Plan Review Details - Permit 18041294
Plan Review Stops For Permit 18041294
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-02 Cont ID  
Sent By shill Date 2019-01-02 Time 17:08 Rev Time 0.00
Received By shill Date 2019-01-02 Time 16:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-29 Cont ID  
Sent By shill Date 2018-09-29 Time 14:22 Rev Time 0.00
Received By shill Date 2018-09-22 Time 15:44 Sent To  
Notes
2018-09-29 14:27:11**CORRECTIONS**
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. EFFECTIVE JULY 1, 2018, SUBMITTALS OVER 25 PAGES ARE
 TO BE DIGITAL. RESUBMITTAL FOR THIS REVISION IS TO BE
 DIGITAL, ALL AFFECTED PAGES.
  
 2.FOR THIS REVISION, TWO OLD SETS WERE REMOVED. ONE OLD
 SET WAS LEFT, THREE NEW SETS SUBMITTED. THE THREE NEW
 SETS ARE LACKING THE PAGES WHICH WERE NOT REVISED;
 THESE PAGES SHOULD HAVE BEEN REMOVED FROM THE OLD SETS
 AND INSERTED INTO THE NEW SETS. THEREFORE, THE SETS I
 HAVE ARE INCOMPLETE. FOR A FEW EXAMPLES, THE FOLLOWING
 PAGES ARE MISSING FROM THE REVISION:
  
 ALL CIVIL PAGES (NEEDED FOR REFERENCE)
 SEVERAL LANDSCAPE PAGES (NOT CLEAR IF THIS IS NEEDED,
 BUT A PARTIAL LANDSCAPE SHOULD NOT BE IN THE PACKAGE -
 SHOULD BE EITHER COMPLETE OR REMOVED)
 A1.13
 A1.15
 A1.17
 A1.18
  
 3. THE ISSUE WITH THE MISSING SHEETS APPEAR TO BE AN
 ISSUE FOR FMEP SHEETS AS WELL AS A AND S SHEETS.
 THEREFORE IT IS NOT POSSIBLE TO ISSUE MECHANICAL AND
 ELECTRICAL, BOTH WHICH HAVE PASSED, AS PREVIOUSLY
 OFFERED.
  
 4. LANDSCAPE PAGES WERE SUBMITTED. LANDSCAPING IS A
 SEPARATE PERMIT. IT APPEARS THAT 17060986 IS READY FOR
 ISSUANCE BUT HAS NOT BEEN PICKED UP. SINCE IT HAS NOT
 BEEN ISSUED, IF THERE ARE LANDSCAPE REVISIONS, YOU CAN
 RESUBMIT WITH UPDATED SHEETS RATHER THAN HAVE THE
 PERMIT ISSUED.
  
 5. ON REVISION 6, REVISION CLOUDS 4, 5 WERE REMOVED. TO
 PROPERLY DOCUMENT ALL CHANGES IN WHAT OUR PERMIT RECORD
 CONSIDERS ONE REVISION, PLEASE INCLUDE ALL CLOUDS 4, 5,
 6 AND (ADDRESSING NEW COMMENTS) 7.
  
 6. SHEET A1.13, A8.03, A8.04 ARE REFERENCED IN THE
 NARRATIVE BUT WAS NOT PROVIDED, PLEASE CORRELATE.
  
 7. SHEET A1.16 WAS SUBMITTED WITH A DELTA 6 BUT I WAS
 UNABLE TO LOCATE THIS REVISION AND IT'S NOT INCLUDED IN
 THE NARRATIVE, PLEASE CORRELATE.
  
 8. A2.04, ROOM 407, FBC B 307.1.1, A NEW FUEL TANK IN A
 NEW ROOM IS SHOWN. NO FIRE RATING IS SHOWN. NO
 INFORMATION REGARDING THE TANK, AMOUNT OF FUEL,
 OCCUPANCY CLASSIFICATION, WAS PROVIDED.
  
 REVISE PLAN TO INCLUDE OCCUPANCY CLASSIFICATION FOR
 THIS NEW ROOM. SEE FBC B TABLE 307.1, FOOTNOTE P, FUEL
 IN THE TANK AND IN VEHICLES ARE EXEMPT, BUT FUEL STORED
 SEPARATELY TO FUEL AN APPLIANCE DOES NOT APPEARS TO BE
 EXEMPT. FBC 107, THERE IS NOT ENOUGH INFORMATION TO
 PROVIDE A COMPLETE REVIEW. REVISE PLAN TO SHOW CLASSIFY
 AS HAZARDOUS OR SHOW AMOUNT ALLOWED UNDER FBC B TABLE
 307.1(1).
  
