Plan Review Details - Permit 18041221
Plan Review Stops For Permit 18041221
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-23 Cont ID  
Sent By shill Date 2018-10-23 Time 15:10 Rev Time 0.00
Received By shill Date 2018-10-23 Time 15:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 11:06 Rev Time 0.00
Received By shill Date 2018-09-02 Time 11:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-15 Cont ID  
Sent By shill Date 2018-06-15 Time 13:07 Rev Time 0.00
Received By shill Date 2018-06-15 Time 07:24 Sent To  
Notes
2018-06-15 13:08:04****CORRECTIONS****
 COURTESY REVIEW TO FURTHER CLARIFY PLAN REVIEW ISSUES
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B CHAPTER 10, FBC ACCESSIBILITY, MEANS OF EGRESS
 NOT CLEAR. REVISE PLAN TO SHOW COMPLIANCE WITH, OR
 CLARIFY; 1-A1.101, CONSTRUCTION PLAN - PLAZA, DOES NOT
 SHOW ALL EXIT DOORS AND THE ACCESSIBLE ROUTE. THERE ARE
 PARALLEL LINES AT THE EAST LOBBY EXIT DOOR; ARE THESE
 STAIRS? IF NOT STAIRS, WHAT DO THE LINES DEPICT? THERE
 IS A "TENANT SPACE" AREA TO THE WEST OF THE PLAZA,
 APPEARS TO INCLUDE SIX EXIT DOORS, BUT THE DOORS ARE
 EXCLUDED FROM THE "ACCESSIBLE ROUTE". FBC 107.
  
 2. A-1.01, NOTE 22 IS "NEW STEPS, SEE LANDSCAPE". NOTE
 17 IS "NEW ACCESSIBLE CONCRETE RAMP". PLEASE REVISE
 PLAN TO INCLUDE THE FOLLOWING:
  
 1-LS2.03 HAS DETAILS FOR RAMP AND STAIR. THERE IS A
 NOTE POINTING TO THE STAIR, "REINFORCING, REF
 STRUCTURAL"; ANOTHER NOTE WHICH STATES "COMPACTED SUB
 GRADE PER GEOTECH OR CIVIL RECOMMENDATION". WHERE ON
 THE CIVILS? PLEASE PROVIDE SOILS REPORT IF IT'S DESIGN
 TEAM'S INTENT THAT A SOILS REPORT SPECIFIES SOIL
 COMPACTION.
  
 ADVISE WHERE THE STRUCTURAL DETAIL FOR THE RAMP CAN BE
 LOCATED ON STRUCTURAL PLAN, OR REVISE PLAN TO INCLUDE.
  
 3. REVISE PLAN TO CLEARLY SHOW THE RISE AND WIDTH OF
 RAMPS AND STAIRS. IT IS NOT CLEAR IF TWO OR MORE
 HANDRAILS ARE REQUIRED. HANDRAIL IS SHOWN ON THE DETAIL
 BUT NOT ON THE PLAN.
  
 4. REVISE PLAN TO PROVIDE A PLAN FOR THE RAMP WHICH
 SHOWS LANDINGS, TURNS IF APPLICABLE, RUN DIMENSION.
  
 5. RAMPS AND STAIRS ARE NOT SHOWN ON S1.101 "STRUCTURAL
 AREA OF WORK PLAN". IT APPEARS THAT A STRUCTURAL DETAIL
 FOR RAMP IS REQUIRED.
  
 SEE FBC A 405, 504, 505, FBC B CHAPTER 10, FBC 107
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 16:28 Rev Time 0.00
Received By shill Date 2018-05-22 Time 15:30 Sent To  
Notes
2018-05-22 16:28:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SECTION 4 A4.103, OTHER LOCATIONS, PLYWOOD
 SPECIFIED. FBC B 603, REVISE TO FRT OR CLARIFY EXTENT
 OF USE OF NON FRT AND APPLICABLE EXCEPTION.
  
 2. SCOPE NOT CLEAR. FBC 107, SHEET SA1.101B INDICATES
 THAT EAST LOBBY HAS ADDITIONAL SQUARE FOOTAGE, AND THE
 EAST AND WEST LOBBIES ARE SHOWN AS INCLUDED IN THE
 SCOPE OF THIS PERMIT. PLEASE CLARIFY SCOPE.
  
 3. FBC 107, PROVIDE A STRUCTURAL/ARCHITECTURAL DETAIL
 FOR THE STAIRS. STAIR LOCATIONS ARE NOT CLEAR EXCEPT
 FOR THE LANDSCAPE ARCHITECT PLANS, WHICH ARE NOT
 DIGITALLY SIGNED AND SEALED, AND IT IS MY UNDERSTANDING
 THAT MEANS OF EGRESS ELEMENTS CANNOT BE DESIGNED BY A
 LANDSCAPE ARCHITECT. EITHER HAVE ARCHITECT REVISE PLANS
 TO INCLUDE LOCATION AND DETAILS FOR THE STAIRS, OR
 CONTACT ME VIA EMAIL IF YOU BELIEVE THAT THIS IS IN THE
 SCOPE OF THE LANDSCAPE ARCHITECT LICENSE AND I'LL
 CONTACT THE FLORIDA BOARD OF ARCHITECTS FOR A
 DETERMINATION. (SHEET LS1.01, OTHER PAGES).
  
 STAIRS AND HANDRAILS TO COMPLY WITH FBC A 504. DISTANCE
 FROM EDGE OF STAIR TO GRADE NOT CLEAR, REVISE PLAN TO
 CLARIFY; IF REQUIRED PROVIDE A GUARDRAIL DETAIL.
  
