Plan Review Details - Permit 18041216
Plan Review Stops For Permit 18041216
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-05-17 Cont ID  
Sent By lcrespo Date 2018-05-17 Time 16:49 Rev Time 0.00
Received By lcrespo Date 2018-05-17 Time 16:49 Sent To  
Notes
2018-05-17 16:51:1005/17/18 GAS APPROVED AND SENT TO PROCESSING, LAC

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By thunt Date 2018-04-30 Time 16:23 Rev Time 0.00
Received By thunt Date 2018-04-30 Time 16:23 Sent To  
Notes
2018-04-30 16:34:1004/30/2018 1ST GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) VALUE SEEMS LOW. MUST INCLUDE COST OF EQUIPMENT.
 PROVIDE SIGN BONA FIDE CONTRACT.WPB AMEND TO THE FBC
 109.3 BUILDING PERMIT VALUATIONS.
  
 2) YOU HAVE INCLUDED SIZING TABLE 402.4 (15) WHICH IS
 CSST. YOUR PLAN DOES NOT SHOW THE USE OF CSST. FBC
 107.2.1
  
 3) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUTS INCLUDING RISERS FOR EACH SECTIONS
 OF PIPE PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2.
 OR 2017 FBC-RES SEC. G2413.4.1, G2413.4.2
  
 4) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 6) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 7) SHOW THE LOCATION OF THE BBQ GRILL ON A FLOOR PLAN.
 IF UNDER THE REAR COVEREWD PORCH THEN A HOOD
 VENTILATION SYSTEM WOULD BE REQUIRED. FBC-FUEL AND GAS
 623.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-17 Cont ID  
Sent By lcrespo Date 2018-05-17 Time 16:49 Rev Time 0.00
Received By lcrespo Date 2018-05-09 Time 14:49 Sent To  
Notes
2018-05-09 14:49:55RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-30 Cont ID  
Sent By thunt Date 2018-04-30 Time 16:34 Rev Time 0.00
Received By thunt Date 2018-04-26 Time 11:32 Sent To I
Notes
2018-04-27 11:32:43PLUMB <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved