Plan Review Details - Permit 18041007
Plan Review Stops For Permit 18041007
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 06:34 Rev Time 0.00
Received By shill Date 2018-05-22 Time 06:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-05 Cont ID  
Sent By ppetty Date 2018-06-05 Time 14:55 Rev Time 0.00
Received By ppetty Date 2018-06-05 Time 14:52 Sent To  
Notes
2018-06-05 14:55:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 1. OK
 2.OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By jpearson Date 2018-05-09 Time 15:33 Rev Time 0.00
Received By jpearson Date 2018-05-09 Time 14:27 Sent To  
Notes
2018-05-09 15:33:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN NEEDS TO BE CLEAR AND LEGIBLE. THE ADDRESS
 BLOCK IS UNREADABLE, MANY OTHER ITEMS DIFFICULT TO
 READ. WPB FBC 107.2.1.3
 2. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 3. ELECTRICAL PANEL MUST HAVE PROPRER CLEARANCE.
 PROVIDE CORRECTION. NEC 110.26
 4. PROVIDE AFCI PROTECTION FOR ANY BRANCH CIRCUIT
 MODIFICATIONS. NEC 210.12(B)
 5. PROVIDE TAMPER RESISTANT RECEPTACLES. NEC 406.12
 6. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D)
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 8. RECEPTACLES IN KITCHEN REQUIRE GFCI AND AFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-27 Cont ID  
Sent By pleduc Date 2018-04-27 Time   Rev Time 0.00
Received By pleduc Date 2018-04-26 Time 12:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-05 Cont ID  
Sent By ppetty Date 2018-06-05 Time 14:56 Rev Time 0.00
Received By ppetty Date 2018-05-29 Time 13:33 Sent To  
Notes
2018-05-30 13:33:27RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 06:34 Rev Time 0.00
Received By shill Date 2018-04-23 Time 09:14 Sent To  
Notes
2018-04-24 09:14:20B10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-10 Cont ID  
Sent By ccole Date 2018-05-10 Time 08:09 Rev Time 0.00
Received By ccole Date 2018-05-10 Time 07:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-05-21 Cont ID  
Sent By tklarge Date 2018-05-21 Time 10:28 Rev Time 0.00
Received By tklarge Date 2018-05-21 Time 10:17 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved