Plan Review Stops For Permit 18041294 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-01-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-01-02 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-01-02 |
Time |
16:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-09-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-09-29 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-09-22 |
Time |
15:44 |
Sent To |
|
|
Notes |
2018-09-29 14:27:11 | **CORRECTIONS** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. EFFECTIVE JULY 1, 2018, SUBMITTALS OVER 25 PAGES ARE | | TO BE DIGITAL. RESUBMITTAL FOR THIS REVISION IS TO BE | | DIGITAL, ALL AFFECTED PAGES. | | | | 2.FOR THIS REVISION, TWO OLD SETS WERE REMOVED. ONE OLD | | SET WAS LEFT, THREE NEW SETS SUBMITTED. THE THREE NEW | | SETS ARE LACKING THE PAGES WHICH WERE NOT REVISED; | | THESE PAGES SHOULD HAVE BEEN REMOVED FROM THE OLD SETS | | AND INSERTED INTO THE NEW SETS. THEREFORE, THE SETS I | | HAVE ARE INCOMPLETE. FOR A FEW EXAMPLES, THE FOLLOWING | | PAGES ARE MISSING FROM THE REVISION: | | | | ALL CIVIL PAGES (NEEDED FOR REFERENCE) | | SEVERAL LANDSCAPE PAGES (NOT CLEAR IF THIS IS NEEDED, | | BUT A PARTIAL LANDSCAPE SHOULD NOT BE IN THE PACKAGE - | | SHOULD BE EITHER COMPLETE OR REMOVED) | | A1.13 | | A1.15 | | A1.17 | | A1.18 | | | | 3. THE ISSUE WITH THE MISSING SHEETS APPEAR TO BE AN | | ISSUE FOR FMEP SHEETS AS WELL AS A AND S SHEETS. | | THEREFORE IT IS NOT POSSIBLE TO ISSUE MECHANICAL AND | | ELECTRICAL, BOTH WHICH HAVE PASSED, AS PREVIOUSLY | | OFFERED. | | | | 4. LANDSCAPE PAGES WERE SUBMITTED. LANDSCAPING IS A | | SEPARATE PERMIT. IT APPEARS THAT 17060986 IS READY FOR | | ISSUANCE BUT HAS NOT BEEN PICKED UP. SINCE IT HAS NOT | | BEEN ISSUED, IF THERE ARE LANDSCAPE REVISIONS, YOU CAN | | RESUBMIT WITH UPDATED SHEETS RATHER THAN HAVE THE | | PERMIT ISSUED. | | | | 5. ON REVISION 6, REVISION CLOUDS 4, 5 WERE REMOVED. TO | | PROPERLY DOCUMENT ALL CHANGES IN WHAT OUR PERMIT RECORD | | CONSIDERS ONE REVISION, PLEASE INCLUDE ALL CLOUDS 4, 5, | | 6 AND (ADDRESSING NEW COMMENTS) 7. | | | | 6. SHEET A1.13, A8.03, A8.04 ARE REFERENCED IN THE | | NARRATIVE BUT WAS NOT PROVIDED, PLEASE CORRELATE. | | | | 7. SHEET A1.16 WAS SUBMITTED WITH A DELTA 6 BUT I WAS | | UNABLE TO LOCATE THIS REVISION AND IT'S NOT INCLUDED IN | | THE NARRATIVE, PLEASE CORRELATE. | | | | 8. A2.04, ROOM 407, FBC B 307.1.1, A NEW FUEL TANK IN A | | NEW ROOM IS SHOWN. NO FIRE RATING IS SHOWN. NO | | INFORMATION REGARDING THE TANK, AMOUNT OF FUEL, | | OCCUPANCY CLASSIFICATION, WAS PROVIDED. | | | | REVISE PLAN TO INCLUDE OCCUPANCY CLASSIFICATION FOR | | THIS NEW ROOM. SEE FBC B TABLE 307.1, FOOTNOTE P, FUEL | | IN THE TANK AND IN VEHICLES ARE EXEMPT, BUT FUEL STORED | | SEPARATELY TO FUEL AN APPLIANCE DOES NOT APPEARS TO BE | | EXEMPT. FBC 107, THERE IS NOT ENOUGH INFORMATION TO | | PROVIDE A COMPLETE REVIEW. REVISE PLAN TO SHOW CLASSIFY | | AS HAZARDOUS OR SHOW AMOUNT ALLOWED UNDER FBC B TABLE | | 307.1(1). | | | | 9. ARCHITECTURAL PAGE PROPOSES NO FIRE RATING FOR NEW | | ROOM 407 FUEL TANK, SHEET P2.06 SHOWS A 3 HOUR RATING; | | PLEASE CORRELATE. | | | | 10. THE TOILET EXHAUST WHICH WAS PREVIOUSLY GOING | | THROUGH STAIR 1, 6TH LEVEL, WAS REROUTED BUT NOW | | PLUMBING PIPING IS IN THE STAIR, SEPARATED BY A | | HORIZONTAL SHAFT WALL. | | | | PER BUILDING OFFICIAL, THIS CONDITION IS ACCEPTABLE BUT | | PROVIDE THE FOLLOWING INFORMATION: | | | | PENETRATION DETAIL FOR THE WALL | | PENETRATION DETAIL FOR THE FLOOR | | SPECIFIC HORIZONTAL SHAFT ASSEMBLY | | | | 11. A7.43 SHOWS FIRE RATING DETAILS, BUT THEY APPEAR | | NON-SYMMETRICAL. IF THEY ARE NON SYMMETRICAL, THEY ARE | | TO BE TESTED FROM BOTH SIDES. SEE ALSO FLORIDA DEC | | STATEMENT DS2016-078. | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-06-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-06-09 |