 9. ARCHITECTURAL PAGE PROPOSES NO FIRE RATING FOR NEW
 ROOM 407 FUEL TANK, SHEET P2.06 SHOWS A 3 HOUR RATING;
 PLEASE CORRELATE.
  
 10. THE TOILET EXHAUST WHICH WAS PREVIOUSLY GOING
 THROUGH STAIR 1, 6TH LEVEL, WAS REROUTED BUT NOW
 PLUMBING PIPING IS IN THE STAIR, SEPARATED BY A
 HORIZONTAL SHAFT WALL.
  
 PER BUILDING OFFICIAL, THIS CONDITION IS ACCEPTABLE BUT
 PROVIDE THE FOLLOWING INFORMATION:
  
 PENETRATION DETAIL FOR THE WALL
 PENETRATION DETAIL FOR THE FLOOR
 SPECIFIC HORIZONTAL SHAFT ASSEMBLY
  
 11. A7.43 SHOWS FIRE RATING DETAILS, BUT THEY APPEAR
 NON-SYMMETRICAL. IF THEY ARE NON SYMMETRICAL, THEY ARE
 TO BE TESTED FROM BOTH SIDES. SEE ALSO FLORIDA DEC
 STATEMENT DS2016-078.
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-06-09 Cont ID  
Sent By jgomez Date 2018-06-09 Time 18:39 Rev Time 0.00
Received By shill Date 2018-06-09 Time 16:31 Sent To  
Notes
2018-06-09 18:39:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SEE FBC B 3306, IT APPEARS THAT A BARRIER AND
 OVERHEAD PROTECTION ARE REQUIRED. ACQUIRE PERMITS OR
 PROVIDE EVIDENCE THAT THE PERMITS HAVE ALREADY BEEN
 OBTAINED.
  
 2. REVISION 4 NARRATIVE STATES THAT A0.01, A1.01, AND
 A1.01A WERE REVISED BUT THE SHEETS WERE NOT INCLUDED IN
 THIS REVISION.
  
 3. ISSUED SHEET A0.01 HAS A NOTE REGARDING THE 5%
 FLORIDA SPECIAL ACCESSIBILITY ROOMS, BUT IT IS NOT
 CLEAR WHICH ROOMS ARE DESIGNATED. REVISE PLAN AND CHART
 ACCORDINGLY. SHOW THE GRAB BARS REQUIRED BY FBC A
 806.4(I) AND (III); NOTE WATER CLOSET REQUIREMENTS,
 NOTE OPEN BED FRAME REQUIREMENT.
  
 4. A1.12, IT IS NOT CLEAR HOW THE OCCUPANT LOAD WAS
 REDUCED. MEETING ROOM 3 WITH 106 OCCUPANTS WAS
 ELIMINATED AND THE AREA COMBINED WITH THE ADJACENT OPEN
 AREA. IS THIS ALL NOW CONSIDERED "PRE-ASSEMBLY" WITH NO
 OCCUPANTS? WE DID NOT REQUIRE OCCUPANTS TO BE COUNTED
 IN THE PRE-ASSEMBLY AREAS AS THE OCCUPANT LOAD IN THE
 MEETING ROOMS WAS CONSERVATIVE (7 SF PER PERSON,
 ALTHOUGH TABLES AND CHAIRS ARE SHOWN). IT APPEARS THAT,
 WITH THE ELIMINATION OF MEETING ROOM 3, PRE-ASSEMBLY
 AREAS ARE LARGER THAN THE MEETING ROOMS.
  
 PLEASE ASSIGN AN AREA DESIGNATION (PRE-ASSEMBLY? OPEN
 MEETING?) TO THIS AREA, AND ASSIGN AN OCCUPANT LOAD TO
 THIS NEW LARGE OPEN AREA, OR CONTACT ME TO DISCUSS.
  
 5. A1.12 AND A1.31 CONFLICT. ONE USES 7 SF/PERSON FOR
 THE ASSEMBLY AREAS, THE OTHER USES 15 SF/PERSON AND
 ALSO STATES THAT AREA OCCUPIED BY TABLES WAS DEDUCTED
 FROM THE AREA. YOU CANNOT DEDUCT FURNITURE, REVISE
 NOTES AND CORRELATE. IF 15 SF/PERSON IS USED TO
 CALCULATE OCCUPANT LOAD, ALSO INCLUDE OCCUPANT LOAD IN
 THE PRE-ASSEMBLY AREA AT 15 SF/PERSON OR EXPLAIN HOW
 YOU CAN CONTROL THE NUMBER OF PEOPLE IN THIS AREA.
  
