Plan Review Details - Permit 18040798
Plan Review Stops For Permit 18040798
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-10 Cont ID  
Sent By skennedy Date 2018-08-10 Time 10:25 Rev Time 0.00
Received By skennedy Date 2018-08-10 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 13:00 Rev Time 0.00
Received By shill Date 2018-07-14 Time 13:00 Sent To  
Notes
2018-07-14 13:06:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION:
  
 FBC B 705.3, BUILDINGS ON THE SAME LOT, SHOW DISTANCE
 FROM PROPOSED SHED TO ASSUMED PROPERTY LINE (DISTANCE
 FROM EX. RESIDENCE #325 TO ASSUMED PROPERTY LINE,
 DISTANCE FROM PROPOSED STORAGE SHED TO ASSUMED PROPERTY
 LINE, SHOW COMPLIANCE FOR BOTH STRUCTURES)
  
 PLAN SHOWS 6' BUT DOES NOT INCLUDE INFORMATION
 REGARDING DISTANCE FROM EX. RESIDENCE #325 TO ASSUMED
 PROPERTY LINE.
  
 SINCE THE PROPOSED STRUCTURE DOES NOT APPEAR TO HAVE
 ANY OPENINGS ON THE SIDE FACING THE EXISTING STRUCTURE,
 IT IS SUGGESTED THAT THE ASSUMED PROPERTY LINE BE
 PLACED AT THE STRUCTURE TO GIVE MORE FLEXIBILITY FOR
 SHOWING COMPLIANCE FOR THE EXISTING WOOD STRUCTURE (IF
 PROPOSED CONSTRUCTION MEETS 2 HOUR REQUIREMENT). FOR
 INSTANCE, SEE FBC B TABLE 705.8, TABLE 602.
  
 NOTE THAT BUILDING TYPE CAN BE DECLARED AS THE MINIMUM
 REQUIRED BY CODE RATHER THAN ACTUAL CONSTRUCTION TYPE.
  
 SEE ALSO FBC B 705.3 EXCEPTION 1.
  
 PLEASE REVISE PLAN TO SHOW ANY FIRE RATINGS REQUIRED.
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 07:14 Rev Time 0.00
Received By shill Date 2018-05-22 Time 06:51 Sent To  
Notes
2018-05-22 07:14:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION:
  
 FBC B TABLE 504.4, TABLE 506.2 (BUILDING HEIGHT AND
 AREA)
 FBC B CHAPTER 6, BUILDING TYPE
 FBC B TABLE 602, FIRE RESISTANCE RATING REQUIREMENTS
 FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE
 FBC B 705.3, BUILDINGS ON THE SAME LOT, SHOW DISTANCE
 FROM PROPOSED SHED TO ASSUMED PROPERTY LINE (DISTANCE
 FROM EX. RESIDENCE #325 TO ASSUMED PROPERTY LINE,
 DISTANCE FROM PROPOSED STORAGE SHED TO ASSUMED PROPERTY
 LINE, SHOW COMPLIANCE FOR BOTH STRUCTURES)
 FBC B 1603.1.4, WIND DESIGN CRITERIA
 FBC 107, GOVERNING CODE
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-08-10 Cont ID  
Sent By jpearson Date 2018-08-10 Time 10:21 Rev Time 0.00
Received By jpearson Date 2018-08-10 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-20 Cont ID  
Sent By jpearson Date 2018-07-20 Time 16:00 Rev Time 0.00
Received By jpearson Date 2018-07-20 Time 16:00 Sent To  
Notes
2018-07-20 16:00:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD FOR PANEL OPHS ON SHEET ESH121.9 IS DIFFERENT
 THAN THE LOAD SPEICIFED ON SHEET E-200. CORRECT
 DISCREPANCY. NEC 220; WPB FBC 107.2.1
 2. PROVIDE GROUNDING OF TRANSFORMERS PER NEC 250.30.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-18 Cont ID  
Sent By jpearson Date 2018-05-18 Time 12:33 Rev Time 0.00
Received By jpearson Date 2018-05-18 Time 12:33 Sent To  
Notes
2018-05-18 12:33:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL. FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-07-25 Cont ID  
Sent By shill Date 2018-07-25 Time 15:50 Rev Time 1.00
Received By mgonzale Date 2018-07-25 Time 15:50 Sent To  
Notes
2018-08-02 15:17:33SHED POSES NO CONFLICTS WITH CITY OF WPB PUBLIC
 UTILITIES.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  
  
  
  
  
2018-07-25 15:51:09CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 06:56 Rev Time 0.00
Received By shill Date 2018-05-22 Time 06:56 Sent To  
Notes
2018-05-22 06:56:35CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-28 Cont ID  
Sent By scaldero Date 2018-06-28 Time 08:36 Rev Time 0.00
Received By scaldero Date 2018-06-28 Time 08:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By scaldero Date 2018-05-02 Time 09:26 Rev Time 0.00
Received By scaldero Date 2018-05-02 Time 09:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-05-30 Cont ID  
Sent By fmittner Date 2018-05-30 Time 14:27 Rev Time 0.00
Received By fmittner Date 2018-05-30 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-08-15 Cont ID  
Sent By cpuell Date 2018-08-15 Time 09:08 Rev Time 0.00
Received By cpuell Date 2018-08-02 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-30 Cont ID  
Sent By gjohnson Date 2018-07-30 Time 16:51 Rev Time 0.00
Received By gjohnson Date 2018-06-19 Time 07:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-05 Cont ID  
Sent By gjohnson Date 2018-06-05 Time 16:59 Rev Time 0.00
Received By gjohnson Date 2018-04-30 Time 16:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-23 Cont ID  
Sent By lmarchan Date 2018-04-23 Time 12:46 Rev Time 0.00
Received By lmarchan Date 2018-04-18 Time 08:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-08-15 Cont ID  
Sent By cpuell Date 2018-08-15 Time 09:07 Rev Time 0.00
Received By cpuell Date 2018-08-15 Time 09:07 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 06:54 Rev Time 0.00
Received By shill Date 2018-05-22 Time 06:54 Sent To  
Notes
2018-05-22 06:55:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-11 Cont ID  
Sent By ccole Date 2018-07-11 Time 16:22 Rev Time 0.00
Received By ccole Date 2018-07-11 Time 16:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-14 Cont ID  
Sent By ccole Date 2018-05-14 Time 15:51 Rev Time 0.00
Received By ccole Date 2018-05-14 Time 15:51 Sent To  
Notes
2018-05-14 16:10:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18040798
 5/14/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC-EC.
  