Time |
18:39 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-09 |
Time |
16:31 |
Sent To |
|
|
Notes |
2018-06-09 18:39:49 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. SEE FBC B 3306, IT APPEARS THAT A BARRIER AND | | OVERHEAD PROTECTION ARE REQUIRED. ACQUIRE PERMITS OR | | PROVIDE EVIDENCE THAT THE PERMITS HAVE ALREADY BEEN | | OBTAINED. | | | | 2. REVISION 4 NARRATIVE STATES THAT A0.01, A1.01, AND | | A1.01A WERE REVISED BUT THE SHEETS WERE NOT INCLUDED IN | | THIS REVISION. | | | | 3. ISSUED SHEET A0.01 HAS A NOTE REGARDING THE 5% | | FLORIDA SPECIAL ACCESSIBILITY ROOMS, BUT IT IS NOT | | CLEAR WHICH ROOMS ARE DESIGNATED. REVISE PLAN AND CHART | | ACCORDINGLY. SHOW THE GRAB BARS REQUIRED BY FBC A | | 806.4(I) AND (III); NOTE WATER CLOSET REQUIREMENTS, | | NOTE OPEN BED FRAME REQUIREMENT. | | | | 4. A1.12, IT IS NOT CLEAR HOW THE OCCUPANT LOAD WAS | | REDUCED. MEETING ROOM 3 WITH 106 OCCUPANTS WAS | | ELIMINATED AND THE AREA COMBINED WITH THE ADJACENT OPEN | | AREA. IS THIS ALL NOW CONSIDERED "PRE-ASSEMBLY" WITH NO | | OCCUPANTS? WE DID NOT REQUIRE OCCUPANTS TO BE COUNTED | | IN THE PRE-ASSEMBLY AREAS AS THE OCCUPANT LOAD IN THE | | MEETING ROOMS WAS CONSERVATIVE (7 SF PER PERSON, | | ALTHOUGH TABLES AND CHAIRS ARE SHOWN). IT APPEARS THAT, | | WITH THE ELIMINATION OF MEETING ROOM 3, PRE-ASSEMBLY | | AREAS ARE LARGER THAN THE MEETING ROOMS. | | | | PLEASE ASSIGN AN AREA DESIGNATION (PRE-ASSEMBLY? OPEN | | MEETING?) TO THIS AREA, AND ASSIGN AN OCCUPANT LOAD TO | | THIS NEW LARGE OPEN AREA, OR CONTACT ME TO DISCUSS. | | | | 5. A1.12 AND A1.31 CONFLICT. ONE USES 7 SF/PERSON FOR | | THE ASSEMBLY AREAS, THE OTHER USES 15 SF/PERSON AND | | ALSO STATES THAT AREA OCCUPIED BY TABLES WAS DEDUCTED | | FROM THE AREA. YOU CANNOT DEDUCT FURNITURE, REVISE | | NOTES AND CORRELATE. IF 15 SF/PERSON IS USED TO | | CALCULATE OCCUPANT LOAD, ALSO INCLUDE OCCUPANT LOAD IN | | THE PRE-ASSEMBLY AREA AT 15 SF/PERSON OR EXPLAIN HOW | | YOU CAN CONTROL THE NUMBER OF PEOPLE IN THIS AREA. | | | | 6. THE PURPOSE OF THE 18'10" DIMENSION IS NOT CLEAR. IT | | APPEARS TO BE INDICATING REMOTENESS OF EXITS BUT IS NOT | | MEASURING EXIT TO EXIT. | | | | 7. A1.16, ELECTRICAL ROOM, HOUSEKEEPING, TEXT IS NOT | | CLEAR, PLEASE PRINT PROPERLY. | | | | 8. A1.16, A DOUBLE KING IS SHOWN; IS THIS ACCESSIBLE? | | SINCE IT APPEARS TO BE THE ONLY DOUBLE KING IT APPEARS | | THAT IT IS REQUIRED TO BE ACCESSIBLE. REVISE PLAN OR | | CLARIFY. | | | | 9. A1.19, THE POOL GATES SHALL OPEN OUTWARD AWAY FROM | | THE POOL AREA, FBC B 454.1.3.1.9. | | | | 10. A1.19, MENS ROOM DOOR 1322 APPEARS TO BE RECESSED | | DUE TO THE COLUMN AND IT IS NOT CLEAR IF IT COMPLIES | | WITH FBC A 404.2.4, 404.2.4.3. | | | | 11. A1.31, POSSIBLY OTHER PAGES, IT APPEARS THAT NOT | | ALL CHANGES WERE CLOUDED. FOR INSTANCE, THE POOL GATES | | ARE NOT CLOUDED. THE OVERALL PLANS ARE DIFFICULT TO | | READ DUE TO THE AMOUNT OF GRAPHICS; CLOUDED CHANGES ARE | | NEEDED ON THE OTHER PAGES TO EXPEDITE PLAN REVIEW, FBC | | 107. | | | | 12. A2.06, FBC A 1004.1, REVISE TO SHOW COMPLIANCE FOR | | EXERCISE EQUIPMENT. | | | | 13. A3.09, A7.22A, POSSIBLY