 4. FBC A 405, PROVIDE A COMPLETE DETAIL FOR RAMP AND
 HANDRAIL. EDGE PROTECTION NOT SHOWN, LANDINGS NOT
 SHOWN, ETC.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-31 Cont ID  
Sent By jpearson Date 2018-08-31 Time 09:10 Rev Time 0.00
Received By jpearson Date 2018-08-31 Time 09:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-20 Cont ID  
Sent By jpearson Date 2018-05-20 Time 11:09 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 11:09 Sent To  
Notes
2018-05-20 11:09:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LIGHTING CONTROLS AS SPECIFIED IN THE FBC
 ENERGY CONSERVATION. FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-10-16 Cont ID  
Sent By rrossano Date 2018-10-16 Time   Rev Time 0.00
Received By rrossano Date 2018-10-16 Time   Sent To I
Notes
2018-10-16 13:03:25PLANS HAVE BEEN PASSED THROUGH FORMAL ENGINEERING
 REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-09-12 Cont ID  
Sent By RRossano Date 2018-09-12 Time   Rev Time 1.00
Received By rrossano Date 2018-09-12 Time   Sent To I
Notes
2018-09-12 12:20:03UNDER DEVELOPMENT REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 16:29 Rev Time 0.00
Received By shill Date 2018-05-22 Time 16:29 Sent To  
Notes
2018-05-22 16:29:31CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-23 Cont ID  
Sent By shill Date 2018-10-23 Time 15:11 Rev Time 0.00
Received By shill Date 2018-10-03 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-26 Cont ID  
Sent By shill Date 2018-09-26 Time 09:01 Rev Time 0.00
Received By shill Date 2018-08-14 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-06 Cont ID  
Sent By shill Date 2018-06-06 Time 15:43 Rev Time 0.00
Received By shill Date 2018-04-27 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-09-11 Cont ID  
Sent By gjohnson Date 2018-09-11 Time 16:10 Rev Time 0.00
Received By gjohnson Date 2018-09-11 Time 14:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-10-23 Cont ID  
Sent By shill Date 2018-10-23 Time 15:11 Rev Time 0.00
Received By shill Date 2018-10-23 Time 15:11 Sent To  
Notes
2018-10-23 15:11:45***PROVISO***
 SUBMIT AT TIME OF PERMIT CARD PICKUP
  
  
 DIGITAL SIGNATURE/SEALS ARE IN COMPLIANCE WITH FS471,
 FS481 EXCEPT AS NOTED BELOW. SHEETS SUBMITTED FOR NEXT
 REVIEW CYCLE NEED REVIEW.
  
 LANDSCAPE ARCHITECT'S PLANS ARE NOT DIGITALLY SIGNED
 AND SEALED. ONE PAPER ORIGINAL MAY BE PROVIDED AFTER
 ALL REVIEWS HAVE PASSED TO RESOLVE THIS COMMENT.
  
 [email protected], 561-805-6724
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 11:07 Rev Time 0.00
Received By shill Date 2018-09-02 Time 11:07 Sent To  
Notes
2018-09-02 11:08:04DIGITAL SIGNATURE/SEALS ARE IN COMPLIANCE WITH FS471,
 FS481 EXCEPT AS NOTED BELOW. SHEETS SUBMITTED FOR NEXT
 REVIEW CYCLE NEED REVIEW.
  
 LANDSCAPE ARCHITECT'S PLANS ARE NOT DIGITALLY SIGNED
 AND SEALED. ONE PAPER ORIGINAL MAY BE PROVIDED AFTER
 ALL REVIEWS HAVE PASSED TO RESOLVE THIS COMMENT.
  
 [email protected], 561-805-6724
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 17:08 Rev Time 0.00
Received By shill Date 2018-05-22 Time 16:29 Sent To  
Notes
2018-05-22 17:08:52DIGITAL SIGNATURE/SEALS ARE IN COMPLIANCE WITH FS471,
 FS481 EXCEPT AS NOTED BELOW. SHEETS SUBMITTED FOR NEXT
 REVIEW CYCLE NEED REVIEW.
  
 LANDSCAPE ARCHITECT'S PLANS ARE NOT DIGITALLY SIGNED
 AND SEALED. ONE PAPER ORIGINAL MAY BE PROVIDED AFTER
 ALL REVIEWS HAVE PASSED TO RESOLVE THIS COMMENT.
  
 [email protected], 561-805-6724
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-09-26 Cont ID  
Sent By aaponte Date 2018-09-26 Time 08:30 Rev Time 0.00
Received By aaponte Date 2018-09-26 Time 08:30 Sent To  
Notes
2018-09-26 08:47:34PROVISO:
 1. THE LANDSCAPE AREAS SOURTH OF THE VALET DROP OFF
 SHALL BE REDUCED AT THE EAST AND WEST END TO ALLOW FOR
 THE FULL WIDTH OF THE PEDESTRIAN CROSSING. PLEASE
 CONTACT ANA MARIA APONTE AT 561-822-1439 FOR DETAILS.
 2. THE GROUND COVER FOR THE AREA SOUTH OF THE VALET
 DROP-OFF SHALL BE CHANGED FROM GRASS TO A LOW GROUND
 COVER MATERIAL ACCEPTABLE TO THE CITY AND FDOT. PLEASE
 REVISE LANDSCAPE PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-06-01 Cont ID  
Sent By AA Date 2018-06-01 Time 16:19 Rev Time 0.00
Received By aaponte Date 2018-06-01 Time 16:19 Sent To  
Notes
2018-06-01 16:23:36PROVISO:
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE GROUND COVER FOR THE AREA SOUTH OF THE VALET
 DROP-OFF SHALL BE CHANGED FROM GRASS TO A LOW GROUND
 COVER MATERIAL ACCEPTABLE TO THE CITY AND FDOT.
  