 2) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW
 CONDITIONED BUILDING ADDITION- SECTION C101.3 &
 C101.5.1 FBC-EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 PLAN REVIEW RESULTS: DENIED.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-30 Cont ID  
Sent By gjohnson Date 2018-07-30 Time 16:49 Rev Time 0.00
Received By gjohnson Date 2018-07-30 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By gjohnson Date 2018-06-05 Time 16:51 Rev Time 0.00
Received By gjohnson Date 2018-06-05 Time 16:51 Sent To  
Notes
2018-06-05 16:59:361ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. WHAT TYPE OF WATER IS DISCHARGING TO THE PITS AND
 WHAT TYPE WILL DISCHARGE TO THE FLOOR DRAIN IN SHED THE
 FOLLOWING SHALL NOT DISCHARGE TO THE SANITARY SYSTEM
 STORM WATER, POOL OR FOUNTAIN WATER, WELL WATER OR ANY
 UNTREATED WATER PER WEST PALM BEACH, FLORIDA - CODE OF
 ORDINANCES
 / CHAPTER 90 - UTILITIES
 / ARTICLE III. - SEWERS AND SEWAGE DISPOSAL
 SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF
 DISCHARGE.(5)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-08-10 Cont ID  
Sent By skennedy Date 2018-08-10 Time 10:24 Rev Time 0.00
Received By skennedy Date 2018-08-10 Time 10:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 13:07 Rev Time 0.00
Received By shill Date 2018-07-14 Time 13:07 Sent To  
Notes
2018-07-14 13:07:57ALL DIGITAL SIGNATURE/SEALS ARE IN ACCORDANCE WITH
 FS471, FS481.
 NEW PAGES SUBMITTED FOR A 3RD REVIEW CYCLE NEED
 VERIFICATION
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 07:17 Rev Time 0.00
Received By shill Date 2018-05-22 Time 06:51 Sent To  
Notes
2018-05-22 07:18:02ALL DIGITAL SIGNATURE/SEALS ARE IN ACCORDANCE WITH
 FS471, FS481.
 NEW PAGES SUBMITTED FOR A 2ND REVIEW CYCLE NEED
 VERIFICATION
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-08-10 Cont ID  
Sent By jroach Date 2018-08-10 Time 11:23 Rev Time 0.00
Received By jroach Date 2018-08-10 Time 11:23 Sent To  
Notes
2018-08-10 11:23:18ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.10.2018
 PERMIT NO.: 18040798
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THIS SCOPE OF THIS PERMIT REVIEW IS FOR THE
 CONSTRUCTION OF THE PROPOSED SHED ONLY! ALL OTHER WORK
 SHALL CONFORM TO THE ASSOCIATED PERMITS AND
 PROVISOS/CONDITIONS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-07-24 Cont ID  
Sent By jroach Date 2018-07-24 Time 14:57 Rev Time 0.00
Received By jroach Date 2018-07-24 Time 14:57 Sent To  
Notes
2018-07-24 15:06:12ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.24.2018
 PERMIT NO.: 18040798
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SETBACKS FOR THE PROPOSED SHED SHALL BE PROVIDED.
 THE DIMENSIONS SHALL INDICATE THE DISTANCE BETWEEN THE
 SHED AND THE PROPERTY LINES ALONG CRANESNEST WAY AND
 SOUTH DIXIE HIGHWAY. THE RESUBMITTED PLANS ONLY PROVIDE
 A DIMENSION TO CRANESNEST, AND WERE FROM THE SCREEN
 WALL, NOT THE SHED STRUCTURE. PLEASE NOTE THAT PURUSANT
 TO THE APPROVED SITE PLAN, THE SHED IS TO BE A MINIMUM
 OF 25 FEET 3 INCHES FROM CRANESNEST WAY AND
 APPROXIMATELY 52 FEET FROM SOUTH DIXIE HIGHWAY. PLEASE
 REFER TO SHEET L-201 PREPARED BY FOSTER+PARTNERS.
  
 2. PLANS INDICATE THAT A UTILITY EASEMENT IS RUNNING
 UNDER THE PROPOSED BUILDING....PLEASE EXPLAIN WHO THIS
 EASEMENT BELONGS TO? IS THIS A GENERAL PUBLIC UTILITY
 EASEMENT? IS IT PRIVATE? EASEMENT CONSENT MAY BE
 REQUIRED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-24 Cont ID  
Sent By JR Date 2018-05-24 Time 10:28 Rev Time 0.00
Received By jroach Date 2018-05-24 Time 10:28 Sent To  
Notes
2018-05-24 10:28:41ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.24.2018
 PERMIT NO.: 18040798
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE THE LAYOUT PLAN SHOWING THE LOCATION
 OF THE SHED WITH SETBACK DIMENSIONS TO ALL PROPERTY
 LINES, ETC. I BELIEVE THIS IS SHEET L-201 OF THE
 PACKAGE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved