Plan Review Details - Permit 18041159
Plan Review Stops For Permit 18041159
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By rmcdouga Date 2018-07-30 Time 08:30 Rev Time 0.00
Received By rmcdouga Date 2018-07-30 Time 08:13 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-03 Cont ID  
Sent By rmcdouga Date 2018-05-03 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2018-05-03 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By jpearson Date 2018-07-25 Time 13:54 Rev Time 0.00
Received By jpearson Date 2018-07-25 Time 13:54 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 13:09 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 13:09 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 16:38 Rev Time 0.00
Received By lcrespo Date 2018-08-20 Time 16:38 Sent To  
Notes
2018-08-20 16:39:3508/20/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-07-30 Cont ID  
Sent By tklarge Date 2018-07-30 Time 06:26 Rev Time 0.00
Received By tklarge Date 2018-07-30 Time 06:09 Sent To  
Notes
2018-07-30 06:26:301) SHOW THE TYPE OF PIPE AND THE PIPE SIZE AT THE
 OUTLET OF THE 2 PSI METER. WPB AMEND. TO FBC SEC.
 107.2.1. THE EXISTING PLANS ON FILE WITH THE CITY SHOW
 AN EXISTING 1 1/2 INCH LINE. WILL THIS REMAIN OR BE
 CHANGED? CLARIFY.2ND REQUEST.
 2) THE SUBMITTED GAS DRAWING SHOWS THE PIPE SIZE OF THE
 SECTION OF PIPE TO THE REGULATOR SERVING THE EXISTING
 GAS LOAD AS 3/4 INCH.. THE PLANS ON FILE WITH THE CITY
 SHOWS AN 1 1/4 INCH LINE TO THE INTERIOR. WILL THIS
 LINE BE REPLACED WITH A 3/4 INCH LINE? CLARIFY. 2ND
 REQUEST.
 3) THE GAS PLAN ON FILE AT THE CITY SHOWS A 1 INCH GAS
 LINE TO THE POOL HEATER AND THE SUBMITTED GAS DRAWING
 SHOWS A 3/4 INCH LINE. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By tklarge Date 2018-05-17 Time 11:26 Rev Time 0.00
Received By tklarge Date 2018-05-17 Time 11:14 Sent To I
Notes
2018-05-17 11:26:24 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE
 REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF
 THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE
 DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON
 THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF THE MP REGULATOR FOR THE EXISTING LOADS.. 2017 FBCR
 SEC. G2420.4.
 5) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH
 GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND
 PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR
 SEC.G2415.9, G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION SHEETS FOR THE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2017 FBCR
 SEC.G2421.1, FBC-FUEL GAS SEC. 410.1.
 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
 10) CITY RECORDS SHOW THE BTU LOAD OF THE EXISTING
 SYSTEM AS 585, 000 BTU'S AND THE SUBMITTED PLAN SSHOWS
 525,000. REVISE THE EXISTING BTU LOAD.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-08-20 Cont ID  
Sent By lcrespo Date 2018-08-20 Time 16:38 Rev Time 0.00
Received By lcrespo Date 2018-08-16 Time 13:34 Sent To  
Notes
2018-08-17 13:34:16RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-30 Cont ID  
Sent By rmcdouga Date 2018-07-30 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2018-07-16 Time 14:04 Sent To  
Notes
2018-07-17 14:04:20RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-17 Cont ID  
Sent By tklarge Date 2018-05-17 Time 11:26 Rev Time 0.00
Received By tklarge Date 2018-04-25 Time 13:27 Sent To I
Notes
2018-04-26 13:27:41ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-07-23 Time 08:49 Rev Time 0.00
Received By mcruz Date 2018-07-23 Time 08:46 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By ajones Date 2018-05-02 Time 12:16 Rev Time 0.00
Received By ajones Date 2018-05-02 Time 12:16 Sent To G
Notes
***NONE***