 6. THE PURPOSE OF THE 18'10" DIMENSION IS NOT CLEAR. IT
 APPEARS TO BE INDICATING REMOTENESS OF EXITS BUT IS NOT
 MEASURING EXIT TO EXIT.
  
 7. A1.16, ELECTRICAL ROOM, HOUSEKEEPING, TEXT IS NOT
 CLEAR, PLEASE PRINT PROPERLY.
  
 8. A1.16, A DOUBLE KING IS SHOWN; IS THIS ACCESSIBLE?
 SINCE IT APPEARS TO BE THE ONLY DOUBLE KING IT APPEARS
 THAT IT IS REQUIRED TO BE ACCESSIBLE. REVISE PLAN OR
 CLARIFY.
  
 9. A1.19, THE POOL GATES SHALL OPEN OUTWARD AWAY FROM
 THE POOL AREA, FBC B 454.1.3.1.9.
  
 10. A1.19, MENS ROOM DOOR 1322 APPEARS TO BE RECESSED
 DUE TO THE COLUMN AND IT IS NOT CLEAR IF IT COMPLIES
 WITH FBC A 404.2.4, 404.2.4.3.
  
 11. A1.31, POSSIBLY OTHER PAGES, IT APPEARS THAT NOT
 ALL CHANGES WERE CLOUDED. FOR INSTANCE, THE POOL GATES
 ARE NOT CLOUDED. THE OVERALL PLANS ARE DIFFICULT TO
 READ DUE TO THE AMOUNT OF GRAPHICS; CLOUDED CHANGES ARE
 NEEDED ON THE OTHER PAGES TO EXPEDITE PLAN REVIEW, FBC
 107.
  
 12. A2.06, FBC A 1004.1, REVISE TO SHOW COMPLIANCE FOR
 EXERCISE EQUIPMENT.
  
 13. A3.09, A7.22A, POSSIBLY OTHER LOCATIONS, FBC B 603,
 A WOOD CEILING IS SHOWN. THIS DOES NOT APPEAR TO BE
 PERMITTED. REVISE OR CONTACT ME TO DISCUSS.
  
 14. A7.01, A7.02, POSSIBLY OTHER PAGES; PLYWOOD IS
 PROPOSED; WILL THIS BE FRT? IF YES, REVISE PER FBC B
 603. IF NOT, NOTE SF AREA; A MINIMAL AMOUNT IS ALLOWED
 AS BACKING. NOTE SF AREA AND EXCEPTION IF FRT IS NOT
 PROPOSED.
  
  
2018-06-06 16:54:40 
  
 ****REVIEW IN PROGRESS.....

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By jpearson Date 2018-12-14 Time 10:23 Rev Time 0.00
Received By jpearson Date 2018-12-14 Time 10:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-02 Cont ID  
Sent By jpearson Date 2018-09-02 Time 13:05 Rev Time 0.00
Received By jpearson Date 2018-09-02 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-17 Cont ID  
Sent By jpearson Date 2018-05-17 Time 13:34 Rev Time 0.00
Received By jpearson Date 2018-05-17 Time 08:22 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-09-12 Cont ID  
Sent By RRossano Date 2018-09-12 Time   Rev Time 1.00
Received By rrossano Date 2018-09-12 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-06-15 Cont ID  
Sent By mgonzale Date 2018-06-15 Time 09:56 Rev Time 0.00
Received By shill Date 2018-06-15 Time 09:56 Sent To  
Notes
2018-06-15 09:56:53CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION OR REVISION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO REVISION
 ISSUANCE - ENGINEERING REVIEW WILL BE DONE NEXT REVIEW
 CYCLE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-27 Cont ID  
Sent By pleduc Date 2018-08-27 Time   Rev Time 0.00
Received By pleduc Date 2018-08-27 Time 12:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-14 Cont ID  
Sent By pleduc Date 2018-05-14 Time   Rev Time 0.00
Received By pleduc Date 2018-05-02 Time 12:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-09-17 Cont ID  
Sent By tklarge Date 2018-09-17 Time 10:01 Rev Time 0.00
Received By gjohnson Date 2018-09-17 Time 10:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-06-11 Cont ID  
Sent By tklarge Date 2018-06-11 Time 10:31 Rev Time 0.00
Received By tklarge Date 2018-06-11 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-06 Cont ID  
Sent By cpuell Date 2019-01-06 Time 07:49 Rev Time 0.00
Received By cpuell Date 2018-12-04 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-01 Cont ID  
Sent By shill Date 2018-10-01 Time 16:56 Rev Time 0.00
Received By shill Date 2018-08-22 Time 09:39 Sent To  
Notes
2018-08-23 09:39:51C31 & C32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 09:56 Rev Time 0.00
Received By shill Date 2018-04-30 Time 15:51 Sent To  
Notes
2018-04-30 15:51:30C33 & 34

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-19 Cont ID  
Sent By ccole Date 2018-09-18 Time 09:44 Rev Time 0.00
Received By ccole Date 2018-09-18 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By ccole Date 2018-05-14 Time 10:48 Rev Time 0.00
Received By ccole Date 2018-05-11 Time 15:48 Sent To  
Notes
2018-05-14 11:00:131ST REVIEW FBC-2014 MECHANICAL
 REVISON PERMIT #18041294
 MASTER #16061443
 5/14/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2.08A, M4.01, M7.05: THERE IS A DISCREPANCY
 IN THE PLANS PETAINING TO HOW THE FLAMEBAR DUCTS ARE
 SHOWN TRANSITIONING FROM THE TE SHAFTS INTO THE
 INTERSTICIAL SPACE. SHEET M2.08 SHOWS HORIZONTAL
 TRANSITIONS, BUT SHEET M4.01 SHOWS VERTICAL
 TRANSITIONS. PLEASE NOTE NO DETAILS FOR VERTICAL
 TRANSITIONS ARE SHOWN ON M7.05.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-01-04 Cont ID  
Sent By gjohnson Date 2019-01-04 Time 17:40 Rev Time 0.00
Received By gjohnson Date 2019-01-04 Time 17:40 Sent To  
Notes
2019-01-04 17:43:41PROVISO:
  
  
 1. SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622
 - THE LAVATORY ARE ENCROACHING INTO THE 60 INCH CLEAR
 FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE MAY
 ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014
 FBC-ACCESS. SEC.604.3.2. //// THE RESPONSE TO THIS
 COMMENT DOES NOT COMPLY WITH THE CODE DUE TO THE
 OCCUPANT LOAD SEPARATE FACILITIES ARE REQUIRED AND BOTH
 SHALL COMPLY WITH ACCESSIBILITY. PER FBC PL 403.2 AND
 FBC ACC 213.1
 OR
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-09-17 Cont ID  
Sent By gjohnson Date 2018-09-17 Time 09:53 Rev Time 0.00
Received By gjohnson Date 2018-09-17 Time 09:53 Sent To  
Notes
2018-09-17 10:00:18 
 2ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED.
  
 1) SHT. A2.02 - THE SINK IN THE PREASSEMBLY ROOM NEXT
 TO ROOM #220 SHALL COMPLY WITH THE 2014
 FBC-ACCESSIBILITY SECS. 212.3, 606.2, 606.3, 606.4.THE
 MAXIMUM HEIGHT OF THE COUNTERTOP/SINK SHALL BE A
 MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR PER THE
 2014 FBC-ACCESS. SEC. 606.3.//// THE RESPONSE LETTER
 REFERS TO DETAIL # 1 ON SHT. ID. 5.13 I COULD NOT
 LOCATE THAT SHEET IN THIS SUBMITTAL IT APPEARS TO BE
 MISSING PLEASE INDICATE ON THE PLAN THE REQUIRED CLEAR
 FLOOR SPACE AND THE SINK HEIGHT.
  
 2) SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622
 - THE LAVATORY APPEARS TO BE ENCROACHING INTO THE 60
 INCH CLEAR FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE
 MAY ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014
 FBC-ACCESS. SEC.604.3.2. //// THE RESPONSE TO THIS
 COMMENT DOES NOT COMPLY WITH THE CODE DUE TO THE
 OCCUPANT LOAD SEPARATE FACILITIES ARE REQUIRED AND BOTH
 SHALL COMPLY WITH ACCESSIBILITY. PER FBC PL 403.2 AND
 FBC ACC 213.1
  