OTHER LOCATIONS, FBC B 603, | | A WOOD CEILING IS SHOWN. THIS DOES NOT APPEAR TO BE | | PERMITTED. REVISE OR CONTACT ME TO DISCUSS. | | | | 14. A7.01, A7.02, POSSIBLY OTHER PAGES; PLYWOOD IS | | PROPOSED; WILL THIS BE FRT? IF YES, REVISE PER FBC B | | 603. IF NOT, NOTE SF AREA; A MINIMAL AMOUNT IS ALLOWED | | AS BACKING. NOTE SF AREA AND EXCEPTION IF FRT IS NOT | | PROPOSED. | | | | | 2018-06-06 16:54:40 | | | | | ****REVIEW IN PROGRESS..... |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-12-14 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-12-14 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-12-14 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-09-02 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-09-02 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-09-02 |
Time |
13:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-05-17 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-05-17 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-05-17 |
Time |
08:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2018-09-12 |
|
|
Cont ID |
|
Sent By |
RRossano |
Date |
2018-09-12 |
Time |
|
Rev Time |
1.00 |
Received By |
rrossano |
Date |
2018-09-12 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2018-06-15 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2018-06-15 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-06-15 |
Time |
09:56 |
Sent To |
|
|
Notes |
2018-06-15 09:56:53 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | APPLICATION OR REVISION IF REQUIRED | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | /FORMS,-PERMITS-APPLICATIONS | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO REVISION | | ISSUANCE - ENGINEERING REVIEW WILL BE DONE NEXT REVIEW | | CYCLE | | | | MAIN PHONE: (561) 822-1200 | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-08-27 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-08-27 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-08-27 |
Time |
12:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-05-14 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-05-02 |
Time |
12:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2018-09-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-09-17 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-09-17 |
Time |
10:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2018-06-11 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-06-11 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-06-11 |
Time |
09:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-01-06 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-01-06 |
Time |
07:49 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-12-04 |
Time |
11:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-10-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-10-01 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-08-22 |
Time |
09:39 |
Sent To |
|
|
Notes |
2018-08-23 09:39:51 | C31 & C32 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-06-15 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-06-15 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-04-30 |
Time |
15:51 |
Sent To |
|
|
Notes |
2018-04-30 15:51:30 | C33 & 34 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-09-19 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-09-18 |
Time |
09:44 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-09-18 |
Time |
10:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-05-14 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-05-11 |
