Plan Review Stops For Permit 18040798 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-08-10 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-08-10 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-07-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-14 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-14 |
Time |
13:00 |
Sent To |
|
|
Notes |
2018-07-14 13:06:50 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION: | | | | FBC B 705.3, BUILDINGS ON THE SAME LOT, SHOW DISTANCE | | FROM PROPOSED SHED TO ASSUMED PROPERTY LINE (DISTANCE | | FROM EX. RESIDENCE #325 TO ASSUMED PROPERTY LINE, | | DISTANCE FROM PROPOSED STORAGE SHED TO ASSUMED PROPERTY | | LINE, SHOW COMPLIANCE FOR BOTH STRUCTURES) | | | | PLAN SHOWS 6' BUT DOES NOT INCLUDE INFORMATION | | REGARDING DISTANCE FROM EX. RESIDENCE #325 TO ASSUMED | | PROPERTY LINE. | | | | SINCE THE PROPOSED STRUCTURE DOES NOT APPEAR TO HAVE | | ANY OPENINGS ON THE SIDE FACING THE EXISTING STRUCTURE, | | IT IS SUGGESTED THAT THE ASSUMED PROPERTY LINE BE | | PLACED AT THE STRUCTURE TO GIVE MORE FLEXIBILITY FOR | | SHOWING COMPLIANCE FOR THE EXISTING WOOD STRUCTURE (IF | | PROPOSED CONSTRUCTION MEETS 2 HOUR REQUIREMENT). FOR | | INSTANCE, SEE FBC B TABLE 705.8, TABLE 602. | | | | NOTE THAT BUILDING TYPE CAN BE DECLARED AS THE MINIMUM | | REQUIRED BY CODE RATHER THAN ACTUAL CONSTRUCTION TYPE. | | | | SEE ALSO FBC B 705.3 EXCEPTION 1. | | | | PLEASE REVISE PLAN TO SHOW ANY FIRE RATINGS REQUIRED. | | | | PLEASE CONTACT ME IF YOU WISH TO DISCUSS. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-05-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-22 |
Time |
07:14 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-22 |
Time |
06:51 |
Sent To |
|
|
Notes |
2018-05-22 07:14:49 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. REVISE PLAN TO INCLUDE THE FOLLOWING INFORMATION: | | | | FBC B TABLE 504.4, TABLE 506.2 (BUILDING HEIGHT AND | | AREA) | | FBC B CHAPTER 6, BUILDING TYPE | | FBC B TABLE 602, FIRE RESISTANCE RATING REQUIREMENTS | | FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE | | FBC B 705.3, BUILDINGS ON THE SAME LOT, SHOW DISTANCE | | FROM PROPOSED SHED TO ASSUMED PROPERTY LINE (DISTANCE | | FROM EX. RESIDENCE #325 TO ASSUMED PROPERTY LINE, | | DISTANCE FROM PROPOSED STORAGE SHED TO ASSUMED PROPERTY | | LINE, SHOW COMPLIANCE FOR BOTH STRUCTURES) | | FBC B 1603.1.4, WIND DESIGN CRITERIA | | FBC 107, GOVERNING CODE | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-08-10 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-08-10 |
Time |
10:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-07-20 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-07-20 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-07-20 |
Time |
16:00 |
Sent To |
|
|
Notes |
2018-07-20 16:00:22 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. LOAD FOR PANEL OPHS ON SHEET ESH121.9 IS DIFFERENT | | THAN THE LOAD SPEICIFED ON SHEET E-200. CORRECT | | DISCREPANCY. NEC 220; WPB FBC 107.2.1 | | 2. PROVIDE GROUNDING OF TRANSFORMERS PER NEC 250.30. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-05-18 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-05-18 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-05-18 |
Time |
12:33 |
Sent To |
|
|
Notes |
2018-05-18 12:33:43 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY A LICENSED DESIGN PROFESSIONAL. FS | | 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2018-07-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-25 |
Time |
15:50 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2018-07-25 |
Time |
15:50 |
Sent To |
|
|
Notes |
2018-08-02 15:17:33 | SHED POSES NO CONFLICTS WITH CITY OF WPB PUBLIC | | UTILITIES. | | | | MANNY GONZALEZ | | SENIOR ENGINEERING PROJECT COORDINATOR | | PUBLIC WORKS DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | EMAIL: [email protected] | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | /FORMS,-PERMITS-APPLICATIONS | | | | | | | | | | | | | 2018-07-25 15:51:09 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | APPLICATION IF REQUIRED | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | /FORMS,-PERMITS-APPLICATIONS | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | MAIN PHONE: (561) 822-1200 | | | | | | | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2018-05-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-22 |
Time |
06:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-22 |
Time |
06:56 |
Sent To |
|
|
Notes |
2018-05-22 06:56:35 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | APPLICATION IF REQUIRED | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | /FORMS,-PERMITS-APPLICATIONS | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | MAIN PHONE: (561) 822-1200 | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-06-28 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-06-28 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-06-28 |
Time |
08:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2018-05-02 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2018-05-02 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2018-05-02 |
Time |
09:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2018-05-30 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2018-05-30 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2018-05-30 |
Time |
14:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2018-08-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-08-15 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-08-02 |
Time |
11:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-07-30 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-07-30 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-19 |
Time |
07:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-06-05 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-05 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-04-30 |
Time |
16:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-04-23 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2018-04-23 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-04-18 |