 4) SUBMIT TWO COPIES OF COMPLETE MANUFACTURER'S
 SPECIFICATIONS FOR THE AUTO-FUEL FILL MINI-SMART PUMP.
 WPB AMEND. TO FBC SEC. 107.2.1.//// COMPLETE
 SPECIFICATION AND INSTALLATION GUIDE IS REQUIRED THE
 DETAIL ON THE PLAN IS JUST A GENERAL DRAWING AND DOES
 NOT HAVE ANY DETAIL SUCH AS THE UL RATING OF THE MOTOR
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-09-14 Cont ID  
Sent By tklarge Date 2018-09-14 Time 14:11 Rev Time 0.00
Received By gjohnson Date 2018-09-14 Time 14:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-26 Cont ID  
Sent By tklarge Date 2018-05-26 Time 08:33 Rev Time 0.00
Received By tklarge Date 2018-05-26 Time 04:59 Sent To  
Notes
2018-05-26 05:03:561) SHT. A2.02 - THE SINK IN THE PREASSEMBLY ROOM NEXT
 TO ROOM #220 SHALL COMPLY WITH THE 2014
 FBC-ACCESSIBILITY SECS. 212.3, 606.2, 606.3, 606.4.THE
 MAXIMUM HEIGHT OF THE COUNTERTOP/SINK SHALL BE A
 MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR PERR THE
 2014 FBC-ACCESS. SEC. 606.3.
 2) SHTS. A7.05 & A.7.41, DETAIL #14 - TOILET ROOM # 622
 - THE LAVATORY APPEARS TO BE ENCROACHING INTO THE 60
 INCH CLEAR FLOOR SPACE FOR THE WATER CLOSET. NO FIXTURE
 MAY ENCROACH INTO THIS CLEAR FLOOR SPACE PER 2014
 FBC-ACCESS. SEC.604.3.2.
 3) THE SUBMITTED NARRATIVE LISTS SHT.P5.02 - THIS SHEET
 IS NOT INCLUDED IN THE SET OF PLANS.SUBMIT THIS SHEET
 FOR REVIEW AS IT CONTAINS THE CHANGES TO THE BOILER
 ROOM EQUIPMENT.
 4) SUBMIT TWO COPIES OF COMPLETE MANUFACTURER'S
 SPECIFICATIONS FOR THE AUTO-FUEL FILL MINI-SMART PUMP.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-01-23 Cont ID  
Sent By shill Date 2019-01-23 Time 15:09 Rev Time 0.00
Received By shill Date 2019-01-23 Time 15:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-01-02 Cont ID  
Sent By shill Date 2019-01-02 Time 17:06 Rev Time 0.00
Received By shill Date 2019-01-02 Time 17:06 Sent To  
Notes
2019-01-02 17:08:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. MANY SHEETS ARE NOT DIGITALLY SIGNED. TO AVOID
 ANOTHER PLAN REVIEW CYCLE, PLEASE SEND VIA EMAIL OR
 UPLOAD ONE DIGITALLY SIGNED PDF (OR ONE PER DESIGN
 PROFESSIONAL) WHICH IS IDENTICAL TO THE PLANS UPLOADED.
  
 PLEASE CALL ME IF YOU WISH TO DISCUSS OR IF YOU NEED
 FURTHER DIRECTION.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-12-13 Cont ID  
Sent By jpearson Date 2018-12-13 Time 14:16 Rev Time 0.00
Received By jpearson Date 2018-12-13 Time 14:16 Sent To  
Notes
2018-12-13 14:16:46EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE. MANY SHEETS MISSING
 THE DIGITAL SIGNATURE. PROVIDE CORRECTION. WPB FBC
 107.1; FS 471/481
2018-12-06 11:24:4812-06-18 SIGNED AND SEALED INTERIOR DESIGN DRAWINGS
 LOCATED UNDER "SIGNATURES" FOLDER. LEM

Review Stop Z ZONING
Rev No 2 Status P Date 2018-09-24 Cont ID  
Sent By aaponte Date 2018-09-24 Time 16:22 Rev Time 0.00
Received By aaponte Date 2018-09-24 Time 16:22 Sent To  
Notes
2018-09-24 16:24:08PROVISO: BIKE RACK MODEL ON ROW SHAL BE CHANGED TO
 SINGLE HITCH AND POST OR LOCATION SHALL BE CHANGED.
 PROPOSED LOCATION OBSTRUCTS THE PEDESTRIAN PATH OF
 TRAVEL.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-14 Cont ID  
Sent By aaponte Date 2018-06-14 Time 15:50 Rev Time  
Received By aaponte Date   Time   Sent To  
Notes
2018-06-14 16:38:34PROVISO:1. PLEASE PROVIDE DETAILS OF PROPOSED BIKE RACK
 ON PUBLIC ROW. RACK SEEMS TO CONFLICT WITH ADA RAMP AT
 THE CORNER. CIVIL DRAWINGS DO NOT CORRESPOND WITH
 ARCHITECTURAL DRAWINGS.
 2. WOOD COMPOSITE CLADDING CANNOT BE REMOVED FROM THE
 EYEBROW.THAT DETAIL IS ESSENTIAL TO THE FACADE DESIGN.
 3. PLEASE CONSIDER PROVIDING SOME BIKE RACKS FOR
 EMPLOYEES INSIDE THE PARKING GARAGE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  