 | | EQUALS 34.75. THEREFORE NUMBER OF PEOPLE IS 35. REVISE | | AS REQUIRED. TABLE 1004.1.2 FBC. | | | | 5- SHEET 1.0A: | | A) DOOR FOR ACCESSIBLE RESTROOM LOCATED IN THE CENTER | | OF THE TENANT SPACE SHALL NOT SWING INTO THE CLEAR | | FLOOR SPACE OF THE LAVATORY. REVISE AS REQUIRED. SEC. | | 603.2.3 FBC-ACCESSIBILITY. | | | | B) PROVIDE ALL DIMENSIONS FOR RESTROOM LOCATED IN THE | | CENTER OF THE SPACE AND SHOW THE TURNING SPACE REQUIRED | | BY SEC. 603.2.1 FBC-ACCESSIBILITY. | | | | C) SHOW THE TURNING SPACE REQUIRED BY SEC. 603.2.1 | | FBC-ACCESSIBILITY FOR THE OTHER RESTROOM. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY | | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-08-21 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-08-21 |
Time |
16:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-06-06 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-06-06 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-06-06 |
Time |
13:11 |
Sent To |
|
|
Notes |
2018-06-06 13:11:36 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. RISER DIAGRAM SHOWS PANEL A, BUT THIS PANEL IS NOT | | SHOWN ON THE PLAN. THERE IS A PANEL B SHOWN ON PLAN AND | | THERE IS A PANEL SCHEDULE FOR PANEL B BUT IT IS NOT | | SHOWN ON THE RISER DIAGRAM. SHOW LOCATION OF ALL | | ELECTRICAL PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE | | FOR PANEL A WITH A LOAD CALCULATION. PROVIDE CORRECTION | | TO LOAD CALCULATION FOR PANEL B, ONE OF THE RTU'S IN | | NOT INCLUDED SO THE MATH IS WRONG. WPB FBC 107.2.1; NEC | | 215.5, 220, 408.4 | | 2. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9 | | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | | | NEW COMMENT: | | | | 4. PLEASE BE ADVISED THAT THIS COMMENT HAS NOT BEEN | | ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF | | IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD | | TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS | | REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO | | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-05-09 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-05-09 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-05-09 |
Time |
10:29 |
Sent To |
|
|
Notes |
2018-05-09 14:20:37 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. RISER DIAGRAM SHOWS PANEL A, BUT THIS PANEL IS NOT | | SHOWN ON THE PLAN. THERE IS A PANEL B SHOWN ON PLAN AND | | THERE IS A PANEL SCHEDULE FOR PANEL B BUT IT IS NOT | | SHOWN ON THE RISER DIAGRAM. SHOW LOCATION OF ALL | | ELECTRICAL PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE | | FOR PANEL A WITH A LOAD CALCULATION. PROVIDE CORRECTION | | TO LOAD CALCULATION FOR PANEL B, ONE OF THE RTU'S IN | | NOT INCLUDED SO THE MATH IS WRONG. WPB FBC 107.2.1; NEC | | 215.5, 220, 408.4 | | 2. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9 | | 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2018-08-24 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-08-24 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-08-24 |
Time |
09:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-06-04 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-06-04 |
Time |
12:30 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-06-04 |
Time |
12:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2018-05-01 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-05-01 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-05-01 |
Time |
11:44 |
Sent To |
|
|
Notes |
2018-05-01 11:48:29 | PERMIT # 18041305 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | APPROVED WITH COMMENTS: | | | | 1) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | 2) PERMIT IS FOR SHELL ONLY. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-08-31 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-31 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-08-10 |
Time |
11:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-07 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-07 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-05-24 |
Time |
13:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-05-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-05-18 |
Time |
19:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-04-27 |
Time |
15:28 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2018-05-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-05-18 |
Time |
19:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-05-18 |
Time |
19:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2018-08-24 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-08-24 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-08-24 |
