Plan Review Details - Permit 18041158
Plan Review Stops For Permit 18041158
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By rmcdouga Date 2018-07-26 Time 08:57 Rev Time 0.00
Received By rmcdouga Date 2018-07-26 Time 08:39 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-03 Cont ID  
Sent By rmcdouga Date 2018-05-03 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2018-05-03 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-26 Cont ID  
Sent By jpearson Date 2018-07-26 Time 09:28 Rev Time 0.00
Received By jpearson Date 2018-07-26 Time 09:28 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-10 Cont ID  
Sent By jpearson Date 2018-05-10 Time 13:00 Rev Time 0.00
Received By jpearson Date 2018-05-10 Time 13:00 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 14:21 Rev Time 0.00
Received By tklarge Date 2018-07-25 Time 13:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-06-29 Cont ID  
Sent By tklarge Date 2018-06-29 Time 07:44 Rev Time 0.00
Received By tklarge Date 2018-06-29 Time 06:24 Sent To I
Notes
2018-06-29 07:46:081) THE EXISTING GAS PLANS ON FILE AT THE CITY SHOW A
 SUMMER KITCHEN WITH A 55,000 BTU LOAD BUT THIS IS NOT
 SHOWN ON THE SUBMITTED GAS DRAWING. REVISE THE GAS
 DRAWING TO REFLECT THE SUMMER KITCHEN AND REVISE THE
 TOTAL BTU LOAD ON THE GAS DOCUMENTS. WPB AMEND. TO FBC
 SEC. 107.2.1, 2017 FBC-FUEL GAS SEC.401.3, 401.4.
 2) THE SHUTOFF VALVE ON THE 3/4 INCH EXISTING LINE INTO
 THE STRUCTURE SHALL BE LOCATED IMMEDIATELY AHEAD OF THE
 REGULATOR. 2017 FBC-FUEL GAS SEC.409.4.
 3) SHOW THE DISTANCE FROM THE MP REGULATOR FOR THE
 EXISTING LINE INTO THE STRUCTURE TO THE MOST REMOTE GAS
 OUTLET ON THAT SECTION. THIS DISTANCE WILL DETERMINE
 THE PIPE SIZING.THE EXISTING PLANS ON FILE SHOW THE
 LONGEST RUN AS 100 FEET.
 4) THE EXISTING PLANS ON FILE AT THE CITY SHOW THE PIPE
 SIZE AT THE METER OUTLET AS 1 INCH AND THE SUBMITTED
 PLAN SHOWS 3/4 INCH. CLARIFY.
 5) SHOW THE PIPE SIZE OF THE PE ON THE GAS PLAN. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SHOW THE DISTANCE FROM THE METER TO THE REGULATOR
 FOR THE EXISTING LINE INTO THE STRUCTURE.
  
 NOTE: THE SAME GAS DRAWING THAT WAS REJECTED ON THE
 REVIEW OF 6/3 HAS BEEN RESUBMITTED AND REJECTED AGAIN
 BECAUSE NONE OF THE CORRECTIONS WERE MADE. RESUBMITTAL
 OF THESE PLANS WILL REQUIRE PAYMENT OF 4X THE PLAN
 REVIEW FEE IN ACCORDANCE WITH FL. STATUTE 553.80 (2)
 (B).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 13:55 Rev Time 0.00
Received By tklarge Date 2018-06-03 Time 13:19 Sent To I
Notes
2018-06-03 13:55:331) THE EXISTING GAS PLANS ON FILE AT THE CITY SHOW A
 SUMMER KITCHEN WITH A 55,000 BTU LOAD BUT THIS IS NOT
 SHOWN ON THE SUBMITTED GAS DRAWING. REVISE THE GAS
 DRAWING TO REFLECT THE SUMMER KITCHEN AND REVISE THE
 TOTAL BTU LOAD ON THE GAS DOCUMENTS. WPB AMEND. TO FBC
 SEC. 107.2.1, 2017 FBC-FUEL GAS SEC.401.3, 401.4.
 2) THE SHUTOFF VALVE ON THE 3/4 INCH EXISTING LINE INTO
 THE STRUCTURE SHALL BE LOCATED IMMEDIATELY AHEAD OF THE
 REGULATOR. 2017 FBC-FUEL GAS SEC.409.4.
 3) SHOW THE DISTANCE FROM THE MP REGULATOR FOR THE
 EXISTING LINE INTO THE STRUCTURE TO THE MOST REMOTE GAS
 OUTLET ON THAT SECTION. THIS DISTANCE WILL DETERMINE
 THE PIPE SIZING.THE EXISTING PLANS ON FILE SHOW THE
 LONGEST RUN AS 100 FEET.
 4) THE EXISTING PLANS ON FILE AT THE CITY SHOW THE PIPE
 SIZE AT THE METER OUTLET AS 1 INCH AND THE SUBMITTED
 PLAN SHOWS 3/4 INCH. CLARIFY.
 5) SHOW THE PIPE SIZE OF THE PE ON THE GAS PLAN. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SHOW THE DISTANCE FROM THE METER TO THE REGULATOR
 FOR THE EXISTING LINE INTO THE STRUCTURE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By tklarge Date 2018-05-15 Time 05:59 Rev Time 0.00
Received By tklarge Date 2018-05-15 Time 05:18 Sent To I
Notes
2018-05-15 05:26:00 
 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE
 REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF
 THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE
 DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON
 THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD
 OF THE MP REGULATOR FFOR THE EXISTING LOADS.. 2017 FBCR
 SEC. G2420.4.
 5) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH
 GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND
 PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR
 SEC.G2415.9, G2415.11.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8).
 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017
 FBCR SEC.G2419.4.
 8) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE
 CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND.
 TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1.
 9) SUBMIT CLEAR AND LEGIBLE SPECIFICATIONS FOR THE
 GENERATOR. SOME AREAS ON THE SHEETS CANNOT BE READ. WPB
 AMEND. TO FBC SEC. 1107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-07-26 Time   Rev Time 0.00
Received By lmarchan Date 2018-07-16 Time 14:34 Sent To  
Notes
2018-07-17 14:34:43RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-29 Cont ID  
Sent By tklarge Date 2018-06-29 Time 07:57 Rev Time 0.00
Received By tklarge Date 2018-06-21 Time 13:13 Sent To I
Notes
2018-06-22 13:14:18RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-03 Cont ID  
Sent By tklarge Date 2018-06-03 Time 13:55 Rev Time 0.00
Received By tklarge Date 2018-05-29 Time 13:58 Sent To  
Notes
2018-05-30 13:58:22RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-15 Cont ID  
Sent By tklarge Date 2018-05-15 Time 06:00 Rev Time 0.00
Received By tklarge Date 2018-04-25 Time 13:29 Sent To  
Notes
2018-04-26 13:29:33ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 4 Status P Date 2018-07-23 Cont ID  
Sent By mcruz Date 2018-07-23 Time 08:46 Rev Time 0.00
Received By mcruz Date 2018-07-23 Time 08:40 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-06-26 Cont ID  
Sent By mcruz Date 2018-06-26 Time 15:57 Rev Time 0.00
Received By mcruz Date 2018-06-26 Time 15:54 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-31 Cont ID  
Sent By mcruz Date 2018-05-31 Time 16:41 Rev Time 0.00
Received By mcruz Date 2018-05-31 Time 16:40 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By ajones Date 2018-05-02 Time 12:12 Rev Time 0.00
Received By ajones Date 2018-05-02 Time 12:12 Sent To G
Notes
***NONE***