Time |
15:48 |
Sent To |
|
|
Notes |
2018-05-14 11:00:13 | 1ST REVIEW FBC-2014 MECHANICAL | | REVISON PERMIT #18041294 | | MASTER #16061443 | | 5/14/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS M2.08A, M4.01, M7.05: THERE IS A DISCREPANCY | | IN THE PLANS PETAINING TO HOW THE FLAMEBAR DUCTS ARE | | SHOWN TRANSITIONING FROM THE TE SHAFTS INTO THE | | INTERSTICIAL SPACE. SHEET M2.08 SHOWS HORIZONTAL | | TRANSITIONS, BUT SHEET M4.01 SHOWS VERTICAL | | TRANSITIONS. PLEASE NOTE NO DETAILS FOR VERTICAL | | TRANSITIONS ARE SHOWN ON M7.05. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2019-01-04 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-04 |
Time |
17:40 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-04 |
Time |
17:40 |
Sent To |
|
|
Notes |
2019-01-04 17:43:41 | PROVISO: | | | | | | 1. SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622 | | - THE LAVATORY ARE ENCROACHING INTO THE 60 INCH CLEAR | | FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE MAY | | ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014 | | FBC-ACCESS. SEC.604.3.2. //// THE RESPONSE TO THIS | | COMMENT DOES NOT COMPLY WITH THE CODE DUE TO THE | | OCCUPANT LOAD SEPARATE FACILITIES ARE REQUIRED AND BOTH | | SHALL COMPLY WITH ACCESSIBILITY. PER FBC PL 403.2 AND | | FBC ACC 213.1 | | OR | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2018-09-17 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-09-17 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-09-17 |
Time |
09:53 |
Sent To |
|
|
Notes |
2018-09-17 10:00:18 | | | 2ND REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED. | | | | 1) SHT. A2.02 - THE SINK IN THE PREASSEMBLY ROOM NEXT | | TO ROOM #220 SHALL COMPLY WITH THE 2014 | | FBC-ACCESSIBILITY SECS. 212.3, 606.2, 606.3, 606.4.THE | | MAXIMUM HEIGHT OF THE COUNTERTOP/SINK SHALL BE A | | MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR PER THE | | 2014 FBC-ACCESS. SEC. 606.3.//// THE RESPONSE LETTER | | REFERS TO DETAIL # 1 ON SHT. ID. 5.13 I COULD NOT | | LOCATE THAT SHEET IN THIS SUBMITTAL IT APPEARS TO BE | | MISSING PLEASE INDICATE ON THE PLAN THE REQUIRED CLEAR | | FLOOR SPACE AND THE SINK HEIGHT. | | | | 2) SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622 | | - THE LAVATORY APPEARS TO BE ENCROACHING INTO THE 60 | | INCH CLEAR FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE | | MAY ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014 | | FBC-ACCESS. SEC.604.3.2. //// THE RESPONSE TO THIS | | COMMENT DOES NOT COMPLY WITH THE CODE DUE TO THE | | OCCUPANT LOAD SEPARATE FACILITIES ARE REQUIRED AND BOTH | | SHALL COMPLY WITH ACCESSIBILITY. PER FBC PL 403.2 AND | | FBC ACC 213.1 | | | | 4) SUBMIT TWO COPIES OF COMPLETE MANUFACTURER'S | | SPECIFICATIONS FOR THE AUTO-FUEL FILL MINI-SMART PUMP. | | WPB AMEND. TO FBC SEC. 107.2.1.//// COMPLETE | | SPECIFICATION AND INSTALLATION GUIDE IS REQUIRED THE | | DETAIL ON THE PLAN IS JUST A GENERAL DRAWING AND DOES | | NOT HAVE ANY DETAIL SUCH AS THE UL RATING OF THE MOTOR | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-09-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-09-14 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-09-14 |
Time |
14:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-05-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-05-26 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-05-26 |
Time |
04:59 |
Sent To |
|
|
Notes |