Time |
07:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-05-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-05-29 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-05-29 |
Time |
08:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-05-09 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-05-09 |
Time |
17:24 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-05-09 |
Time |
17:24 |
Sent To |
|
|
Notes |
2018-05-09 17:31:26 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18041305 | | 5/9/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | SOME OF THE COMMENTS BELOW ALSO APPEAR ON PERMIT | | #18041229 BECAUSE THE PLANS ARE BOTH TITLED "VANILLA | | SHELL BUILDOUT", THE APPLICATIONS SHOW THE SAME WORK | | DESCRIPTION, AND BOTH PLANS SHOW THE SAME RTU | | INSTALLATIONS. | | | | 1) REPLACEMENT OF THE AC SYSTEMS ARE NOT EXACT SAME | | SIZE REPLACEMENTS SO COOLING AND HEATING CALCULATIONS | | ARE REQUIRED TO VERIFY ACCURATE SIZING- SECTION | | C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | 2) SHEET C-1, NOTE 3 & SHEET 4.0M: SHOW THE LOCATIONS | | OF THE ROOFTOP HOODS AND PROVIDE CAPPING DETAILS. | | | | 3) 4.0M: DUCT SMOKE DETECTORS ARE REQUIRED IN THE | | SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S , UNLESS | | MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS | | CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY AIR- SECTION | | 606.2.1. | | | | 4) 4.0M: THE CONDENSATE PIPING SHALL BE SUPPORTED AT | | MAXIMUM 4' INTERVALS- TABLE 305.4. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2018-08-31 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-08-31 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-08-31 |
Time |
09:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-06-07 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-07 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-07 |
Time |
09:39 |
Sent To |
|
|
Notes |
2018-06-07 09:54:04 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN | | COMPLIED WITH. 2ND REQUEST. NO RESPONSE LETTER WAS | | PROVIDE | | | | 1. PLEASE PROVIDE WATER ISOMETRIC DRAWING. AMEND TO FBC | | 107.3.5.1.3(3)(13) | | | | 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA PER FBC PL 416.5 PROVIDE | | PIPING DETAIL | | | | 3. IS THE WATER HEATER EXISTING IF NEW PROVIDE | | MANUFACTURE SPECS. PER AMEND TO FBC 107.2.1 PROVIDE | | PIPING DETAIL | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-05-17 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-05-17 |
Time |
13:49 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-05-17 |
Time |
11:39 |
Sent To |
|
|
Notes |
2018-05-17 13:50:03 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. PLEASE PROVIDE WATER ISOMETRIC DRAWING. AMEND TO FBC | | 107.3.5.1.3(3)(13) | | | | 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA PER FBC PL 416.5 | | | | 3. IS THE WATER HEATER EXISTING IF NEW PROVIDE | | MANUFACTURE SPECS. PER AMEND TO FBC 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-08-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2018-08-23 |
Time |
15:59 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2018-08-23 |
Time |
08:21 |
Sent To |
|
|
Notes |
2018-08-23 16:03:36 | PASSED W/PROVISO | | | | THE NEW ROOFTOP RTUS ARE A LOWER PROFILE THAN EXISTING | | AND MUST BE PAINTED TO MATCH THE SKY IN LIEU OF A | | SCREENWALL. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-05-31 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2018-05-31 |
Time |
15:35 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2018-05-31 |
Time |
15:35 |
Sent To |
|
|
Notes |
2018-05-31 15:35:15 | FAILED | | | | 1) REPEAT COMMENT: RESOLUTION NO. 358-16 REQUIRES THAT | | WITHIN VILLAGE COMMONS, ALL NEW MECHANICAL EQUIPMENT, | | WHETHER GROUND OR ROOF MOUNTED, MUST BE SCREENED FROM | | VIEW OF THE PUBLIC. PLEASE PROVIDE VERIFICATION THAT | | THE TWO NEW ROOF MOUNTED RTUS MEET THIS REQUIREMENT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2018-05-15 |
Time |
10:33 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2018-05-15 |
Time |
10:16 |
Sent To |
|
|
Notes |
2018-05-15 10:33:39 | FAILED | | | | 1) RESOLUTION NO. 358-16 REQUIRES THAT WITHIN VILLAGE | | COMMONS, ALL NEW MECHANICAL EQUIPMENT, WHETHER GROUND | | OR ROOF MOUNTED, MUST BE SCREENED FROM VIEW OF THE | | PUBLIC. PLEASE PROVIDE VERIFICATION THAT THE TWO NEW | | ROOF MOUNTED RTUS MEET THIS REQUIREMENT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] |
|
|