Plan Review Details - Permit 18041305
Plan Review Stops For Permit 18041305
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-29 Cont ID  
Sent By jgomez Date 2018-08-29 Time 10:25 Rev Time 0.00
Received By jgomez Date 2018-08-29 Time 08:55 Sent To  
Notes
2018-08-29 09:04:48SHELL ONLY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-05 Cont ID  
Sent By jgomez Date 2018-06-05 Time 11:11 Rev Time 0.00
Received By jgomez Date 2018-06-05 Time 09:49 Sent To  
Notes
2018-06-05 09:54:38SHELL ONLY, SECOND REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE ALL THE WIND DESIGN DATA AS REQUIRED BY SEC.
 1603.1.4 FBC.
  
 SEC. 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2.RISK CATEGORY.
 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN
 ONE WIND EXPOSURE IS UTILIZED.
 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF
 (KN/M2).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. PLANS CALL FOR
 REPLACEMENT OF EXISTING STOREFRONT. ALL WIND DESIGN
 DATA IS REQUIRED. PLANS NEED TO BE CLEAR ON THE SCOPE
 OF WORK TO AVOID CONFLICTS/DELAYS. REVISE INFORMATION
 ON PLANS AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 2- A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED
 BY FAC 61G20-3.001 FOR THE NEW EXTERIOR DOOR #1.
  
 ORIGINAL COMMENT:
 B) DOOR #2 SHOWN ON FLOOR PLAN AT THE ENTRY DOESN'T
 MATCH DOOR SHOWN ON THE DOOR SCHEDULE ON SHEET 1.0A.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 4- REVISE OCCUPANT LOAD NUMBER. NUMBER OF PEOPLE IS
 ROUNDED UP NOT ROUNDED DOWN. 3475 SF DIVIDED BY 100
 EQUALS 34.75. THEREFORE NUMBER OF PEOPLE IS 35. REVISE
 AS REQUIRED. TABLE 1004.1.2 FBC.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 5- SHEET 1.0A:
 A) PROVIDE ALL DIMENSIONS FOR RESTROOM LOCATED IN THE
 CENTER OF THE SPACE AND SHOW THE TURNING SPACE REQUIRED
 BY SEC. 603.2.1 FBC-ACCESSIBILITY.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-21 Cont ID  
Sent By jgomez Date 2018-05-18 Time 19:25 Rev Time 0.00
Received By jgomez Date 2018-05-18 Time 19:13 Sent To  
Notes
2018-05-21 09:49:23SHELL ONLY, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE ALL THE WIND DESIGN DATA AS REQUIRED BY SEC.
 1603.1.4 FBC.
  
 SEC. 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2.RISK CATEGORY.
 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE THAN
 ONE WIND EXPOSURE IS UTILIZED.
 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF
 (KN/M2).
  
 2- A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED
 BY FAC 61G20-3.001 FOR THE NEW EXTERIOR DOOR #1.
  
 B) DOOR #2 SHOWN ON FLOOR PLAN DOESN'T MATCH DOOR SHOWN
 ON THE DOOR SCHEDULE ON SHEET 1.0A. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 4- REVISE OCCUPANT LOAD NUMBER. NUMBER OF PEOPLE IS
 ROUNDED UP NOT ROUNDED DOWN. 3475 SF DIVIDED BY 100
 EQUALS 34.75. THEREFORE NUMBER OF PEOPLE IS 35. REVISE
 AS REQUIRED. TABLE 1004.1.2 FBC.
  
 5- SHEET 1.0A:
 A) DOOR FOR ACCESSIBLE RESTROOM LOCATED IN THE CENTER
 OF THE TENANT SPACE SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF THE LAVATORY. REVISE AS REQUIRED. SEC.
 603.2.3 FBC-ACCESSIBILITY.
  
 B) PROVIDE ALL DIMENSIONS FOR RESTROOM LOCATED IN THE
 CENTER OF THE SPACE AND SHOW THE TURNING SPACE REQUIRED
 BY SEC. 603.2.1 FBC-ACCESSIBILITY.
  