2018-05-26 05:03:56 | 1) SHT. A2.02 - THE SINK IN THE PREASSEMBLY ROOM NEXT | | TO ROOM #220 SHALL COMPLY WITH THE 2014 | | FBC-ACCESSIBILITY SECS. 212.3, 606.2, 606.3, 606.4.THE | | MAXIMUM HEIGHT OF THE COUNTERTOP/SINK SHALL BE A | | MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR PERR THE | | 2014 FBC-ACCESS. SEC. 606.3. | | 2) SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622 | | - THE LAVATORY APPEARS TO BE ENCROACHING INTO THE 60 | | INCH CLEAR FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE | | MAY ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014 | | FBC-ACCESS. SEC.604.3.2. | | 3) THE SUBMITTED NARRATIVE LISTS SHT.P5.02 - THIS SHEET | | IS NOT INCLUDED IN THE SET OF PLANS.SUBMIT THIS SHEET | | FOR REVIEW AS IT CONTAINS THE CHANGES TO THE BOILER | | ROOM EQUIPMENT. | | 4) SUBMIT TWO COPIES OF COMPLETE MANUFACTURER'S | | SPECIFICATIONS FOR THE AUTO-FUEL FILL MINI-SMART PUMP. | | WPB AMEND. TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2019-01-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-01-23 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-01-23 |
Time |
15:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2019-01-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-01-02 |
Time |
17:06 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-01-02 |
Time |
17:06 |
Sent To |
|
|
Notes |
2019-01-02 17:08:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. MANY SHEETS ARE NOT DIGITALLY SIGNED. TO AVOID | | ANOTHER PLAN REVIEW CYCLE, PLEASE SEND VIA EMAIL OR | | UPLOAD ONE DIGITALLY SIGNED PDF (OR ONE PER DESIGN | | PROFESSIONAL) WHICH IS IDENTICAL TO THE PLANS UPLOADED. | | | | PLEASE CALL ME IF YOU WISH TO DISCUSS OR IF YOU NEED | | FURTHER DIRECTION. | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2018-12-13 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-12-13 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-12-13 |
Time |
14:16 |
Sent To |
|
|
Notes |
2018-12-13 14:16:46 | EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED | | BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL | | PLAN REQUIRES A DIGITAL SIGNATURE. MANY SHEETS MISSING | | THE DIGITAL SIGNATURE. PROVIDE CORRECTION. WPB FBC | | 107.1; FS 471/481 | 2018-12-06 11:24:48 | 12-06-18 SIGNED AND SEALED INTERIOR DESIGN DRAWINGS | | LOCATED UNDER "SIGNATURES" FOLDER. LEM |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-09-24 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-09-24 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-09-24 |
Time |
16:22 |
Sent To |
|
|
Notes |
2018-09-24 16:24:08 | PROVISO: BIKE RACK MODEL ON ROW SHAL BE CHANGED TO | | SINGLE HITCH AND POST OR LOCATION SHALL BE CHANGED. | | PROPOSED LOCATION OBSTRUCTS THE PEDESTRIAN PATH OF | | TRAVEL. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-06-14 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-06-14 |
Time |
15:50 |
Rev Time |
|
Received By |
aaponte |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2018-06-14 16:38:34 | PROVISO:1. PLEASE PROVIDE DETAILS OF PROPOSED BIKE RACK | | ON PUBLIC ROW. RACK SEEMS TO CONFLICT WITH ADA RAMP AT | | THE CORNER. CIVIL DRAWINGS DO NOT CORRESPOND WITH | | ARCHITECTURAL DRAWINGS. | | 2. WOOD COMPOSITE CLADDING CANNOT BE REMOVED FROM THE | | EYEBROW.THAT DETAIL IS ESSENTIAL TO THE FACADE DESIGN. | | 3. PLEASE CONSIDER PROVIDING SOME BIKE RACKS FOR | | EMPLOYEES INSIDE THE PARKING GARAGE. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439 | | |
|
|