Time |
08:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2018-08-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-08-15 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-08-15 |
Time |
09:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2018-05-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-22 |
Time |
06:54 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-22 |
Time |
06:54 |
Sent To |
|
|
Notes |
2018-05-22 06:55:54 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED. | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | THAT FEES DUE, IF APPLICABLE, PROVIDED. | | | | 561-233-5025 FOR MORE INFORMATION | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-07-11 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-07-11 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-07-11 |
Time |
16:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-05-14 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-05-14 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-05-14 |
Time |
15:51 |
Sent To |
|
|
Notes |
2018-05-14 16:10:21 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18040798 | | 5/14/18 | | | | CODES IN EFFECT: | | FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | AC SYSTEM- SECTION C403.2.1 FBC-EC. | | | | 2) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW | | CONDITIONED BUILDING ADDITION- SECTION C101.3 & | | C101.5.1 FBC-EC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | PLAN REVIEW RESULTS: DENIED. | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-07-30 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-07-30 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-07-30 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-06-05 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-06-05 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-06-05 |
Time |
16:51 |
Sent To |
|
|
Notes |
2018-06-05 16:59:36 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. WHAT TYPE OF WATER IS DISCHARGING TO THE PITS AND | | WHAT TYPE WILL DISCHARGE TO THE FLOOR DRAIN IN SHED THE | | FOLLOWING SHALL NOT DISCHARGE TO THE SANITARY SYSTEM | | STORM WATER, POOL OR FOUNTAIN WATER, WELL WATER OR ANY | | UNTREATED WATER PER WEST PALM BEACH, FLORIDA - CODE OF | | ORDINANCES | | / CHAPTER 90 - UTILITIES | | / ARTICLE III. - SEWERS AND SEWAGE DISPOSAL | | SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF | | DISCHARGE.(5) | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-08-10 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-08-10 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2018-07-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-07-14 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-07-14 |
Time |
13:07 |
Sent To |
|
|
Notes |
2018-07-14 13:07:57 | ALL DIGITAL SIGNATURE/SEALS ARE IN ACCORDANCE WITH | | FS471, FS481. | | NEW PAGES SUBMITTED FOR A 3RD REVIEW CYCLE NEED | | VERIFICATION | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2018-05-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-05-22 |
Time |
07:17 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-05-22 |
Time |
06:51 |
Sent To |
|
|
Notes |
2018-05-22 07:18:02 | ALL DIGITAL SIGNATURE/SEALS ARE IN ACCORDANCE WITH | | FS471, FS481. | | NEW PAGES SUBMITTED FOR A 2ND REVIEW CYCLE NEED | | VERIFICATION | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-08-10 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2018-08-10 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2018-08-10 |
Time |
11:23 |
Sent To |
|
|
Notes |
2018-08-10 11:23:18 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 08.10.2018 | | PERMIT NO.: 18040798 | | ___________________________________________ | | | | REVIEW STATUS: PASSED WITH PROVISOS | | ___________________________________________ | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. THIS SCOPE OF THIS PERMIT REVIEW IS FOR THE | | CONSTRUCTION OF THE PROPOSED SHED ONLY! ALL OTHER WORK | | SHALL CONFORM TO THE ASSOCIATED PERMITS AND | | PROVISOS/CONDITIONS. | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-07-24 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2018-07-24 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2018-07-24 |
Time |
14:57 |
Sent To |
|
|
Notes |
2018-07-24 15:06:12 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 07.24.2018 | | PERMIT NO.: 18040798 | | ___________________________________________ | | | | REVIEW STATUS: FAILED | | ___________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. SETBACKS FOR THE PROPOSED SHED SHALL BE PROVIDED. | | THE DIMENSIONS SHALL INDICATE THE DISTANCE BETWEEN THE | | SHED AND THE PROPERTY LINES ALONG CRANESNEST WAY AND | | SOUTH DIXIE HIGHWAY. THE RESUBMITTED PLANS ONLY PROVIDE | | A DIMENSION TO CRANESNEST, AND WERE FROM THE SCREEN | | WALL, NOT THE SHED STRUCTURE. PLEASE NOTE THAT PURUSANT | | TO THE APPROVED SITE PLAN, THE SHED IS TO BE A MINIMUM | | OF 25 FEET 3 INCHES FROM CRANESNEST WAY AND | | APPROXIMATELY 52 FEET FROM SOUTH DIXIE HIGHWAY. PLEASE | | REFER TO SHEET L-201 PREPARED BY FOSTER+PARTNERS. | | | | 2. PLANS INDICATE THAT A UTILITY EASEMENT IS RUNNING | | UNDER THE PROPOSED BUILDING....PLEASE EXPLAIN WHO THIS | | EASEMENT BELONGS TO? IS THIS A GENERAL PUBLIC UTILITY | | EASEMENT? IS IT PRIVATE? EASEMENT CONSENT MAY BE | | REQUIRED. | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-05-24 |
|
|
Cont ID |
|
Sent By |
JR |
Date |
2018-05-24 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2018-05-24 |
Time |
10:28 |
Sent To |
|
|
Notes |
2018-05-24 10:28:41 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 05.24.2018 | | PERMIT NO.: 18040798 | | ___________________________________________ | | | | REVIEW STATUS: FAILED | | ___________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PLEASE PROVIDE THE LAYOUT PLAN SHOWING THE LOCATION | | OF THE SHED WITH SETBACK DIMENSIONS TO ALL PROPERTY | | LINES, ETC. I BELIEVE THIS IS SHEET L-201 OF THE | | PACKAGE. | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|