 C) SHOW THE TURNING SPACE REQUIRED BY SEC. 603.2.1
 FBC-ACCESSIBILITY FOR THE OTHER RESTROOM.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-08-21 Cont ID  
Sent By jpearson Date 2018-08-21 Time 16:13 Rev Time 0.00
Received By jpearson Date 2018-08-21 Time 16:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-06 Cont ID  
Sent By jpearson Date 2018-06-06 Time 13:11 Rev Time 0.00
Received By jpearson Date 2018-06-06 Time 13:11 Sent To  
Notes
2018-06-06 13:11:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. RISER DIAGRAM SHOWS PANEL A, BUT THIS PANEL IS NOT
 SHOWN ON THE PLAN. THERE IS A PANEL B SHOWN ON PLAN AND
 THERE IS A PANEL SCHEDULE FOR PANEL B BUT IT IS NOT
 SHOWN ON THE RISER DIAGRAM. SHOW LOCATION OF ALL
 ELECTRICAL PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE
 FOR PANEL A WITH A LOAD CALCULATION. PROVIDE CORRECTION
 TO LOAD CALCULATION FOR PANEL B, ONE OF THE RTU'S IN
 NOT INCLUDED SO THE MATH IS WRONG. WPB FBC 107.2.1; NEC
 215.5, 220, 408.4
 2. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 NEW COMMENT:
  
 4. PLEASE BE ADVISED THAT THIS COMMENT HAS NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By jpearson Date 2018-05-09 Time 14:20 Rev Time 0.00
Received By jpearson Date 2018-05-09 Time 10:29 Sent To  
Notes
2018-05-09 14:20:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS PANEL A, BUT THIS PANEL IS NOT
 SHOWN ON THE PLAN. THERE IS A PANEL B SHOWN ON PLAN AND
 THERE IS A PANEL SCHEDULE FOR PANEL B BUT IT IS NOT
 SHOWN ON THE RISER DIAGRAM. SHOW LOCATION OF ALL
 ELECTRICAL PANELS ON PLAN. ALSO, PROVIDE PANEL SCHEDULE
 FOR PANEL A WITH A LOAD CALCULATION. PROVIDE CORRECTION
 TO LOAD CALCULATION FOR PANEL B, ONE OF THE RTU'S IN
 NOT INCLUDED SO THE MATH IS WRONG. WPB FBC 107.2.1; NEC
 215.5, 220, 408.4
 2. PROVIDE AIC RATING OF NEW PANEL. NEC 110.3, 110.9
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-08-24 Cont ID  
Sent By scaldero Date 2018-08-24 Time 09:51 Rev Time 0.00
Received By scaldero Date 2018-08-24 Time 09:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-04 Cont ID  
Sent By scaldero Date 2018-06-04 Time 12:30 Rev Time 0.00
Received By scaldero Date 2018-06-04 Time 12:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-01 Cont ID  
Sent By scaldero Date 2018-05-01 Time 11:48 Rev Time 0.00
Received By scaldero Date 2018-05-01 Time 11:44 Sent To  
Notes
2018-05-01 11:48:29PERMIT # 18041305
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 2) PERMIT IS FOR SHELL ONLY.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-31 Cont ID  
Sent By gjohnson Date 2018-08-31 Time 09:22 Rev Time 0.00
Received By gjohnson Date 2018-08-10 Time 11:32 Sent To  
Notes
2018-08-14 11:32:29B23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-07 Cont ID  
Sent By gjohnson Date 2018-06-07 Time 09:54 Rev Time 0.00
Received By gjohnson Date 2018-05-24 Time 13:37 Sent To  
Notes
2018-05-25 13:37:57B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-21 Cont ID  
Sent By jgomez Date 2018-05-18 Time 19:25 Rev Time 0.00
Received By jgomez Date 2018-04-27 Time 15:28 Sent To I
Notes
2018-04-30 15:28:38B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-05-21 Cont ID  
Sent By jgomez Date 2018-05-18 Time 19:25 Rev Time 0.00
Received By jgomez Date 2018-05-18 Time 19:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-24 Cont ID  
Sent By ccole Date 2018-08-24 Time 09:36 Rev Time 0.00
Received By ccole Date 2018-08-24 Time 07:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-29 Cont ID  
Sent By ccole Date 2018-05-29 Time 08:40 Rev Time 0.00
Received By ccole Date 2018-05-29 Time 08:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By ccole Date 2018-05-09 Time 17:24 Rev Time 0.00
Received By ccole Date 2018-05-09 Time 17:24 Sent To  
Notes
2018-05-09 17:31:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18041305
 5/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME OF THE COMMENTS BELOW ALSO APPEAR ON PERMIT
 #18041229 BECAUSE THE PLANS ARE BOTH TITLED "VANILLA
 SHELL BUILDOUT", THE APPLICATIONS SHOW THE SAME WORK
 DESCRIPTION, AND BOTH PLANS SHOW THE SAME RTU
 INSTALLATIONS.
  
 1) REPLACEMENT OF THE AC SYSTEMS ARE NOT EXACT SAME
 SIZE REPLACEMENTS SO COOLING AND HEATING CALCULATIONS
 ARE REQUIRED TO VERIFY ACCURATE SIZING- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) SHEET C-1, NOTE 3 & SHEET 4.0M: SHOW THE LOCATIONS
 OF THE ROOFTOP HOODS AND PROVIDE CAPPING DETAILS.
  
 3) 4.0M: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S , UNLESS
 MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEMS
 CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY AIR- SECTION
 606.2.1.
  
 4) 4.0M: THE CONDENSATE PIPING SHALL BE SUPPORTED AT
 MAXIMUM 4' INTERVALS- TABLE 305.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-08-31 Cont ID  
Sent By gjohnson Date 2018-08-31 Time 09:22 Rev Time 0.00
Received By gjohnson Date 2018-08-31 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-06-07 Cont ID  
Sent By gjohnson Date 2018-06-07 Time 09:50 Rev Time 0.00
Received By gjohnson Date 2018-06-07 Time 09:39 Sent To  
Notes
2018-06-07 09:54:042ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN
 COMPLIED WITH. 2ND REQUEST. NO RESPONSE LETTER WAS
 PROVIDE
  
 1. PLEASE PROVIDE WATER ISOMETRIC DRAWING. AMEND TO FBC
 107.3.5.1.3(3)(13)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA PER FBC PL 416.5 PROVIDE
 PIPING DETAIL
  
 3. IS THE WATER HEATER EXISTING IF NEW PROVIDE
 MANUFACTURE SPECS. PER AMEND TO FBC 107.2.1 PROVIDE
 PIPING DETAIL
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By gjohnson Date 2018-05-17 Time 13:49 Rev Time 0.00
Received By gjohnson Date 2018-05-17 Time 11:39 Sent To  
Notes
2018-05-17 13:50:031ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE WATER ISOMETRIC DRAWING. AMEND TO FBC
 107.3.5.1.3(3)(13)
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA PER FBC PL 416.5
  
 3. IS THE WATER HEATER EXISTING IF NEW PROVIDE
 MANUFACTURE SPECS. PER AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-08-23 Cont ID  
Sent By eschneid Date 2018-08-23 Time 15:59 Rev Time 0.25
Received By eschneid Date 2018-08-23 Time 08:21 Sent To  
Notes
2018-08-23 16:03:36PASSED W/PROVISO
  
 THE NEW ROOFTOP RTUS ARE A LOWER PROFILE THAN EXISTING
 AND MUST BE PAINTED TO MATCH THE SKY IN LIEU OF A
 SCREENWALL.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-05-31 Cont ID  
Sent By eschneid Date 2018-05-31 Time 15:35 Rev Time 0.25
Received By eschneid Date 2018-05-31 Time 15:35 Sent To  
Notes
2018-05-31 15:35:15FAILED
  
 1) REPEAT COMMENT: RESOLUTION NO. 358-16 REQUIRES THAT
 WITHIN VILLAGE COMMONS, ALL NEW MECHANICAL EQUIPMENT,
 WHETHER GROUND OR ROOF MOUNTED, MUST BE SCREENED FROM
 VIEW OF THE PUBLIC. PLEASE PROVIDE VERIFICATION THAT
 THE TWO NEW ROOF MOUNTED RTUS MEET THIS REQUIREMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By eschneid Date 2018-05-15 Time 10:33 Rev Time 0.25
Received By eschneid Date 2018-05-15 Time 10:16 Sent To  
Notes
2018-05-15 10:33:39FAILED
  
 1) RESOLUTION NO. 358-16 REQUIRES THAT WITHIN VILLAGE
 COMMONS, ALL NEW MECHANICAL EQUIPMENT, WHETHER GROUND
 OR ROOF MOUNTED, MUST BE SCREENED FROM VIEW OF THE
 PUBLIC. PLEASE PROVIDE VERIFICATION THAT THE TWO NEW
 ROOF MOUNTED RTUS MEET THIS REQUIREMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]